65
Ceiec Electric Technology
basis using the meter clock (
Triggered by Timer
).
For
Triggered by Setpoint
, when the Setpoint goes active, the Data Recorder starts to record, and
when the Setpoint becomes inactive, the Data Recorder stops.
2)
If the “
Recording Depth
” is set to “
0
”, the Data Recorder will be disabled.
3)
Recording Offset
can be used to delay the recording by a fixed time from the
Recording Interval
.
For example, if
Recording Interval
is set to 3600 (hourly) and
Recording Offset
is set to 300 (5
minutes), the recording will take place at 5 minutes after the hour every hour, i.e. 00:05, 01:05,
02:05…etc. The programmed value of
Recording Offset
should be less than that of
Recording
Interval
.
4)
Appendix A
provides a list of available parameters for data recording. All parameters are
available for standard data recording. If
Number of parameters
is set to
0
, the Data Recorder is
disabled.
5)
Modifying
Recording Mode
,
Recording Depth
,
Recording Interval
,
Recording Offset
,
Number of
Parameters
and
Parameters 1 to 16
will clear the DRx Log and reset the
DRx Pointer
to 0.
5.5 Energy Log
Register
Property
Description
Format
Note
7700
RW
Recording Mode
UINT16
0*=Disabled
1=Stop-When-Full
2= First-In-First-Out
7701
RW
Recording Depth
1
UINT16
0 to 65535
(Default=5760)
7702
RW
Recording Interval
UINT16
0=5mins
1=10mins
2=15mins*
3=30mins
4=60mins
7703
RW
Start Time
2
High-order Byte: Year
UINT16
0-99 (Year-2000)
Low-order Byte: Month
1 to 12
7704
RW
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
7705
RW
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
7706
RW
Number of Parameters
UINT16
0 to 5*
7707
RW
Parameter 1
UINT16
0=kWh Import*
1=kWh Export
2=kvarh Import
3=kvarh Export
4=kVAh
7708
RW
Parameter 2
UINT16
0=kWh Import
1=kWh Export*