FS-8705-12 Federal Signal Ultravoice - Electronic Siren Controllers Driver Manual
Page 11 of 30
© 2021 CHIPKIN AUTOMATION SYSTEMS
Example
//
Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Data_Bits,
Stop_Bits
P1,
FSU_ESC,
1200,
Even,
8,
1
4.3
Client Side Node Descriptors
Create one Node per connection only.
SECTION TITLE
Nodes
COLUMN TITLE
FUNCTION
LEGAL VALUES
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Node_ID
Station address of physical server
node
This parameter is not used directly
by the driver. We recommend that
a unique Node ID’s be given to
each node.
1-258
Protocol
Specify protocol used
FSU_ESC
Connection
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
2
Example
// Client Side Nodes
Nodes
Node_Name
Node_ID
Protocol
Connection
SirenNode
1
FSU_ESC
P1
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports
available on specific hardware.