16.4 Modbus slave communication parameters
MODBUS
Speed / Vitesse :
9600
In case of multiple controllers, change ModBus controler slave number
Bit number / Nbre de bits :*
8
Parameter="DEVICE ID"
Stop bit / Bit de stop :
1
Parity / Parité :
None / Aucune
Mode :
RTU
ModBus Points
MODBUS adress**
Type
Sub-type
Mode
Value
Comment
PD_Cmd_P1
15
HR _16
BOOL
R
0=Off, 1=On
Command(e) P1
PD_Cmd_P2
16
HR _16
BOOL
R
0=Off, 1=On
Command(e) P2
PD_Cmd_P3
17
HR _16
BOOL
R
0=Off, 1=On
Command(e) P3
PD_Cmd_P4
18
HR _16
BOOL
R
0=Off, 1=On
Command(e) P4
PriP1_Alarm_On
19
HR _16
BOOL
R
0=OK, 1=Alarm
P1 Fault P1
PriP2_Alarm_On
20
HR _16
BOOL
R
0=OK, 1=Alarm
P2 Fault P2
SecP3_Alarm_On
23
HR _16
BOOL
R
0=OK, 1=Alarm
P3 Fault P3
SecP4_Alarm_On
24
HR _16
BOOL
R
0=OK, 1=Alarm
P4 Fault P4
PD_High_Alarm
27
HR_16
BOOL
R
0=OK, 1=Alarm
S1 High Temp Alarm
PD_Main_Alarm
28
HR_16
BOOL
R
0=OK, 1=Alarm
General default
Fooling_Alarm
30
HR_16
BOOL
R
0=OK, 1=Alarm
Fooling alarm (S3)
ThermTr_Alarm
32
HR_16
BOOL
R
0=OK, 1=Alarm
Therm.Treat. Failed
PD_Triac_Output
33
HR _16
BOOL
R
0=Off, 1=On
230V Triac output
SAFETY_FCT
35
HR_16
BOOL
R
0=Off, 1=On
Safety function
AFF_Leg_active
36
HR_16
BOOL
R
0=Off, 1=On
Therm.Treat. On going
Remote_Control_Rev
37
HR_16
BOOL
R
0=Off, 1=On
Remote control
PC_Distrib_Com
38
HR_16
BOOL
R
0=Internal, 1=External
AlfaPilot external setpoint
AFF_FD20
39
HR_16
BOOL
R
0=Off, 1=On
Heating mode
AFF_FD22
40
HR_16
BOOL
R
0=Off, 1=On
Cooling mode
BOOSTER
41
HR_16
BOOL
R
0=Off, 1=On
BOOSTER activated
ECO
42
HR_16
BOOL
R
0=Off, 1=On
ECO activated
PD_Pumps_Fault
43
HR_16
BOOL
R
0=Off, 1=On
Synthesis pump(s) fault
Tank_load
44
HR_16
BOOL
R
0=Off, 1=On
Tank loaded
(16 bit integer/Entier 16 bit)*
SW AL Version
34
HR_16
int16
R
Software version
PA10_Speed_P1P2
45
HR_16
int16
R
%
Primary pump signal
PA10_Speed_P3P4
46
HR_16
int16
R
%
Secondary pump signal
PA10_valve1
47
HR_16
int16
R
%
Control vlave 1 signal
PA10_valve2
48
HR_16
int16
R
%
Control vlave 2 signal
SP_Apilot
49
HR_16
int16
R
°C
AlfaPilot Setpoint
S1_10
50
HR_16
int16
R
°C
Sensor 1 measurement
S2_10
51
HR_16
int16
R
°C
Sensor 2 measurement
S3_10
52
HR_16
int16
R
°C
Sensor 3 measurement
S4_10
53
HR_16
int16
R
°C
Sensor 4 measurement
S5_10
54
HR_16
int16
R
°C
Sensor 5 measurement
S6_10
55
HR_16
int16
R
°C
Sensor 6 measurement
pt1_10
56
HR_16
int16
R
°C
Sensor Pt1 measurement
pt2_10
57
HR_16
int16
R
°C
Sensor Pt2 measurement
DT_recup_min10
61
HR_16
int16
R
°C
Min DT energy recov
S1_PID_SP_10
62
HR_16
int16
R
°C
Calculated S1 setpoint
SP_T_Amb_S5_10
63
HR_16
int16
R
°C
Ambiant temp. Setpoint
Solar_Option_Ana
64
HR_16
int16
R
0=no/pas/keine Option
1=Solar Flow
2=Alfa_store A
3=AlfaPilot
4=Aqua_Heating
0 for AquaFirst, AquaEfficiency
(16 bit integer/Entier 16 bit)*
High_Alm_Reset
201
HR_16
BOOL
R/W
Pump fault Reset
202
HR_16
BOOL
R/W
(16 bit integer/Entier 16 bit)*
DeltaT_ByPass
210
HR_16
int16
R/W
°C
Delta T bypass (S4-S3)
SP_T_Sec_Outlet
211
HR_16
int16
R/W
°C
S1 fixed setpoint (DHW)
PC_Distrib_distant
212
HR_16
int16
R/W
°C
AlfaPilot external setpoint on Pt2
ThTr_setpoint
213
HR_16
int16
R/W
°C
Thermal treatment setpoint
(16 bit integer/Entier 16 bit)*
* For some supervisors, it is necessary to implement BOOL as int16
** For some supervisors, remove 1 to adress number (ex : S1_10 adress=49)
Read Only digital
Read Only Analogic
Read-Write digital
Read-Write Analogic
1=Reset fault. Pulse point necessary 30 seconds On/Off