248
Technical Data
CG Drives & Automation 01-5326-01r5
14.6 Fuses and glands
14.6.1 According to IEC ratings
Use mains fuses of the type gL/gG conforming to IEC 269
or breakers with similar characteristics. Check the
equipment first before installing the glands.
Max. Fuse = maximum fuse value that still protects the AC
drive and upholds warranty.
NOTE: The dimensions of fuse and cable cross-
section are dependent on the application and must
be determined in accordance with local regulations.
NOTE: The dimensions of the power terminals used in
the cabinet drive models 300 to 3K0 can differ
depending on customer specification.
Table 65
Fuses, cable cross-sections and glands for VFX48 and VFX52 models
Model VFX
Nominal input
current
[A]
Maximum
value fuse
[A]
Cable glands (clamping range ) *
mains / motor
Brake
##-003-54
2.2
4
M32 opening
M20 + reducer
(6–12 mm(0.24 - 0.47 in))
M25 opening
M20 + reducer
(6–12 mm(0.24 - 0.47 in))
##-004-54
3.5
4
##-006-54
5.2
6
##-008-54
6.9
10
M32 (12–20)/M32 opening
M25+reducer
(10-14 mm(0.39 - 0.55 in))
M25
(10-14 mm(0.39 - 0.55 in))
##-010-54
8.7
10
##-013-54
11.3
16
M32 (16–25)/M32 (13–18)
##-018-54
15.6
20
##-025-20
22
25
- (12 - 16 mm(0.55 - 0.63 in))
##-026-54
22
25
M32
(15–21 mm(0.59 - 0.83 in))
M25
##-030-20
26
35
- (16 - 20 mm (0.63 - 0.79 in))
##-031-54
26
35
M32
(15–21 mm(0.59 - 0.83 in))
M25
##-036-20
31
35
- (20 - 24 mm(0.79 - 0.94))
##-037-54
31
35
M40
(19–28 mm (0.75 - 1.1 in))
M32
##-045-20
38
50
- (24 - 28 mm(0.94 - 1.1 in))
##-046-54
38
50
M40
(19–28 mm (0.75 - 1.1 in))
M32
##-058-20
50
63
- (24 - 28 mm(0.94 - 1.1 in))
##-060-20
52
63
- (28 - 32 mm(1.1 - 1.26 in))
##-061-54
52
63
M50
(27 - 35 mm(1.06 - 1.38 in))
M40
(19–28 mm (0.75 - 1.1 in))
##-072-20
64
80
- (28 - 32 mm(1.1 - 1.26 in))
##-074-54
65
80
M50
(27 - 35 mm(1.06 - 1.38 in))
M40
(19–28 mm(0.75 - 1.1 in))
##-088-20
78
100
- (32 - 36 mm(1.26 - 1.42 in))
##-090-54
78
100
(Ø17-42 mm (0.67 - 1.65 in)) cable
flexible leadthrough or M50
opening.
(Ø11-32 mm(0.43 - 1.26 in)) Cable
flexible leadthrough or M40
opening.
##-105-20
91
100
(32 - 36 mm(1.26 - 1.42 in)
##-109-54
94
100
(Ø17-42 mm (0.67 - 1.65 in)) cable
flexible leadthrough or M50 opening
(Ø11-32 mm(0.43 - 1.26 in)) Cable
flexible leadthrough or M40
opening
##-142-20
126
160
- (40 - 44 mm (1.57 - 1.73 in))
- (36 - 40 mm(1.42 - 1.57 in))
##-146-54
126
160
(Ø17-42 mm (0.67 - 1.65 in)) cable
flexible leadthrough or M50
opening.
(Ø11-32 mm(0.43 - 1.26 in)) Cable
flexible leadthrough or M40
opening.
##-171-20
152
160
- (40 - 44 mm (1.57 - 1.73 in))
- (36 - 40 mm(1.42 - 1.57 in))
##-175-54
152
160
(Ø17-42 mm (0.67 - 1.65 in)) cable
flexible leadthrough or M50
opening.
(Ø11-32 mm(0.43 - 1.26 in)) Cable
flexible leadthrough or M40
opening.
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......