Z4-SERIES SEISMICFRAME PDU BRACKET
Page 2 of 2
Installation Instructions
1. Position the PDU Adapter Bracket at the desired location along the
cabinet slides. Fasten bracket using M6 X 20mm Taptite FH into the top
and bottom slides (Fig. 3, detail). Torque to 168 in-lb (19 N-m).
2. Align the PDU bracket to the adapter bracket in the correct orientation.
The top of the bracket is indicated by a punched arrow (Fig. 2, detail).
3. Fasten the PDU Bracket using M6 X 20mm Taptite FH into adapter
bracket (Fig. 4, detail). Torque to 168 in-lb (19 N-m).
Slides
Front side
of the
cabinet
M6 X 20mm
Taptite FHCSK
TORX Screw
Slides
PDU adapter
bracket
PDU adapter
bracket
M6 X 20mm
Taptite FHCSK
TORX Screw
Fig. 3
Adapter Bracket Installation
Slides
M6 X 20mm
Taptite FHCSK
TORX Screw
PDU mounting
bracket
Slides
PDU mounting
bracket
M6 X 20mm
Taptite FHCSK
TORX Screw
Fig. 4