![CG Emotron VFX Series Instruction Manual Download Page 101](http://html1.mh-extra.com/html/cg/emotron-vfx-series/emotron-vfx-series_instruction-manual_2585388101.webp)
CG Drives & Automation,01-5326-01r5
Functional Description
97
Supply Type [21C]
Set supply voltage type.
Communication information
When changing to / from the “AFE Supply” selection, the
following parameters are set to following values:
11.4.4 Motor Data [220]
In this menu you enter the motor data to adapt the AC drive
to the connected motor. This is crucial for the control
accuracy as well as different read-outs and analogue output
signals.
Emotron VFX AC drive can control both Asynchronous
motors and Permanent magnet synchronous motor
(PMSM) select type of motor in menu [22I].
Motor M1 is selected as default and motor data entered will
be valid for motor M1. If you have more than one motor
you need to select the correct motor in menu [212] before
entering motor data.
Motor Voltage [221]
Set the nominal motor voltage.
21C
Supply Type
Default:
AC Supply
AC Supply
0
Normal AC supply
AFE Supply
1
DC supply voltage by AFE
DC Supply
2
DC supply voltage
AC/DC Suppl
3
AC/DC supply voltage
Modbus Instance no/DeviceNet no:
43382
Profibus slot/index
170/31
EtherCAT and CANopen index (hex)
4d36
Profinet IO index
19766
Fieldbus format
UInt
Modbus format
UInt
Menu
to AFE
from AFE
[523] DigIn 3
Sleep
Off
[542] DigOut 3
Run
Brake
[527] DigIn 7
Off
Off
[561] VIO 1 Dest
External Trip
Off
[562] VIO 1 Source
!D1
Off
[6151] CD 1
DigIn 7
Run
WARNING!
Do not work on a drive when a rotating
Permanent Magnet synchronous motor is
connected to it. A rotating PMSM motor
energizes the drive including its power
terminals.
NOTE 1: The parameters for motor data cannot be
changed during run mode.
NOTE 2: The default settings are for a standard 4-
pole motor according to the nominal power of the AC
drive.
NOTE 3: Parameter set cannot be changed during run
if the parameter set is set for different motors.
NOTE 4: Motor Data in the different sets M1 to M4
can be revert to default setting in menu “[243]
Default>Set”.
WARNING!
Enter the correct motor data to prevent
dangerous situations and assure correct
control.
Volts
Default:
400 V for VFX48
500 V for VFX52
690 V forVFX 69
Range:
100-700 V
Resolution
1 V
NOTE: The Motor Volts value will always be stored as
a 3 digit value with a resolution of 1 V.
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......