- 22 -
Output terminal board
The output terminal board is situated below the
control and indicator panel.
S2 ....... Emergency stop button
X1 ....... Terminal board
Provides a more easy connection of cables.
X2 ....... Single phase outlet socket (240V)
Socket rated to 50A.
Provides L1,L2, neutral and earthing.
X3 ....... Single phase outlet socket (240V)
Socket rated to 50A.
Provides L1,L2, neutral and earthing.
X4 ....... Single phase GFCI outlet socket
(120V). Socket rated to 20A.
X5 ....... Single phase GFCI outlet socket
(120V). Socket rated to 20A.
Q1.1 ....Circuit breaker for low voltage, high
current
Interrupts the low voltage power supply
towards X1 when a short-circuit occurs at
the load side or when the overcurrent
protection (364 A) is activated. It must be
reset manually after eliminating the
problem.
Q1.2 ....Circuit breaker for high voltage, low
current
Interrupts the high voltage power supply
towards X1 when a short-circuit occurs at
the load side or when the overcurrent
protection (172 A) is activated. It must be
reset manually after eliminating the
problem.
Q2 ....... Circuit breaker for X2
Interrupts the power supply to X2 when a
short-circuit occurs at the load side, or when
the overcurrent protection (50 A) is
activated. When activated, Q2 interrupts one
phase towards X2. It can be activated again
after eliminating the problem.
Q3 .......Circuit breaker for X3
Interrupts the power supply to X3 when a
short-circuit occurs at the load side, or when
the overcurrent protection (50 A) is
activated. When activated, Q3 interrupts 2
phases towards X3. It can be activated again
after eliminating the problem.
Q4 .......Circuit breaker for X4
Interrupts the power supply to X4 when a
short-circuit occurs at the load side, or when
the overcurrent protection (20 A) is
activated. When activated, Q4 interrupts 2
phases towards X4. It can be activated again
after eliminating the problem.
Q5 .......Circuit breaker for X5
Interrupts the power supply to X5 when a
short-circuit occurs at the load side, or when
the overcurrent protection (20 A) is
activated. When activated, Q5 interrupts 2
phases towards X5. It can be activated again
after eliminating the problem.
Circuit breakers Q1.1 do not only
interrupt the power supply towards
socket X1 but also towards X2, X3,
X4 and X5.
Make sure to switch on circuit
breakers Q1.1, Q2, Q3, Q4 and Q5
after starting the generator when
power supply is done by means of
X2, X3, X4 or X5.
Summary of Contents for CPG 90-120 JD
Page 1: ...CPG 90 120 JD Instruction Manual for AC Generators English ...
Page 2: ......
Page 19: ... 19 This is the described menu flow for changing the unit type ...
Page 47: ... 47 Circuit diagrams ...
Page 48: ... 48 1310 3200 01 00 Applicable for CPG 90 120 John Deere Power circuit ...
Page 49: ... 49 ...
Page 51: ... 51 ...
Page 52: ... 52 1310 3200 00 00 Applicable for CPG 90 120 John Deere Engine circuit Qc1002TM ...
Page 53: ... 53 ...
Page 55: ... 55 ...
Page 56: ...Printed in Belgium 04 2010 1310 3012 23 www cp com ...