DR #15 Record Size (Bytes)
UINT16
7383
RO
DR #16 Record Size (Bytes)
UINT16
Table 5-19 Data Recorder Setup Registers
Notes:
1)
DRx Record Size (Bytes) =
Number of Parameters
*4+8.
DRx Log Size=DRx
Recording Depth
*
DRx Record Size
. The Log Size is rounded up to the
nearest kB.
5.4.2 Standard Data Recorder Setup Data Structure
Offset
Property
Description
Format
Range/Options
+0
RW
Trigged Mode
1
UINT16
0=Disabled*
1=Triggered by Timer
2=Triggered by Setpoint
+1
RW
Recording Mode
UINT16
0=Stop-When-Full*
1=First-In-First-Out
+2
RW
Recording Depth
2
UINT16
0 to 65535
(Default=5760)
+3
RW
Recording Interval
UINT32
1 to 3456000 (seconds)
(Default=900)
+5
RW
Recording Offset
3
UINT16
0* to 43200 (seconds)
+6
RW
Number of Parameters
4
UINT16
0* to 16
+7
RW
Parameter 1
UINT16
0* to 322
+8
RW
Parameter 2
UINT16
0* to 322
+9
RW
Parameter 3
UINT16
0* to 322
+10
RW
Parameter 4
UINT16
0* to 322
+11
RW
Parameter 5
UINT16
0* to 322
+12
RW
Parameter 6
UINT16
0* to 322
+13
RW
Parameter 7
UINT16
0* to 322
+14
RW
Parameter 8
UINT16
0* to 322
+15
RW
Parameter 9
UINT16
0* to 322
+16
RW
Parameter 10
UINT16
0* to 322
+17
RW
Parameter 11
UINT16
0* to 322
+18
RW
Parameter 12
UINT16
0* to 322
+19
RW
Parameter 13
UINT16
0* to 322
+20
RW
Parameter 14
UINT16
0* to 322
+21
RW
Parameter 15
UINT16
0* to 322
+22
RW
Parameter 16
UINT16
0* to 322
* Default
Table 5-20 Standard DR Setup Data Structure
Notes:
1)
The Standard Data Recorder can be triggered by Setpoint (
Triggered by Setpoint
) or on a time