Chapter 4
Configuring
Settings
(
MODE SELECT Mode
)
CMN612-002
原本
(Original instructions)
51
E
nglis
h
4.3
Communication Format Setting Mode (When
Equipped with Communication Function)
This mode sets the below listed items of serial communication format.
The settings are enabled after the main power switch is turned off and back on.
Item
Setting
Default
Communication station number
1 to 25
1
Baud rate
9600 bps, 19200 bps,
38400 bps, 57600 bps,
115200 bps
9600 bps
Bit length and parity
Bit length = 8 bits, with no parity
Bit length = 8 bits, odd parity
Bit length = 8 bits, even parity
Bit length = 9 bits, with no parity
Bit length = 8 bits, with no parity
Stop bit
Stop bit = 1 bit
Stop bit = 2 bits
Stop bit = 1 bit
1.
Move to the MODE SELECT mode.
2.
Press the Up/Down arrow buttons to move to the communication format setting mode
(“Com Setting”).
3.
Press the ENTER button.
The communication station number check screen appears, showing the current settings.
4.
Press the Up/Down arrow buttons to move to the item you want to set.
5.
Press the ENTER button.
The setting screen appears.
6.
Press the Up/Down arrow buttons to select the desired setting.
7.
Press the ENTER button to determine the setting.
8.
To exit this mode, press the MODE SELECT button to return to normal mode.
4.4
Air Volume-Down Alert Timing Setting Mode
This mode allows for changing the timing for displaying an air volume-down warning (WARN4) as desired.
1.
Move to the MODE SELECT mode.
2.
Press the Up/Down arrow buttons to move to the air volume-down alert timing setting mode
(“Volume Down ST”).
3.
Press the ENTER button.
The current setting appears.
The default is 50%, displayed as “3: Down to 50%”.
4.
Press the Up/Down arrow buttons to select a timing between 30 to 70%.
A lower setting causes the air volume-down alert to occur later, and vice versa.
5.
Press the ENTER button to determine the setting.
6.
To exit this mode, press the MODE SELECT button to return to normal mode.