57
Ceiec Electric Technology
2924-2929
RO
Vab min
x100, V
2930-2935
RO
Vbc min
x100, V
2936-2941
RO
Vca min
x100, V
2942-2947
RO
VLL average min
x100, V
2948-2953
RO
Ia min
x1000, A
2954-2959
RO
Ib min
x1000, A
2960-2965
RO
Ic min
x1000, A
2966-2971
RO
I average min
x1000, A
2972-2977
RO
I4 min
1
x1000, A
2978-2983
RO
∑kW min
W
2984-2989
RO
∑kvar min
var
2990-2995
RO
∑kVA min
VA
2996-3001
RO
∑P.F. min
x1000
3002-3007
RO
FREQ min
x100, Hz
3008-3013
RO
Va THD min
x10000
3014-3019
RO
Vb THD min
x10000
3020-3025
RO
Vc THD min
x10000
3026-3031
RO
Ia THD min
x10000
3032-3037
RO
Ib THD min
x10000
3038-3043
RO
Ic THD min
x10000
3044-3049
RO
Ia K-Factor min
x10
3050-3055
RO
Ib K-Factor min
x10
3056-3061
RO
Ic K-Factor min
x10
3062-3067
RO
V Unbalance min
x1000
3068-3073
RO
I Unbalance min
x1000
Table 5-12 Min Log of Last Month
Note:
1)
Registers 2972-2977 are valid only if the device is equipped with the I4 Current Input.
Otherwise, they are reserved.
5.2 Setup Register
5.2.1 Basic Setup Parameters
Register
Property
Description
Format
Range/Options
6000
RW
PT Ratio
1
UINT16
1* to 10000
6001
RW
CT Ratio
1
UINT16
1* to 6000 (5A input)
1* to 30000 (1A input)
6002
RW
I4 Ratio
UINT16
1* to 10000
6003
RW
Wiring Mode
UINT16
0=WYE*
1=DELTA
2=DEMO
6004
RW
VLL Nominal Secondary
(VLL
nominal
)
UINT16
100V* to 700V (VLL)