Cetetherm Mini Plus CM737 

Installation, service and operating instruction

 

 

28 

13.3.1  Pump curve proportional pressure mode 2, PP2 

 

 
Line type 

Description 

 

Constant Curve 

Proportional Pressure 

Constant Pressure 

13.3.2  Change pump operating mode 

The display shows the current operation status. 

 

Press the button for more than 2 seconds and the circulator switches to "setting selection".  
The LEDs flash and show the current setting mode.  
Please note that if the key lock is disabled, the circulator will not switch to "setting selection". In this 
case, unlock the key lock by pressing the button for more 10 seconds. 

 

To select between the settings, instantly press the button until you find the setting you want. If you pass 
a setting, you need to continue until the setting appears again as it is not possible to go back in the 
settings menu. 

 

Release the button for more than 10 seconds and the user interface switches back to the performance 
view and the last setting is stored.  

13.3.3  Key lock function 

The purpose of the key lock function is to avoid accidental change of settings and misuse. 
When the key lock function is enabled, all long key presses will be ignored.  
 
Lock and unlock by pressing the key for more than 10 seconds. 
 

 

Summary of Contents for Mini Plus CM737

Page 1: ...01 Installation service and operating instruction Cetetherm Mini Plus CM737 DHWC och serviceinstruktion Mini Mini XL RVS46 District heating substation for single family houses and multi family buildin...

Page 2: ...to the content in this manual if it is necessary due to printing mistakes wrong information or changes in the hardware or software All these types of changes will be included in future release of the...

Page 3: ...er installation 13 7 5 Setting the day 14 7 6 Setting the time 14 8 Operating the room thermostat CM737 15 8 1 Choosing the operating mode 15 8 2 Temperature Enquiry with the Info button 7 15 8 3 Holi...

Page 4: ...diator system 36 16 Service actions for the installer 37 16 1 Check the function of the valve for hot water 37 16 2 Check the heating actuator and valve function 38 16 3 Check the circulation pump Gru...

Page 5: ...t the substation can be started without delay The Mini Plus is designed for hanging on the wall Mini Plus is supplied fully wired The wiring conforms to the applicable rules for CE marking and has und...

Page 6: ...make sure that the secondary heating system is topped up with water Starting up the system without water will damage the circulation pump The substation comes prepared with an electrical plug to be c...

Page 7: ...gh otherwise the risk of lime deposits in the heat exchanger may increase 2 2 Safety equipment inspection Daily inspection to check for leaks from pipes or components Weekly inspection to make sure th...

Page 8: ...circuit 23 Pressure gauge for heating circuit 7 Outdoor temperature sensor not in picture 24 Circulation pump heating 8 Operator control panel with room thermostat 25 Safety thermostat option 9 Contr...

Page 9: ...hot water systems 4 3 Mounting Mount the substation on the wall using four screws or bolts suitable for the material of the wall and for the weight of the unit The unit may be mounted at any height o...

Page 10: ...Heating system service instructions After final bleeding the pressure should not be less than 1 0 bar in winter and not less than 0 6 bar in summer Set the pump capacity of the heating circulation pu...

Page 11: ...Cetetherm Mini Plus CM737 Installation service and operating instruction 9 5 Measure sketch Mini Plus Picture 3...

Page 12: ...to 35 C Built in Memory holds the user program indefinitely Holiday button saves energy by letting you reduce the temperature for 1 to 99 days 7 days heating program to match your lifestyle and maximi...

Page 13: ...meters above floor and on an inner wall The room thermostat must not be combined with other thermostats in the same control zone Use a suitable 2 conductor cable between the connection box and the op...

Page 14: ...Cetetherm Mini Plus CM737 Installation service and operating instruction 12 Picture 6...

Page 15: ...schedule 10s actuator clockwise if not closed at start 10s actuator counter clockwise 10s actuator clockwise 10s pump runs 150s actuator closes After approximately another 4 minutes the room thermosta...

Page 16: ...6 Setting the time 1 Press either of the or buttons once to enter timer setting mode The LCD screen flashes the time digits When the unit is powered for the first time the display shows 12 00 2 Use t...

Page 17: ...on 7 Each value will be displayed for 3 second before returning to show the initial screen NOTE The initial screen shows different temperatures depending on if the outdoor temperature sensor is connec...

Page 18: ...exit the function at any time press the button a second time 8 4 OTC heating curve The CM737 controls the indoor temperature as a function of the measured outside air temperature The heating curve is...

Page 19: ...each day of the week so the complete 7 day heating program can be reviewed or edited 8 6 3 Temperature Override During AUTO mode the programmed temperature can be adjusted manually The target tempera...

Page 20: ...firm the setting again by pressing the green button e The next time and temperature period will now be active Adjust this by repeating steps b d above until all four periods are set or press the AUTO...

Page 21: ...lues Category 4 parameters Heating actuator settings Category 5 Fault History 9 1 Entering the installer set up mode 1 Press the OFF button 2 Press and hold the button and the two PROGRAM and buttons...

Page 22: ...ment in 0 1 C steps Room control OTC 1 14 rC 0 Room temperature control thermostat 1 or 2 1 OTC control without room temperature compensation 2 OTC control with room temperature compensation OTC heat...

Page 23: ...f day DHW storage during HOLIDAY 9 HH 0 DHW storage disabled during HOLIDAY 1 DHW storage enabled during HOLIDAY Low capacity control 10 LD 1 Not applicable 0 Not applicable 9 5 Category 4 parameters...

Page 24: ...No power feed after the installation of the control panel Check that the power supply cable of the connection box is connected The control panel is not connected to the correct terminals of the conne...

Page 25: ...ult code 2 Outside sensor out of operating range This fault code can only occur after the measured outside temperature has been in range 40 C to 60 C Cause Measured outside temperature is below 40 C o...

Page 26: ...Cetetherm Mini Plus CM737 Installation service and operating instruction 24 11 Electrical circuit diagram Picture 11...

Page 27: ...Cetetherm Mini Plus CM737 Installation service and operating instruction 25 12 Schematic diagram main components Picture 12...

Page 28: ...one for the hot water circulation DHWC pump and one for the heating circuit The DHWC pump is a traditional three speed circulation pump The DHWC pump has a switch where the speed capacity can be set...

Page 29: ...ng heat demand and increased at rising heat demand The duty point of the pump will move up or down on the selected proportional pressure curve depending on the heating demand PP2 PP3 CP1 Constant pres...

Page 30: ...setting selection In this case unlock the key lock by pressing the button for more 10 seconds To select between the settings instantly press the button until you find the setting you want If you pass...

Page 31: ...pulse width modulation The user interface allows to select between six control curves in two control modes three proportional pressure curves PP three constant pressure power curves CP The pump is fac...

Page 32: ...ting mode LED starts flashing 2 With each push the setting changes LED 1 2 3 are permanently on and then the control curve and mode is changed 3 Flashing mode Fast Proportional pressure Slow Constant...

Page 33: ...control box with a screwdriver Pump is defective Replace the pump Noise in the system Air in the system Vent the system Differential pressure is too high Reduce the pump performance at the pump or ex...

Page 34: ...ncing valve Check that the balancing valve is open enough 15 1 2 Tap water temperature too high Reason Action Handle on control valve incorrectly positioned Adjust the handle on the control valve The...

Page 35: ...ressure should not be below 1 0 Bar in winter time or below 0 6 Bar in summer The circuit should only be topped up with fresh water when necessary The water used for topping up contains oxygen which c...

Page 36: ...eating parameters in operator control panel Summer reduction parameter 2 category 2 If measured outdoor temperature is higher than target temperature the pump should not be operating Economy function...

Page 37: ...for leaks Leaks from the substation or the heating system cause pressure drop Contact your service technician if finding any leaks The heating system safety valve is leaking or does not work Check th...

Page 38: ...y is set too high Reduce the pump capacity Reduce the level by choosing a lower output setting on the pump Air in the pump Vent the pump The pump is self venting Air in the pump may cause noise This n...

Page 39: ...y and then the return line to avoid pollutions in the system Open the valves slowly to avoid pressure surges 1 Disconnect the power feed to the substation 2 Close the shut off valves 3 Unscrew the tap...

Page 40: ...he valve s spindle with a tool and check the valve s travel and spring back NOTE The valve may be very hot Picture 21 16 3 Check the circulation pump Grundfos UPS If the pump fails to start after stop...

Page 41: ...circulation pump 3 Open the heating valve manually by turning the actuator knob counter clockwise Open the control valve sufficiently to satisfy the heating needs 4 Connect the power feed to the subs...

Page 42: ...valves Start with DH supply and then the return line to avoid pollutions in the system Open the valves slowly to avoid pressure surges 1 Disconnect the power feed to the substation 2 Close the shut o...

Page 43: ...tting of the balancing valve then close it Release the pressure using the DHWC safety valve After finishing repair fill up the hot water circuit and vent Open the shutoff valves start with DH Supply a...

Page 44: ...ump 2 Close the shut off valves 3 Choose alternative a or b c When changing the complete pump release the brass nuts with a wrench and replace the pump Connect the pump cable d Only changing the motor...

Page 45: ...he control panel after 5 min Picture 28 17 7 Change the heating actuator Maintenance and repairs must be carried out by an authorized service technician 1 Disconnect the power feed to the substation 2...

Page 46: ...by turning the knob clockwise to the closing position Fasten the actuator use only hand power 7 Open the shutoff valves and connect the power feed to the substation Picture 31 17 9 Change the hot wat...

Page 47: ...he hot water circuit and vent Open the shutoff valves start with DH Supply and then DH return to avoid pollutions in the system Open the valves slowly to avoid pressure surges 8 Disconnect the power f...

Page 48: ...valves cold and hot water 7 Open and adjust the balancing valve 8 Vent the circuit by opening a hot water tap 9 Connect the power feed to the substation Open the shutoff valves DH Supply and then DH r...

Page 49: ...e for heating supply 6 Set the correct maximum temperature value for the thermostat 7 Attach all electrical wires with the necessary number of straps It is important not to attach electrical wires on...

Page 50: ...Cetetherm Mini Plus CM737 Installation service and operating instruction 48 19 Operating data and performance 19 1 Operating data Mini Plus CB30 60H 19 2 Operating data Mini Plus CB18 54H...

Page 51: ......

Page 52: ...Cetetherm AB Fridhemsv gen 15 372 38 Ronneby Sweden www cetetherm com...

Reviews: