5-97

ELO LH

Technical
Data

Product
Description

The Central Model ELO LH Extra Large

Orifice Recessed Pendent and Pendent
Automatic Glass Bulb Sprinklers are
specifically designed for Extended Cover-
age/Light Hazard as defined by NFPA 13.
They are Listed as Quick Response, up to
18'x18' spacing, and as Standard Re-
sponse, above 18'x18' spacing.  The ELO
LH is Listed for smooth flat horizontal
ceilings as are all Extended Coverage
Light Hazard Sprinklers.

The ELO LH provides the maximum in

design flexibility as it has a minimum
separation of only 11'-0" and is Listed for
flows and pressures associated with
16'x16', 18'x18' and 20'x20' spacing.

They are intended for use with hydrauli-

cally designed systems using the flows
and pressures as shown in this literature.
For the purpose of determining the correct
flow and pressure to use in the hydraulic
calculations, all spacing is rounded up to
the next higher category.  For example,
17'-6"x15'-0" spacing would be calculated
at the Listed 18'x18' flow and pressure.

The advantage of the ELO LH is the

ability to cover large areas, up to 400
square feet, with pressures that compare
to 

1

2

" standard sprinklers spaced at their

maximum of 225 square feet.  For ex-
ample, the ELO LH can cover 20'x20'
spacing or 400 square feet with less
pressure than is required with 

1

2

" sprin-

klers at 225 square feet.  (12.3 vs. 16.1)

The Model ELO LH Sprinkler incorpo-

rates a specially designed deflector that
provides a much greater area of coverage
than standard commercial sprinklers.
The two (2) piece recessed escutcheon
assembly provides for 

3

4

" of field adjust-

ment.

Quick Response
Extended
Coverage Light
Hazard Recessed
Pendent and
Pendent
Sprinkler

Quick Response
Extended Coverage Light Hazard

Extra Large Orifice

Recessed Pendent and Pendent
Glass Bulb Automatic Sprinkler

ELO LH

Manufactured by:  Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446

No. 3-3.5

Model:  ELO LH
Style:  Recessed Pendent, Pendent
Escutcheon:  Model ELO (2-piece)

Recessed

Escutcheon Part #'s:
850 - Brush Brass

853 -White

851 - Bright Chrome

848 - Off-White

852 - Bright Brass

849 - Black

Note:  In the recessed position, only the
Model ELO (2-piece) Recessed Escutch-
eon may be used.  Substitution of other
“recessed” escutcheons may impair the
operating sensitivity and distribution
pattern.

Wrench

Pendent:  Part #1073

ELO/ELO/ESFR Combination

Recessed Pendent:  Part #1092

ELO Offset

Orifice Size:  0.64" 

(16.3 mm) (ELO)

K-Factor:  11.4 

(163.02)

Thread Size:

 

3

4

" N.P.T. 

(19.1 mm)

Temperature Rating:

155

°

F/68

°

C

200

°

F/93

°

C

 (Available as Standard Response Only)

250

°

F/121

°

C

 (Available as Standard Response Only)

Approvals:  U.L., cUL
Maximum Working Pressure:  175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes:

Sprinkler:  brass or chrome plated
Decorative Finishes:  white or black

painted

Escutcheon:  brass, chrome plated,

white or black painted

Length:  2 

3

4

(70 cm)

Width:  1

1

2

(3.80 cm)

Weight:  4.2 oz. 

(120 grams)

OBSOLETE

Summary of Contents for ELO LH

Page 1: ...he Model ELO LH Sprinkler incorpo rates a specially designed deflector that provides a much greater area of coverage than standard commercial sprinklers The two 2 piece recessed escutcheon assembly provides for 3 4 of field adjust ment Quick Response Extended Coverage Light Hazard Recessed Pendent and Pendent Sprinkler Quick Response Extended Coverage Light Hazard Extra Large Orifice Recessed Pend...

Page 2: ...cheon the face of the R C is to protrude 1 8 1 16 beyond the finished ceiling line Installation Diagrams ELO LH Extended Coverage Light Hazard Pendent Face of Reducing Coupling Finished Ceiling LIne 1 x 3 4 Reducing Coupling Model ELO 2 piece Recessed Escutcheon 3 1 4 Diameter 2 1 4 Dia Min 2 3 4 Dia Max 3 8 Min 3 4 Nominal 1 1 8 Max 2 3 4 1 1 2 Dia O B S O L E T E ...

Page 3: ... pattern to control the fire All Central Model ELO LH Re cessed Pendent and Pendent Auto matic Sprinklers must be installed according to the current NFPA 13 Standard and these installation instructions Deviations from these requirements and standards or any alteration to the sprinkler itself will void any warranty made by Central Sprinkler Company In addition installation must also meet local gove...

Page 4: ... and notify all personnel who may be affected during system shutdown A fire watch during maintenance periods is a wise precaution To remove the system from service mode first refer to the system operating guide and valve instruction Drain water and relieve pressure in the pipes Remove the existing unit and install the replacement using only the special sprinkler wrench Be certain to match model st...

Reviews: