F2.16
Pressure feedback source
Range:00
~
13
Default:00
When voltage dormancy or wake up:
Unit
’
s place: Pressure feedback channel
0:AI1
Pressure feedback given by AI1
1:AI2
Pressure feedback given by AI2
2:DI7/HI pulse input
Pressure feedback given by DI7/HI
Ten
’
s place: dormancy mode on pressure
0: Positive mode, dormancy on high pressure and wakeup on low pressure
When inverter is running, if the pressure feedback is higher than dormancy pressure, then inverter
enter into dormancy.
When inverter is in dormancy, if the pressure feedback is lower than wake up pressure, then
inverter wake up from dormancy
1: Negative mode, dormancy on low pressure and wake up on high pressure.
When inverter is running, if the pressure feedback is lower than dormancy pressure, then inverter
enter into dormancy.
When inverter is in dormancy, if the pressure feedback is higher than wake up pressure, then
inverter wake up from dormancy
Group H0 Communication Parameters
H0.00
Baud rate
Range:0
~
5
Default:1
0: 4800bps 1: 9600bps
2: 19200bps 3: 38400bps
4: 57600bps 5: 115200bps
H0.01
Data format
Range:0
~
3
Default:0
0: No check, data format (1-8-N-2) for RTU
1: Even parity check, data format (1-8-E-1) for RTU
2: Odd Parity check, data format (1-8-O-1) for RTU
3: No check, data format (1-8-N-1) for RTU
H0.02
Local address
Range:1
~
247
Default:1
Set this drive address. 0 is broadcast address, while available addresses are 1
~
247.
H0.03
Communication timeout
Range:0.0
~
60.0s
Default:0.0s
This parameter sets communication error detection time. When it's set to 0.0, no communication
Error will be reported.
H0.04
Response time delay
Range:0
~
200ms
Default:1ms
Set response time delay of this drive to the master.
H0.05
Master-slave Communication
Mode
Range:0
~
1
Default:0
0: The inverter is the slave
PC as master controls the drive. This supports all communication protocols.
1: The inverter is the master
This drive as master sends current running frequency data or set frequency data (H0.06) through
RS-485 port to 2001H. Data cannot be received but sent.
H0.06
The Master Communication
Sending Data
Range:0
~
1
Default:0
0: Set frequency
1: Current running frequency
H0.07
Information return when
communication error
Range: 0
~
1
Default: 1
0: No return
1: Return