i.Fct
=
2
-
Bistable Reset-Start/Stop
At the 1
st
impulse on the
CNT
input the timer is reset and
started, at the 2
nd
impulse, if given before the end of the
count, the count is stopped (disabling the output if active)
and the 3
rd
impulse starts a new cycle, otherwise, if the
2
nd
impulse should arrive after the end of the count it
starts directly a new cycle.
In this mode, the front
-Start/Stop
button (if
t.UFt
=
2
)
acts in exactly the same way as the
CNT
input.
CNT
Count
RESET
0 . 1 . 2 . 3 . 4 . 5
0 . 1 . 2 . 3 . 0
i.fct
=
2
Reset/
Start
Stop
Reset/
Start
Stop/
Reset
i.Fct
=
3
-
Monostable Start/Stop
Activating the
CNT
input and keeping it active, the count
is started; the count stops on the value reached when
the input is disabled (without disabling the output if ac-
tive); re-activating the
CNT
input, the count restarts from
the value reached and so on until the
Reset
signal.
In this operating mode, the front
-Start/Stop
key (if
t.UFt
is different from
oF
) only acts as a
Reset
.
CNT
Count
RESET
0 . 1 . 2 . 3
. 4 . 5 . 6 . 7
0
i.fct
=
3
Start
Stop
Start
Stop Reset
i.Fct
=
4
-
Monostable Reset-Start/Stop
Activating the
CNT
input and keeping it active, the timer
resets and starts counting, disabling the
CNT
input the
count stops disabling the output if active.
This operating mode is similar to the one of the tradition-
al timers in which counting is enabled when the instru-
ment is powered while the
Reset
occurs when power
supply is removed.
In this operating mode, the front
-Start/Stop
key (if
t.UFt
is different from
oF
) only acts as a
Reset
.
CNT
Count
RESET
0 . 1 . 2 . 3
i.fct
=
4
Reset/
Start
Reset/
Start
Stop
0 . 1 . 2 . 3
0 . 1 . 2 . 3
0
Stop
Reset
i.Fct
=
5
-
Bistable Reset-Start/Stop
At 1
st
CNT
impulse the timer is reset, at the 2
nd
the count
starts, at the 3
rd
impulse the count stops disabling the
output if active and so on.
In this mode, the front
-Start/Stop
button (if
t.UFt
=
2
)
acts in exactly the same way as the
CNT
input.
CNT
Count
RESET
0 . 1 . 2 . 3
0
0
0 . 1 . 2 . 3 . 4 . 0
i.fct
=
5
Start
Reset
Reset
Stop
Start
Stop/
Reset
i.Fct
=
6
-
Bistable Start/Stop-Reset
At 1
st
CNT
impulse the count is started, while at the 2
nd
impulse, if given before the end of the count, the count is
stopped disabling the output if active and reset, other-
wise, if the 2
nd
impulse should arrive after the end of the
count it starts directly a new cycle.
In this mode, the front
-Start/Stop
button (if
t.UFt
=
2
)
at
S.t1
time end acts exactly in the same way as the
CNT
input.
CNT
Count
RESET
0 . 1 . 2 . 3 . 0
0 . 1 . 2 . 3 . 4 . 0
0 . 1 . 2 . 0
i.fct
=
6
Start
Stop
Reset
Start Stop
Reset
Start
End
Reset
5.3
OUT1 Operating mode
The Output 1 operation can be programmed in 5 different
modes with
F.o1t
parameter:
F.o1t
=
1
-
ON DELAY
Received the
Start
signal, instrument starts counting and,
at the end of
S.t1
time, activates the
OUT1
output. The
output is disabled by the
Reset
signal.
Reset
OUT1
Start
off
off
S.t1
f.o1t
=
1
F.o1t
=
2
-
Feed-through
Received the
Start
signal, the instrument starts counting
and activates the
OUT1
output;
OUT1 is disabled
when
S.t1
time has elapsed. The output can be reactivated
only after a
Reset
and a new
Start
signal
Reset
OUT1
Start
off
f.o1t
=
2
S.t1
ELETTROMECCANICA CDC S.r.l - TX40
- MANUAL rev.2 - PAG.
6