CET Inc.
28
2)
SOE Classification
Table 5-5 SOE Classification
5.3 Device Setup
Register
Property
Description
Format
Range, Default*
51000
RW
Alarm Buzzer
UINT16
0 = Disabled
1 = Intermittent*
2 = Continuous
51001
RW
Fault Buzzer
UINT16
0 = Disabled
1 = Intermittent*
2 = Continuous
51002
RW
Alarm Reset Mode
UINT16
0 = Manual*, 1 = Auto
51003
RW
RTD Probe Compensation
UINT16
0 = Disabled, 1 = Enabled*
51004
RW
Temp. Threshold
UINT16
0 to 45°C, 0°C*
51005
RW
I
residual
Threshold
UINT16
10 to 500 mA, 20 mA*
51006
RW
DO Pulse Width
UINT16
0 to 6000 (0.1s), 1.0s*
0=Latch Mode
51007
RW
Reserved
UINT16
-
51008
RW
IRn Alarm Setpoint
UINT16
0 = IRn RMS*
1 = IRn Fundamental
51009
RW
Reserved
UINT16
-
51010
RW
IR1 Setpoint
UINT16
See Note 1), 0*
51011
RW
IR1 Alarm Limit
UINT16
20 to 1000 mA, 500 mA*
51012
RW
IR1 Alarm Time Delay
UINT16
0 to 20s, 5s*
51013
RW
IR1 Warning Level
UINT16
0.1 to 0.8, 0.6*
Event
Classification
Sub-
Classification
Event Value
Description
1
1
Reserved
2
Reserved
3
1/0
DO Operated/Released
2
1
Triggered
Value
TC1 Alarm
2
TC2 Alarm
3
TC3 Alarm
4
TC4 Alarm
5
IR1 Alarm
6
IR2 Alarm
7
IR3 Alarm
8
IR4 Alarm
9
Reserved
10
TC1 Warning
11
TC2 Warning
12
TC3 Warning
13
TC4 Warning
14
IR1 Warning
15
IR2 Warning
16
IR3 Warning
17
IR4 Warning
18~19
Reserved
20
0
TC1 RTD Probe Fault
21
0
TC2 RTD Probe Fault
22
0
TC3 RTD Probe Fault
23
0
TC4 RTD Probe Fault
24
0
IR1 Residual CT Fault
25
0
IR2 Residual CT Fault
26
0
IR3 Residual CT Fault
27
0
IR4 Residual CT Fault
3
1
0
System Parameter Fault
2
0
Calibration Parameter Fault
3
0
Ferroelectric Fault
4
0
AD Fault
4
1
0
Setup Changed via Communication
2
0
Clear SOE via Communication
3
0
Power On
4
0
Setup Changed via Front Panel
5
0
Clear SOE via the Front Panel