Broadcaster Setup
13
Alert Suspend Time
The time after an alert has been Acknowledged to go back to inactive or call/text if still active. The maximum
suspend time is 29:50 (min:seconds).
1. From the Setup Menu screen, select General.
2. Select Alert Suspend Time.
3. Enter the Alert Suspend time.
4. Press Enter to Save.
Alert Digital Inputs Naming
You can name up to eight different alert inputs. These inputs are normally open. See diagram wiring for proper
wiring to the inputs. A specific name can be assigned to inputs by selecting (Other) from the Input Name List.
The landline modem will only voice the names in the list.
1. From the Setup Menu screen, select General.
2. Select Input Names.
3. Select the Input you want to name/rename.
4. Select a Name for the Input from the list. Available Input names are Other, Gen Temp, Gen Batt, Low fuel,
SP, Max Temp, Min Temp, Temp, Door 2, Door 1, Water press, Gen Sw, Gen, Input01, Input02, Input03,
Input04, Input05, Input06, Input07, and Input08.
5. If "Other" is selected use the Keypad and Arrow Buttons to enter each letter or number. (The maximum of
letters and numbers is eight.)
6. Press Enter to Save.