Chatsworth Products Floor Supported Cube-It Installation Instructions Download Page 5

 

 

FLOOR SUPPORTED CUBE-IT 

 

Page 5 of 5

 

Installation Instructions 

Grounding Wire 

1.  Use M5.5 self-tapping Torx screws, star washers, and grounding wire to 

electrically bond center chassis to rear panel using any accessory holes. 

 

Cable Access 

1.  Per cabling requirements removable cable knockouts are provided on top and 

bottom of rear panel. Knockouts are removed using a large flat-head screw driver. 

2.  Use provided rubber grommets on large knockouts. Alternatively, large knockouts 

will accommodate 2-1/2” metal conduit.  Small knockouts accommodate ¾” metal 
conduit. 

 

Equipment Rail Adjustment 

1.  Loosen M8 bolts, star washers, and hex nuts to move equipment rails to 

desired depth spacing. 

2.  Tighten M8 bolts, star washers, and hex nuts to secure equipment rails. 

 

Ground Jumper Wire 

(P/N 40159-009 sold separately) 

1.  Remove paint mask from grounding emboss with two holes. 
2.  Install ground jumper wire using two black M6 Torx TAPTITE screws. 
3.  Place grounding label next to ground emboss. 

 

 

Cable Fill 

Rubber Grommet 

3in Knockout 

1in Knockout 

Grounding Emboss 

Black M6 Torx Screw 

Ground Jumper Wire 

Grounding Label 

M8 Carriage Bolt 

Star Washer 

M8 Hex Nut 