Celsiair UDG Series Instructions Download Page 1

INSTRUCTIONS

67028A 05/10 (MBC)

English

The thermostat is an electronic on/off

thermostat for temperature control by means of

an NTC sensor located either externally or

internally within the thermostat. The thermostat

has a built-in ground fault circuit interrupter

(GFCI, Class A). The thermostat and GFCI are

suitable for 120-240 V (incl. 208V) 50/60 Hz

power supplies.

The thermostat is for flush mounts in a wall

socket.

Product programme
Thermostats with built-in GFCI
UCG-4991 Programmable thermostat incl.

floor sensor

UDG-4999 Programmable thermostat with

2 sensors:

floor sensor and built-in room

sensor

UTN-4991 Non-programmable thermostat

incl. floor sensor

Power module with built-in GFCI
USG-4000 Power module without sensor

Mounting of floor sensor (fig. 3)

Floor sensor is supplied from SELV (Safety Extra

low Voltage) Circuit, allowing the sensor to be

placed as close to the floor surface as desired

without having to take special account to the

risk of shock at the damage to the sensor cable.

It is not intended that the temperature sensor

wire shall enter through the wall socket

mounting box. The sensor cable shall be

seperated from LINE and LOAD cables. Can be

separated in conduite, inside or outside the

wall. (see fig. 7)

Recommended placed in an non conductive

installation pipe, which is embedded in the floor.

(fig. 3). The pipe must be sealed in the end and

placed as high as possible in the concrete layer.

Alternativerly, the floor sensor is monted directly

in the floor construction. The sensor cable shall

be placed in a separate pipe or be separated

from power cables.

The floor sensor must be centered in between

the heating cable.

Sensor cable can be extended up to 300 ft (100

m.) by means of a separate two-core cable. Two

remaining cores of a multi-core cable which, for

example, supplies current to the floor heating

wires, must not be used. The two-core cable

must be placed in a separate pipe or be

separated from power cables.

Other approved floor sensors can be used if

they comply with the technical specifications

(see fig. 5).

Mounting of thermostat with built-in sensor

(UDG-4999) (fig. 4)

The room sensor is used for comfort

temperature regulation in rooms. The

thermostat should be mounted on the wall

approx. 5.4 ft (1.6 m) above the floor in such a

way as to allow free air circulation around it.

Draughts and direct sunlight or other heat

sources must be avoided.

Mounting of thermostat

Installation

TO AVOID ELECTRIC SHOCK, DISCONNECT

THE HEATING SYSTEM POWER SUPPLY AT

THE MAIN PANEL BEFORE INSTALLING THE

THERMOSTAT.

KEEP THERMOSTAT AIR VENTS CLEAN AND

FREE FROM OBSTRUCTION.

This thermostat is an electrical product and

must be installed in compliance with the

National and/or Local Electrical Code.

Installation must be performed by qualified

personnel where required by law. The

thermostat is equipped with a ground fault

circuit interrupter (GFCI, Class A) which requires

that the line and load cables are isolated from

one another for correct operation. The

thermostat is designed for resistive load. The

resistive load must not exceed 15 A (1800 W at

120 Vac / 3120 W at 208 Vac / 3600 W at 240

Vac).

During a ground fault, the two lines will be cut

off.

Line cable

Delivers power from the service panel (breaker

panel or fuse box) to the thermostat.

This cable must only be connected to the

thermostat’s line terminals, marked L1 and L2.

Load cable

Delivers power from the thermostat to the

heating cable.

This cable must only be connected to the

thermostat’s load terminals, marked load 15 A.

1. Use a screwdriver to release the catch (fig. 1),

and remove the front cover

2. Connect cables according to the diagram (fig. 2)

3. Mount the thermostat in the wall socket.

4. Carefully replace the front cover by first

positioning its upper edge and then clicking it

into place.

Temperature sensor

The floor sensor must be connected to

terminals marked “sensor”, terminals C and D.

(fig. 6).

Power module, type USG

If loads of more than 15 A are required,

expansion is possible using power modules.

Power modules can be connected to the live

cable and load cable, see relevant sections.

Maximum distance between thermostat and

power modules is 80 ft (25 m.)

Use field wiring cable, recommended min. 20

AWG. Connect A to C and B to D (fig. 6).

Operation

Types UCG and UDG (with built-in clock):

The first time the thermostat is connected,

time and day must be set. The thermostat will

automatically start up in the menu for setting

time and day.

Type UTN (without built-in clock):

The actual temperature setting is shown and the

thermostat is ready for use.

Checking the GFCI

It is important that the GFCI is checked for

correct installation and function.

To check the GFCI:

Testing can only be performed while the

thermostat is calling for heat.

Adjust the setpoint until the heating symbol ( )

appears. Use the “Up” button to increase the

heating demand and then press the “OK”

button. Wait 10 seconds to allow the thermostat

to adjust to the new setpoint.

Then press the “TEST” button.

The test is successful if the red light in the

“TEST” button lights up and “GROUND FAULT”

is shown on the display. If this does not occur,

check the installation.

Press the “Standby/Reset” button to reset the

GFCI.

The red light should go out and the display

returns to normal appearance.

Press the “Down” button to return to the original

temperature setting.

If the test fails, check the heating cable and

thermostat.

The GFCI should be tested monthly.

If during normal operation the GFCI trips

without the “TEST” button being pressed, there

could be a ground fault! To check whether it is a

ground fault or nuisance tripping, press

“Standby/Reset”. If this causes the red light to

go off and stay off, it was nuisance tripping and

the system is operating correctly. If this does

not occur, there is a ground fault!

Check the heating cable, sensor cable and

thermostat. Replace the defective part.

Programming

See user manual.

Fault location

If the sensor is disconnected or short-circuited,

the heating system is switched off. The sensor

can be checked against the resistance table

(fig. 5).

Error codes

E0: Internal error. The thermostat must be

replaced.

E1: Built-in sensor short-circuited or

disconnected. The thermostat must be

replaced (n/a for UTN-4991)

E2: External sensor short-circuited or

disconnected.

UL Listed for the US and Canada

According to the following standards:

Thermostat:

UL 873

CSA C22.2 No. 24.

UL file number: E157297

GFCI:

UL 943 4th ed.

CSA C22.2 No. 144.1-06

Classification

The product is a class II device (enhanced

insulation) and must be connected to the

following leads:

Phase L1 (L) 120-240 V ±10%, 50/60 Hz

Neutral L2 (N)

Max. load 15 A (resistive load)

The terminals are suitable for field wiring cables

of 12 to 22 AWG.

Technical data

Supply . . . . . . . . . . . . . .120-240 Vac 50/60 Hz

Load

. . . . . . . . . . .max. 15 A (resistive load)

Power

. . . . . . . . . . . . . . . .1.800 W at 120 Vac

. . . . . . . . . . . . . . . .3.120 W at 208 Vac

. . . . . . . . . . . . . . . .3.600 W at 240 Vac

GFCI

. . . . . . . . . . . .Class A (5 mA trip level)

Temperature range +5 to +40°C, +41 to +104°F

Amb. temp. range . . . .0 to +25°C, +32 to +77°F

Type UDG, UCG, UTN, USG

The trademark is registered and belongs to OJ Electronics A/S · © 2010 OJ Electronics A/S

67028A-05-10.qxp:57609  06/05/10  12:29  Side 1

Reviews: