Wireless Fire Alarm Smoke Detector

Installation

 

Instructions

1.Product Introduction

This wireless photoelectric fire alarm smoke detector adopts 
unique structure design and MCU processing to photoelectric 
signal in order to increase the functions of anti dust, insects 
and white light interference to guarantee the stability. At the 
same time, this detector is with wireless net linkage function 
and suitable for different environments installation, which 
has greatly increased users' sense for smoke alarm signal. 
It is with better response to visible smoke caused by smoldering 
and burning so it is suitable for fire alarm protection in 
residential area, supermarket, factory, office, school, bank, 
library, hotels, warehouse etc. Its functions and stability is 
much better than those smoke detectors with similar prices 
in the market

-Elegant appearance design
-Stable, safe and reliable
-Adopts super low power consumption processor and 
  software calculation
-Unique self-check function
-Lower power check and remind
-Anti RFI/EMI interference
-Adopts advanced SMT technology
-Detection range reaches 40

 when installed at 2.3-6m;

                                                                        60

 at 6-12m 

2.Main functions

3.Technical Parameter

5.Installation And Internal Parts

This detector adopts plastic base direct installation

Power input: 3

.

6V 1/2AA

 

lithium battery

Current: <10uA (stand

 

by)   <20mA(in

 

alarm)

Installation way: ceiling mount
Alarm threshold: 5

-

25% obs/m  

Self check: according to client's requirements(H)
Alarm volume: >85dB (3m ahead)
Alarm period: continuous trigger till smoke disappear 
Low voltage alarm triggered: at 2.8V
Wireless distance:

300m (open

 

space)

Frequency: 315/433MHz etc.
Encoding: Ev1527 or Pt2262
Anti REI/EMI: 1-500MHz/10V/m

Operation temperature : -10

/+55

Operation humidity :95% RH

Dimensions:

φ

101mm×44mm

6m

4.Installation Guide And Operation Principle

1.When installation height is less than 6m, and 
   detector is installed on diaphragm, the distance 
   from lower surface of detector to ceiling can't 
   be over 0.3m
2.Distance from detector to ventilation hole must 
   be more than 1.5m when there is air-conditioner 
   in the room
3.Detector must be installed at 0.6m over the wall 
   or girder.

Detector's protection range and calculation on how 
many detectors should be installed in a space

Can get detection range of 40m² when 

installed at the height of 2.3-6m

12m

+  -

Plastic base

Installation 

bayonet

Screw hole

Installation 

slip hook

Press down TEST button for 0.5 second, buzzer will 
send out one “Di” sound and then send out wireless 
smoke alarm signal
Keep pressing down the TEST button, buzzer will 
send out three “Di, Di, Di” sounds and repeat this 
each 1.5 seconds, then red alarm LED keeps on, that 
means detector is working well, detector will return 
to normal working status after release of TEST button

Optical maze

Fit for installation in: 

Residential area, cafe, KTV, hotel, restaurant, 
apartment, trattoria etc.

Not suitable for: 

place full of dust, powder and plenty vapour; 

place that might be with corrosive gas; 

kitchen and other place that might with smoke remain; 

place with oversized temperature and humidity; 

place with ventilation speed over 15m/sec

Detector's detection to smoke can be fulfilled by 
optical maze, there are a pair of infrared transmitter
and receiver, their ejection angle is around 120°, 
when there is no smoke, receiver can't receive the 
infrared light from transmitter, so there will be no 
voltage output from following circuit. When there 
is smoke, smoke enters the maze and scatters the 
infrared light from transmitter. Receiver receives 
the scattered infrared light and makes voltage output 
at the following circuit, the thicker the smoke is, 
the stronger scattering is, and the higher voltage is. 
When the voltage reaches preset value, detector 
sends out alarm signal and alarm is triggered.

Detector operation principle:

Adjustment

Installation position must satisfy following 
requirements:

PUSH

 

TO

TEST

 

WEEKLY

ANUAL  F

  M

O

`S

R

R

  

E

O

N

P

W

ER

 O

A

 

T

O

IN

 T

 

N

R

G

E

 

F

 IN

E

S

 R

 

T

:

R

T

U

N

C

A

T

T

R

IO

O

N

P

S

MI

Buzzer

LED

Test button

Can get detection range of 60m² when 

installed at the height of 6-12m

Detector

When target space height is 6-12m, protection 
range is 60

Battery cover

Accessories

Buzzer output

Battery input

Battery box

(with bat)

Data set

Transmission
antenna(315M or 433M)

Buzzer

When target space height is below 6m, protection 
range is 40

Detection range

Protection area for each detector

Detector quantity=