background image

The fire should be riddled with all
doors shut. Place the tool on the knob
and rotate between the horizontal and
the 45 degree position several times as
shown in Fig. 3.

When burning wood or peat do not
riddle all the ash into the ashpan,
keep a layer about 12 mm (1/2 inch)
thick on the grate.

Caution: when riddling the grate
using solid fuel do not go beyond the
45 degree position as this can cause
the grate to jam.

If jamming does occur then the fire
should be allowed to burn for
approximately half an hour before
riddling the grate again as described
above.

Too much riddling can result in
emptying unburnt fuel into the ashpan
and should therefore be avoided.
Clinker should regularly be removed
from the firebed.

After riddling, the grate should be put
back into the solid fuel or wood

position as required (the tool should
be horizontal for solid fuel or vertical
for wood or peat).

REFUELLING

Keep the firebox well filled (the fuel
may be sloped up from the front
firebars), but do not allow fuel to spill
over the top of the front fire bars.
Take care, especially when burning
wood, that fuel does not project over
the front fire bars or damage to the
glass may be caused when the doors
are closed.

OVERNIGHT

BURNING

Empty the ashpan, if necessary, and
then riddle the fire if you are burning
solid fuel. If the fire is very low then
it may be necessary to add a little fuel
and turn the thermostat control up to
maximum for a brief period until the
fire is burning brightly before filling
with fuel. When burning wood use
large logs overnight as they will burn
more slowly than small ones.

If the central heating pump is off
overnight then the thermostat may be
left at the same setting for both day
and night operation. If the central
heating pump is on overnight then set
the thermostat control to give the
required level of heating.

Some experimentation may be
necessary to find the setting most
suitable for the particular fuel used
and the draw on the chimney.

For overnight burning the fire doors
must be closed.

To revive the fire, empty the ashpan if
necessary, riddle, (when burning solid
fuel), and turn the thermostat control
knob to maximum. When the fire is
burning well load on more fuel as
necessary and turn the control knob to
the desired setting.

When burning wood do not riddle but
simply turn the air control to
maximum until the fire picks up and
then set the air control at the desired
setting and refuel as necessary.

THROAT PLATE AND

FLUEWAY CLEANING

It is important that the throat plate
and all the appliance flueways are

kept clean. When burning smokeless
fuels they should be cleaned monthly.
When burning other fuels they should
be cleaned at least once a week, and
more frequently if necessary.

The throat plate and flueways may be
cleaned with a low fire still burning.
Lower the throat plate using the throat
plate tool. To do this engage the end
of the tool in the throat plate as shown
in Fig.4., pull the plate forward and
then lower it. Use the scraper tool to
push any sooty deposits up the plate
until they fall off the back and into the
fire. While the throat plate is in the
lowered position also scrape any soot
deposits from the sides and top of the
firebox.

Ensure that soot deposits are

not allowed to build up on the side
boiler faces because if the throat
plate becomes tight between the
faces this can cause it to fail
prematurely.

Return the throat plate to its correct
position - raise the front of the plate,
push it back and then lower it onto the
retaining lugs. The upper set of lugs
are for use when burning smokeless
fuels and the lower set of lugs are for
use when burning coal, wood or peat
(see Fig. 4.).

More soot will be deposited on the
throat plate and in the flueways if the
appliance is run at low levels for long
periods. If this is the case then more
frequent cleaning will be necessary.

SPECIAL POINTS

WHEN BURNING

COAL

When burning housecoal keep the
throat plate in the lower position and
the secondary air control open all the
time (refer to Fig 4. and Fig 2.).

When loading the appliance take care
not to smother the fire, instead fill the
firebox in two stages waiting between
each stage for the flames to appear
above the fire.

After a period of slumbering always
turn the air control up to maximum
and wait until flames appear above the
fuel bed before opening the doors.

Burning coal will produce more soot
deposits than other fuels, especially if
the fire is run at low levels for long
periods. It is therefore vital to clean
the throat plate regularly, daily

C

W

Fig. 3. Grate Operation

For Wood

Do Not Go Beyond
45° Position

When Riddling

Riddle Between
Horizontal &

45° Positions

Tool To Be
Horizontal
For Solid Fuel

Vertical

Tool to be

Page 4

DX50iB 3/99

Summary of Contents for DX45iB

Page 1: ...rating and Installation Instructions Charnwood DX45iB DX50iB Multifuel Roomheater With Boiler Bishops Way Newport Isle Of Wight PO3O 5WS U K Tel 01983 537799 Fax 01983 537788 E Mail charnwood ajwells co uk ...

Page 2: ...y Cleaning 4 Special Points When Burning Coal 4 Maintenance 5 Chimney Sweeping 5 Trouble Shooting 5 Installation Instructions Health Safety Precautions 7 Performance 7 Chimney 7 Hearth 8 Preparation Of Fireplace 8 Central Heating System 8 System Controls 9 Fitting The Fire 9 Flue Connection Infilling 9 Thermostat 10 Assembly 10 Pre Lighting Check 10 Commissioning 10 Overall Dimensions 11 Exploded ...

Page 3: ...soned wood should be burnt on this appliance as burning wet unseasoned wood will give rise to heavy tar deposits For the same reason hard wood is better than soft wood Burning wet unseasoned wood will also result in considerably reduced outputs The wood should be cut and split and then left to season in a well ventilated dry place for at least one year but preferably two years before use Peat Ensu...

Page 4: ...when the doors are open than fuels like phurnacite sunbrite and ancit For safety reasons use a spark guard and do not leave the fire unattended with the doors open SYSTEM CONTROLS The heating system controls may consist of time switches room thermostats outdoor temperature thermostats and thermostatic radiator valves in virtually any combination These will work in conjunction with the thermostat c...

Page 5: ...etting When burning wood do not riddle but simply turn the air control to maximum until the fire picks up and then set the air control at the desired setting and refuel as necessary THROAT PLATE AND FLUEWAY CLEANING It is important that the throat plate and all the appliance flueways are kept clean When burning smokeless fuels they should be cleaned monthly When burning other fuels they should be ...

Page 6: ... sweep the chimney ensuring that soot is removed from all horizontal surfaces after sweeping In situations where it is not possible to sweep through the appliance the installer will have provided alternative means such as a soot door After sweeping the chimney the appliance flue outlet and the flue pipe connecting the appliance to the chimney must be cleaned with a flue brush After clearing any so...

Page 7: ...ney Fires If the chimney is thoroughly and regularly swept chimney fires should not occur However if a chimney fire does occur turn the control knob to the minimum setting and tightly close the doors of the appliance This should cause the chimney fire to go out in which case the control should be kept at the minimum setting until the fire in the appliance has gone out The chimney and flueways shou...

Page 8: ...perform satisfactorily the chimney height must not be less than 4 metres measured vertically from the outlet of the appliance to the top of the chimney The chimney should preferably be 175 mm 7 inches or 200mm 8 inches internal diameter or square with sides of 175mm or 200mm internally and MUST NOT BE LESS THAN 150mm 6 INCHES INTERNAL DIAMETER OR 150 x 150mm INTERNAL SQUARE If an existing chimney ...

Page 9: ...ombined heating and domestic hot water system then a double feed indirect hot water storage cylinder to BS 1566 part 1 should be used In order to prevent the build up of scale and corrosion a suitable inhibitor should be used The system must be correctly vented as shown in Figs 8 and 9 The height differential between the header tank and the appliance must not exceed 15 2 metres 50 feet If all four...

Page 10: ... fire cement to the rear face of the sealing flange on the appliance Fit it into the opening ensuring that it is central and that a good seal is made between the sealing flange and the face of the surround The fire should be screwed to the hearth through the holes at the base of the sealing flange Remove any excess fire cement from around the sealing flange Connect the heating system to the boiler...

Page 11: ...imum setting the flap should be 18 mm from the air inlet as shown in Fig 12 To adjust the distance slacken the locking nut and adjust as necessary When set correctly re tighten the locking nut Ensure that the flap opens and closes freely as the knob is turned ASSEMBLY Fit the side panels hood and top grid onto the appliance Instructions for this are enclosed with the panel pack Replace any interna...

Page 12: ...8 i d To Suit 150mm Flue Pipe Charnwood DX45iB DX50iB Overall Dimensions dimensions are in mm Boiler Tappings 1 BSP Female 2 On Each Side Of Boiler 620 400 240 261 250 360 120 147 547 520 Page 11 DX50iB 3 99 ...

Reviews: