. PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available on the instrument.  Some of them may not be present, either due 
to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.

Parameter

Description

Range

Default

Note

S.Lt1 s.t1

 min. Set time

0 ÷ S.Ht1

0

S.Ht1 s.t1

 max. Set time

S.Lt1 ÷ 9999

99.59

S.Lt2 s.t2

 min. Set time

0 ÷ S.Ht2

0.00

S.Ht2 s.t2

 max. Set time

S.Lt2 ÷ 9999

99.59

S.St1 s.t1 

Time range

 1  Hours (9999 h);

 2  Hours - Minutes (99 h 59 min);

 3  Minutes - Seconds (99 min 59 s);

 4  Seconds - Hundreds of seconf (99 s 99 1/100 s).

3

S.St2 s.t2 

Time range

3

S.t1

s.t1

 Set time

S.Lt1 ÷ S.Ht1

0.00

S.t2

s.t2

 Set time

S.Lt2 ÷ S.Ht2

0.00

S.t3

s.t3

 Set time

S.Lt1 ÷ S.Ht1

0.00

10 

i.Fct

CNT input 

operating mode

 1  Bistable START/STOP;

 2  Bistable RESET-START/STOP;

 3  Monostable START/STOP;

 4  Monostable RESET-START/STOP;

 5  Bistable RESET/START/STOP;

 6  Bistable START/STOP-RESET.

2

11 

F.o1t

OUT1 output 

operating mode

 1  On delay;

 2  Feed-through;

 3  Asymmetrical oscillator with start ON;

 4  Asymmetrical oscillator with start OFF;

 5  Asymmetrical oscillator with start ON (one cycle only).

1

12 

F.o2t

OUT2 output 

operating mode

oF  No function;

 1  Out2 operates as Out1;

 2  Instantaneous Contact Output (ON during count);

 3  Out2 operates as  Out1 but with absolute Set time 

s.t3

;

 4  Out2 operates as  Out1 but with relative Set time 

s.t3

 in advance;

 5  Out2 operates as the buzzer.

oF

13 

F.Cnt

Count

 mode

uP UP;

dn DOWN.

uP

14 

F.buF

Buzzer

 operating mode

oF Disable;

 1  Sounds at end of the cycle for the 

s.t2

  key pressure;

 2  Sounds at end of the cycle for the 

s.t2

 period;

 3  Key pressure sound only;
 4  External buzzer only (if configured on Output 2 with 

F.o2t

 = 

5

with end of the cycle for the 

s.t2

 period

1

15 

t.UFt

-START/STOP

 button operating 

mode

oF  No function

 1  RESET only
 2  RESET-START/STOP if 

i.Fct

 = 

1

 / 

2

, or 

RESET/START/STOP if 

i.Fct

 = 

5

 / 

6

2

16 

t.Edt

Times visibility with Fast Set time 
procedure (

 key)

oF  No Set time visibility;

 1 

S.t1

;

 2 

S.t2

;

 3 

S.t1

 and 

S.t2

;

 4 

S.t3

;

 5 

S.t1

 and 

S.t3

;

 6 

S.t2

 and 

S.t3

;

 7 

S.t1

S.t2

 and 

S.t3

;

 8 

S.t1

 only directly with 

/

 keys with no 

 key pressure.

1

17 

F.but

Backup operation mode

 1  Resets the current count;

 2  Stops the current count storing the value reached;

 3  Stores the reached value and when the power returns, it restarts 

from that value if the conditions for restarting are present.

1

18 

t.Lo

Keyboard lock

oF  Lock disabled;

1 ÷ 9999 s

oF

19 

t.PP

Password parameters protection

oF  Password disabled;

1 ÷ 9999

oF

ELETTROMECCANICA CDC S.r.l - TX40

 

- MANUAL rev.2 - PAG.

9

Summary of Contents for TX40

Page 1: ...r external buzzer for signaling the end of the count The 4 digits display normally shows the counting status while the outputs status is signalled by 2 LEDs The instru ment has also 2 digital inputs for voltage free contacts that can be used for the count enabling CNT EN and Reset RES commands and can have up to 2 relay outputs or SSR for driving Solid State Relays The instrument is programmed by ...

Page 2: ... short key if pressed and released the key has no effect 1 Only s t1 Set Time value can be set with this procedure 2 Only s t2 Set Time value can be set with this procedure 3 s t1 and s t2 Set Times can be set with this procedure 4 Only s t3 Set Time value can be set with this procedure 5 s t1 and s t3 Set Times can be set with this procedure 6 s t2 and s t3 Set Times can be set with this procedur...

Page 3: ... without password unprotected To change the parameter visibility press the key and keeping it pressed press also the button The SET LED changes its state indicating the new level of parameter accessibility ON Not protected Flashing Password protected In case some parameters are set as Not protected access ing the programming mode the display first shows the Not protected parameters then the r p pa...

Page 4: ...To obtain the declared protection degree IP65 use screw type bracket optional Avoid placing the instrument in dirty environments or with very high humidity levels that may create condensation and avoid the introduction of conductive substances into the instrument Ensure adequate ventilation to the instrument and avoid installation in containers that house devices which may overheat or which may ca...

Page 5: ...fore the end steady on Count ended Reset status off After Reset display shows 0000 when counting mode is UP F Cnt uP or Set time value if the count mode is DOWN F Cnt dn While counting display shows the time that elapses increas ing if F Cnt uP or decreasing if F Cnt dn For functions that require a cycle end F o1t 1 2 at the end of the count the display flashes 0000 if F Cnt dn or the Set time val...

Page 6: ...Ft is different from oF only acts as a Reset CNT Count RESET 0 1 2 3 i fct 4 Reset Start Reset Start Stop 0 1 2 3 0 1 2 3 0 Stop Reset i Fct 5 Bistable Reset Start Stop At 1st CNT impulse the timer is reset at the 2nd the count starts at the 3rd impulse the count stops disabling the output if active and so on In this mode the front Start Stop button if t UFt 2 acts in exactly the same way as the C...

Page 7: ...in 5 different modes with F o2t parameter Se si desidera utilizzare OUT2 è possibile stabilirne il funzi onamento tramite il parametro F o2t secondo 5 diversi modi F o2t oF OUT2 Output disabled F o2t 1 OUT2 works like OUT1 OUT2 output operates exactly like OUT1 output in order to have a double output contact F o2t 2 OUT2 output works as an instant contact ON during count OUT2 is activated during t...

Page 8: ...peration The internal buzzer can be programmed using the F buF parameter to operate in the following ways oF Internal buzzer disabled 1 Activated at end of S t1 time for S t2 period sound also when keys are pressed If Reset command is given with key or digital input the buzzer is silenced immediately This mode is only active for operations that normally do not involve the use of the S t2 time this...

Page 9: ...tput operating mode oF No function 1 Out2 operates as Out1 2 Instantaneous Contact Output ON during count 3 Out2 operates as Out1 but with absolute Set time s t3 4 Out2 operates as Out1 but with relative Set time s t3 in advance 5 Out2 operates as the buzzer oF 13 F Cnt Count mode uP UP dn DOWN uP 14 F buF Buzzer operating mode oF Disable 1 Sounds at end of the cycle for the s t2 period key pressu...

Page 10: ...er supply and relay outputs and front panel Reinforced insulation between low voltage parts H or L type power supply and outputs if both are relays and the extra low voltage parts inputs Reinforced insulation between power supply and relay outputs Basic insulation between relay outputs and between relay and SSR drive output Basic insulation between H or L type power supply and inputs when a relay ...

Page 11: ...Codice d ordine T X 4 0 H I R R 1 0 Y Y P ZZ Relè Relay R Statica Static S YY OLP 3RZHU 9DF GF OLP 3RZHU 9DF H Morsettiera estraibile Removable screw terminal M Faston Faston F 0 I Terminali a vite Screw terminal Buzzer With buzzer B No buzzer Not buzzer 0 ...

Reviews: