“Execute” command is received without first having received an “Arm” command, the meter ignores the “Execute”
command and returns the 0x04 exception code.
Register
Property
Description
Format
Note
9100
WO
Arm DO1 Close
UINT16
Writing “0xFF00” to
the register to perform
the described action.
9101
WO
Execute DO1 Close
UINT16
9102
WO
Arm DO1 Open
UINT16
9103
WO
Execute DO1 Open
UINT16
9104
WO
Arm DO2 Close
UINT16
9105
WO
Execute DO2 Close
UINT16
9106
WO
Arm DO2 Open
UINT16
9107
WO
Execute DO2 Open
UINT16
9108
WO
Arm DO3 Close
UINT16
9109
WO
Execute DO3 Close
UINT16
9110
WO
Arm DO3 Open
UINT16
9111
WO
Execute DO3 Open
UINT16
Table 5-60 DO Control
5.10.9
Clear/Reset Control
Register
Property
Description
Format
Note
6400
WO
Manual WFR Log #1 Trigger
UINT16
Writing “0xFF00” to
the register to execute
the described action.
6401
WO
Manual WFR Log #2 Trigger
UINT16
6402
WO
Clear DR #1 (High-Speed)
UINT16
6403
WO
Clear DR #2 (High-Speed)
UINT16
6404
WO
Clear DR #3 (High-Speed)
UINT16
6405
WO
Clear DR #4 (High-Speed)
UINT16
6406
WO
Clear DR #5 (Standard)
UINT16
…
WO
…
UINT16
6416
WO
Clear DR #15 (Standard)
UINT16
6417
WO
Clear DR #16 (Standard)
UINT16
6418
WO
Clear WFR Log #1
UINT16
6419
WO
Clear WFR Log #2
UINT16
6420
WO
Clear IER Log
UINT16
6421
WO
Clear PQ Log
UINT16
6422
WO
Clear SOE Log
UINT16
6423
WO
Clear All Energy
UINT16
6424
WO
Clear Max./Min. Log of This Month
UINT16
6425
WO
Clear Peak Demand Log of This Month
UINT16
6426
WO
Clear Counter #1 (DI1)
UINT16
6427
WO
Clear Counter #2 (DI2)
UINT16
…
WO
…
UINT16
6430
WO
Clear Counter #5 (DI5)
UINT16
6431
WO
Clear Counter #6 (DI6)
UINT16
6432
WO
Clear Device Operating Time
UINT16
6433
WO
Manual Switch TOU Schedule
UINT16
6434
WO
Clear TOU Energy
UINT16
6435
WO
Send Testing Email
UINT16
6436
WO
Clear Event Counter
UINT16
6437
WO
Clear all Data
UINT16
Writing “0xFF00” to
the register clears all of
the above
Table 5-61 Clear/Reset Registers
Notes:
1)
Writing “0XFF00” to the register clears all 3-Phase, Total Energy Measurement, TOU Energy and Interval Energy Measurements.
2)
Writing “0XFF00” to the register clears all logs, including Data Recorder, Waveform Recorder, Energy Log, PQ Log, SOE Log, Max./Min.
Log of This Month (Since Last Reset), Peak Demand of This Month (Since Last Reset), DI Counters, Energy Registers, Device Operating
Time and TOU energy.
5.11
Time
There are two sets of Time registers supported by the iMeter 6 – Year / Month / Day / Hour / Minute / Second
(Registers # 60000 to 60002) and UNIX Time (Register # 60004). When sending time to the iMeter 6 over Modbus
communications, care should be taken to only write one of the two Time register sets. All registers within a Time
register set must be written in a single transaction. If registers 60000 to 60004 are being written to at the same
time, both Time register sets will be updated to reflect the new time specified in the UNIX Time register set
(60004) and the time specified in registers 60000-60002 will be ignored. Writing to the Millisecond register