![Ceiec Electric PMC-630 E User Manual Download Page 70](http://html1.mh-extra.com/html/ceiec-electric/pmc-630-e/pmc-630-e_user-manual_2579014070.webp)
70
Ceiec Electric Technology
Other bits are reserved.
9830
RO
Current configuration
UINT16
0=1 (A)
1=5 (A)
9831
RO
Voltage configuration
UINT16
0=120 (V)
1=415 (V)
2=690 (V)
Table 5-26 Meter Information
Note:
1)
The Meter Model appears in registers 9800 to 9819 and contains the ASCII encoding of the
string “PMC-630E” as shown in the following table.
Register
Value(Hex)
ANSCII
9800
0x50
P
9801
0x4D
M
9802
0x43
C
9803
0x2D
-
9804
0x36
6
9805
0x63
3
9806
0x33
0
9807
0x45
E
9808-9819
0x20
<Space>
Table 5-27 ASCII Encoding of “PMC-630E”
5.11 Data Format
5.11.1 Peak Demand Data Structure
Offset
Property
Description
Format
Note
+0
RO
Peak Demand
INT32
/
+2
RO
High-order Byte: Year
UINT16
0-99 (Year-2000)
Low-order Byte: Month
1 to 12
+3
RO
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
+4
RO
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
+5
RO
Millisecond
UINT16
0 to 999
Table5-28 DMD-LOG Data Structure
5.11.2 Max/Min Data Structure
Offset
Property
Description
Format
Note
+0
RO
Max/Min Value
INT32
-
+2
RO
High-order Byte: Year
UINT16
0-99 (Year-2000)
Low-order Byte: Month
1 to 12
+3
RO
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23