USER’S MANUAL 

Rev. 05/2022

2PH

from 60A to 210A

018

M-RC2-60-210

CD Automation S.r.l. 

Via Picasso, 34/36 - 20025 Legnano (MI)- Italy 
Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: [email protected]   -  Web: www.cdautomation.com

Summary of Contents for Revo C 2Ph 60-210A

Page 1: ...MANUAL Rev 05 2022 2PH from 60A to 210A 018 M RC2 60 210 CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...

Page 2: ...y Standard EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Generic Emission standard EN60947 4 3 2014 Group 1 Class A emissions Generic Immunity standard EN60947 4 3 2014 Industrial Immunity SODDISFA I REQUISITI DELLA NORMA Specifica di sicurezza EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Specifica sulle emissioni EN60947 4 3 2014 gruppo 1 emissioni classe A Specifica sulle Immunità EN60947 4...

Page 3: ...y Standard EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Generic Emission standard EN60947 4 3 2014 Group 1 Class A emissions Generic Immunity standard EN60947 4 3 2014 Industrial Immunity SODDISFA I REQUISITI DELLA NORMA Specifica di sicurezza EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Specifica sulle emissioni EN60947 4 3 2014 gruppo 1 emissioni classe A Specifica sulle Immunità EN60947 4...

Page 4: ... Control Switches and equivalent to CSA C22 2 14 For more detail search for File E231578 on www ul com ESD Sensitive product use proper grounding and handling techniques when installing or servicing product Do not throw in trash use proper recycling techniques or consult manufacturer for proper disposal A NOTE marks a short message to alert you to an important detail A CAUTION safety alert appears...

Page 5: ...ironment and application AVERTISSEMENT L indice de protection du régulateur de puissance est de IP20 lorsque les couvercles sont installés et fermés L appareil doit être installé dans une enceinte qui assure toute la protection supplémentaire nécessaire pour l environnement et l application WARNING Ground the power controller via the provided protective earth grounding terminal Verify ground is wi...

Page 6: ...AUTION The thyristor units here described have been designed for use with sinusoidal networks with nominal frequency 50 60 Hz Any application with NON SINUSOIDAL distorted or disturbed networks could compromise the correct operation of the unit ATTENTION Les unités de thyristors décrites ici ont été conçues pour être utilisées avec des réseaux sinusoïdaux d une fréquence nominale de 50 à 60 Hz Tou...

Page 7: ... must first complete a Return Material Authorisation RMA form to obtain an RMA number from the Service Department A full repair service is available for customers Prior to submitting the RMA form and returning products customers are recommended to contact the technical support team to determine whether the issue can be resolved with telephone support How the RMA service works The RMA form and deta...

Page 8: ...nput features 17 6 3 Output features power device 17 6 4 Fan Specification only from 90 to 210A 17 6 5 Environmental installation conditions 18 6 6 Derating Curve 18 6 7 Calculating flow capacity of the fan 18 6 8 Wi Fi Transmitter Module 19 Installation 20 7 1 Dimensions and weight 21 7 2 Fixing holes 21 Wiring instructions 22 8 1 Terminal Positions 22 8 2 Power Terminals 22 8 3 Control Terminals...

Page 9: ...Alarm 60 12 2 AUX High 61 12 3 AUX Low 61 12 4 ComError 61 12 5 AUX Line Loss 61 12 6 SD Error 61 12 7 SHRT 61 12 8 SCR Temp 61 12 9 Line Loss 61 Enable Function in static Unit 62 13 1 Using Digital Input only 62 13 2 Using Serial Port RS485 only 63 13 3 Using Digital Input Serial Port RS485 63 13 4 Using FieldBus only 64 13 5 Using Digital Input FieldBus 65 Firing type 66 14 1 Zero Crossing 66 14...

Page 10: ...ut signal will be on and the thyristor will switch off at first Zero Crossing voltage with no input signal The benefits of thyristor units compared with electromechanical contactors are numerouses no moving parts no maintenance and capacity to switch very fast Thyristors are the only solution to control transformers and special loads that change resistance with temperature and with age L1 L2 Thyri...

Page 11: ...ostics Comprehensive power controller range Provides wide range of options from simple single phase to complex three phase loads to 690V 100kA short circuit current rating SCCR Not reviewed by UL Enables greater protection in the event of a short circuit c UL 508 Listed Shortens project schedules agency testing and expenses Control modes contactor voltage current or power Satisfies a wide range of...

Page 12: ...unit section For install the software launch the program and follow the instructions on the screen Run the software configurator and set the correct serial port number by menu setting serial com port number 2 To connect the unit at the PC it s necessary to use the micro USB 2 0 Modbus RTU cable USB connection need a driver to work properly you can find it from our site However the configuration so...

Page 13: ... the Unit 5 Go in the Operator menu Set the parameters Operative Load Voltage and Nominal Current of the load using the frontal keypad or Thyristor configurator software The Unit is ready to work The auxiliary voltage supply of the REVO C unit must be synchronized with load voltage power supply If the Auxiliary Voltage written on the identification label is different from Supply Voltage to the loa...

Page 14: ...ontrol on two phases with REVO C 2PH V Nominal voltage of the load I Nominal current of the load P Nominal power of the load Delta wiring with resistive load control on two phases with REVO C 2PH V Nominal voltage of the load I Nominal current of the load P Nominal power of the load I P 1 73V I P 1 73V 4 V V ...

Page 15: ...SIDE IND CONT EQ E231578 2RD5 Model Serial Number Max Load Current Max Load Voltage Auxiliary Voltage Fan Voltage XXXXX XXXXX XXXXX XXXXXX XXXXXX XXX 35A 480VAC 50 60Hz 90 135Vac 50 60Hz 6VA No Fan 1 Phase 1 Leg Control CAUTION WARNING hot surfaces des surfaces chaudes Risk of burns Risque de brûlure Ser NO XXXXXX XXXXXX XXX 43 2017 Mod XXX XXXXX XXXXX Contains FCC ID XXXXXX XX X Use Wire rated 75...

Page 16: ...stive Load with 3 Phase Delta Connection 1 IRSW Infrared Short wave with 3 Phase Star Connection 2 IRSW Infrared Short wave with 3 Phase Delta Connection 3 COMMUNICATION AND RETRANSMISSION 16 description description code N 1 Modbus RTU No Retransmission 0 Retransmission 4 20mA 1 Retransmission 0 10V 2 N 2 Modbus RTU No Retransmission 3 Retransmission 4 20mA 4 Retransmission 0 10V 5 N 1 Profibus DP...

Page 17: ...OFF 1Vdc 0 5Hz max Volt Analogic input 0 10Vdc impedance 15 kΩ Current Analogic input 0 20mA impedance 100 Ω 4 20mA impedance 100 Ω Potentiometer 10 kΩ min Logic input SSR Fast Enable 4 30Vdc 5mA Max ON 4Vdc OFF 1Vdc duty cycle min 100 ms max 3Hz 6 3 Output features power device Current Nominal Voltage range Ue Repetitive peak reverse voltage Uimp Latching current Max peak one cycle Leakage curren...

Page 18: ... used are for information only and is not a substitute for a proper thermal rating done by a qualified person 6 5 Environmental installation conditions Ambient temperature 0 40 C 32 104 F at nominal current Over 40 C 104 F use the derating curve max 50 C Storage temperature 25 C to 70 C 13 F to 158 F Installation place Don t install at direct sun light where there are conductive dust corrosive gas...

Page 19: ...not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Caution no changes or modifications allowed on the equipment not expressly approved by the party responsible for compliance It could void the user s authority to operate the equipment The FCC number is located on the right side of the unit see sample belo...

Page 20: ...m distances inverticaland in horizontal as represented this area must be free from obstacle wire copper bar plastic channel When more unit has mounted inside the cabinet maintain the air circulation like represented in figure without obstacle for the air flow Is necessary to install a fan to have better air circulation as calculated previously 7 30 cm 20 cm 2 cm AIR FLOW IN V AIR FLOW OUT V FAN in...

Page 21: ... s manual 21 W D H Size SR13 SR16 60A no Fan 90 210A with Fan W mm 186 186 D mm 170 170 H mm 269 273 Weight Kg 6 8 7 REVO C 2PH 7 2 Fixing holes 7 1 Dimensions and weight H1 SR13 60A no Fan 256 SR16 90 210A with Fan 260 5 5 5 5 165 H1 ...

Page 22: ...es AWG wire terminal type ZMVV terminal tightening torque in the table below Power cable torque suggested Type Connector Type Torque Lb in N m Wire Range mm AWG MAX Current Terminals Wire Terminals UL Listed ZMVV 060 090 120 Screw M6 70 8 8 0 16 5 25 3 35 2 150 Fork Spade Terminal Copper Tube Crimp Lug 150 180 210 Screw M8 141 6 16 0 50 0 70 00 90 000 250 Fork Spade Terminal Copper Tube Crimp Lug ...

Page 23: ...60A to 210A User s manual 23 Locations of the line power load earth ground and control signal connections T1 T3 L1 L3 5 4 3 2 1 Iout 0 0A Ref 0 0 M4 Ethernet or Profibus port M1 M3 M2 Cover closed Cover tipped forward ...

Page 24: ...REVO C 2PH from 60A to 210A User s manual Suggested wiring mode connect the cables below not above Correct Not correct Maintain adequate distance to avoid obstructing the air flow See the figure on page 20 ...

Page 25: ...nce ext feed back 9 Slave Output 10 Retransmission Output 11 RS485 A 12 RS485 B 13 0V GND 14 C Common contact alarm relay output 15 NC Normally Close contact alarm relay output Thermal or SC HB 16 NO Normally Open contact alarm relay output Thermal or SC HB 8 3 2 Terminal block M2 Terminal Description L1 Aux Voltage Supply for electronic boards and synchronization See order code for the Value Not ...

Page 26: ... 4 RS485 A 5 RS485 B 8 4 Schematic Caution this procedure must be performed only by qualified persons A B Ethernet Profibus 14 11 12 16 15 6 5 7 4 3 2 1 8 13 1 2 4 5 F1 F2 10 24V GND FAN power USB Retransmit output Second comm port 24Vdc power input RS485 Relay output Analog Input 1 Digital Input 2 Digital Input 1 10Vdc supply Analog Input 2 Micro USB M1 M4 M1 M3 L2 L1 Power supply M2 Microprocess...

Page 27: ...ld be acceptable as an external fuse following national electric code guide for resistive heating of 125 load current rating to protect external wires 2 The auxiliary voltage supply of the REVO C unit must be synchronized with load voltage power supply If the Auxiliary Voltage written on the identification label is different from Supply Voltage to the load use an external transformer as designated...

Page 28: ... manual M1 Analog Input 1 SSR INPUT SSR Input 4 30Vdc 5mA Max ON 4Vdc OFF 1Vdc Frequency 3Hz Max On time min 100 ms 8 4 1 SSR Control Input schematic For SSR input use follow the schematic below and configure Digital Input 1 as Fast Enable ...

Page 29: ...Voltage Supply Analog Inp 2 0 10VDC 4 20mA Reference Ext FeedBack Analog Inp 1 0 10VDC 4 20mA ANALOG SET POINT SLAVE OUT RETRANS OUT T1 T2 T3 T1 T2 T3 Delta Star Load Type Note Aux Voltage and Load Voltage must be synchronized 1 The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator The Fuse must be branch circuit protection For UL any listed UL branch circ...

Page 30: ...he keys are used as follows Press to Function Scroll through the parameters on the home page Local Remote Switch between local and remote set point for power demand Up Increment power demand set point when set to local Down Decrement power demand set point when set to local Press and hold for about two seconds to access the menus To view the status parameters Press Function once to advance from on...

Page 31: ...Menu Password Parameter used to Operator 0 View measured values and basic settings including current voltage and set point Setup 2 Configure the power controller for the load Adv Setup 10 Configure the operation and performance of the power controller in the application Hardware 5 Configure the functions of the analog and digital inputs and outputs and the re transmission parameters Comm 3 Configu...

Page 32: ...o low ComError Communication Watchdog error Line Loss Line power not detected SD Error SD card error SHRT Short Circuit on SCR SCR Temp Thermal Switch over temperature Line Loss L1 and L2 not detected Aux High SP 100 1 Local Remote Flashing Poweroutput set locallyorvia communications Off Power output set remotely via analog input 2 Enable On Output enabled Off Output disabled 3 Communications Flas...

Page 33: ...on Monitoring Set Point Out Scale Firing Type Analog in 1 Port 1 Baud Dig in 1 Volts Out Nom Line V Min Cycle Analog in 2 Port 1 Addr Dig in 2 Current Nominal I Start Ramp An2 Funct Port 2 Baud Enable Power SP Select Delay DI1 Functn Watchdog SP Source Volts In Cycle Time DI2 Functn WD Reset Analog In1 Frequency Feedback Alm Out Fn Wi Fi Addr Analog In2 Pwr Factor Pb Power Retransmit Field Name SW...

Page 34: ...ll phases 0 to 1023 V 11 Read Only Power Indicates the average RMS power output 0 to 100 12 Read Only Volts In Indicates the average RMS voltage input 0 to 65535 V 47 Read Only Frequency Indicates frequency of the power input 0 to 655 35 Hz 9 Read Only Pwr Factor Indicates power factor of the output power 0 to 1000 102 Read Only Load Ω Indicates the resistance of the load 0 to 655 35 Ω 46 Read Onl...

Page 35: ...viding the set point is 5V and output scaling is 80 then the effective set point is 40 0 to 100 0 16 Read Write Parameter Name Description Default Range Unit Modbus Address Par Type Nom Line V Set the nominal value for the line voltage input 220V 0 to 1023 V 37 Read Write Nominal I Set the nominal load current Maximum current 0 to 6000 0 A 38 Read Write SP select Choose the source for the remote s...

Page 36: ...r Type Min Cycles Set the minimum number of On cycles and off cycles for burst firing 8 0 to 999 9 n 20 Read Write Start Ramp Set the number of half cycles over which the power ramps each time the output turns on 0 0 to 1024 n 25 Read Write Delay Set the firing delay degrees Applies to burst firing with delay trigger 1 1 to 255 22 Read Write Cycle time Set the duration of one on off cycle in incre...

Page 37: ... the threshold of resistance that activates the Heater Break alarm This setting is in percentage of the nominal load resistance 100 0 to 100 0 29 Read Write HB Delay Set a delay between when the resistance drops below the value set for a heater break sensitivity and when the heater break alarm is indicated This set increments of 50mSec 50 2 5 sec 0 to 255 0 to 12 75 sec 28 Read Write Logging Enabl...

Page 38: ...ue 0 10V 0 to 10 Vdc or 10 000Ω 1 4 20mA 4 to 20 mAdc 2 0 20mA 0 to 20 mAdc 3 DEFAULT 0 10V 1 Parameter Name Description Default Modbus Address Par Type Analog In 2 Choose the type of signal to be measured by analog input 2 1 105 Read Write Option Description Value 0 10V 0 to 10 Vdc or 10 000Ω 1 4 20mA 4 to 20 mAdc 2 0 20mA 0 to 20 mAdc 3 DEFAULT 0 10V 1 Parameter Name Description Default Modbus A...

Page 39: ...able 8 Alarm reset 9 DEFAULT Voltage Feed back 2 SSR Input 4 30Vdc 5mA Max ON 4Vdc OFF 1Vdc Frequency 3Hz Max On time min 100 ms Parameter Name Description Default Modbus Address Par Type DI2 Functn Choose how the signal detected by digital input 2 is used 0 33 Read Write Option Description Value Enable Enable power output 0 V Feedback Use voltage feed back when on 2 Local Rmt Local when on Remote...

Page 40: ...k or short circuit condition only when included in the option selected for Alarm Output Function 1 34 Read Write Option Description Bit Heater Break Heater Break 0 Short Circuit Short circuit 1 Therm SCR is over temperature 3 Communication Communication watchdog error 4 DEFAULT None Alarm Bitwise is allowed Parameter Name Description Default Modbus Address Par Type Retransmit Choose which paramete...

Page 41: ... Output xV where x is the Nominal Line Voltage 4mADC 0V 20mADC xV 0mADC 0V 20mADC xV 0VDC 0V 10VDC xV 999 9 I Output xA where x is the Nominal Line Current 4mADC 0A 20mADC xA 0mADC 0A 20mADC xA 0VDC 0A 10VDC xA 999 9 Power 100 4mADC 0 20mADC 100 0mADC 0 20mADC 100 0VDC 0 10VDC 100 100 Parameter Name Description Default Modbus Address Par Type Rtx Type Choose type of signal for the retransmission o...

Page 42: ...2 30 Read Write Option Value 9600 0 19 2K 1 38 4K 2 115 2K 3 DEFAULT 38 4K 2 Parameter Name Description Default Range Modbus Address Par Type Port 1 Addr Set the address for the primary serial port 1 0 to 255 31 Read Write Port 2 Baud Choose the baud rate for the primary serial port 2 45 Read Write Option Value 9600 0 19 2K 1 38 4K 2 115 2K 3 DEFAULT 38 4K 2 Parameter Name Description Default Modb...

Page 43: ... Name Indicate the name of the unit max 16 characters 83 84 85 86 87 88 89 90 Read Only Port 2 Addr Set the address for the secondary serial port or the Profibus Address 0 0 to 1024 122 Read Write Port 2 Indicates the type of secondary communication port 119 Read Write Option Description Value Disabled No secondary communication port 0 Ethernet Modbus TCP or ProfiNet 1 RS 485 RS 485 2 Parameter Na...

Page 44: ...alue Off 0 On 1 Parameter Name Description Modbus Address Par Type Dig In 2 Indicate the state of the signal to digital input 2 13 bit9 Read Only Option Value Off 0 On 1 Parameter Name Description Modbus Address Par Type Enable Indicate whether or not the power controller is enabled The enable signal must be on for the unit to output power to the load 14 bit2 Read Only Option Value Off 0 On 1 Para...

Page 45: ...ingle Phase 7 RC 2 Two Leg three phase 8 RC 3 Three Leg three phase 9 RC 3P Three Leg three phase with phase angle capability 10 Parameter Name Description Range Unit Modbus Address Par Type Max Voltage Indicates the maximum voltage rating of the power controller 0 to 1023 V 41 Read Only Max Current Indicates the maximum current capacity of the power controller 0 to 9999 A 62 Read Only Aux Voltage...

Page 46: ...ect it before applying power NOTE the power of the USB port is limited and not designed to power industrial cards so it manages to feed only the essential parts of the electronics For complete control you need to power up the auxiliaries of the power controller 10 3 Recipes A recipe is a file that store the settings of power controller internal parameter Is used to save a power controller configur...

Page 47: ...ler REVO C 3PH for 3 phase power controller 4 Choose Serial Port From the Setting Serial Port menu 5 In value Port select the connected COM port to the power controller see the note below 6 To verify communications click Test 7 Click OK NOTE to determine which port is connected to the power controller you can in the Windows Device Manager under Ports COM LPT looking for the COM port named LPC USB ...

Page 48: ...k Save button NOTE In the simple view the change are not live so to take effect the change in simple section is necessary to download it following the download procedure 10 5 2 To edit a setting in a recipe 1 Click Simple if not already on the simple view 2 Click Open existing recipe 3 Locate and select the recipe file and click Open 4 Click OK 5 Click the menu with the setting you want to change ...

Page 49: ...t view 1 Click Test if not already on the test view 2 Click Online 10 5 5 To log in on the test view to change the digital input and analog input functions 1 Click the Access Level value zero when logged out 2 Type the password 1111 3 Click OK 10 5 6 To log out the test view 1 Click the Access Level value 2 Click Log out 3 Click OK 10 5 7 To view data on the scope 1 Click Test if not already on th...

Page 50: ... Log Enabled 6 Click Set Time 7 If necessary Set the date and time and close the date time window 8 Set Log Time to the number of seconds between records 9 Click Connect 10 Click Config 11 Click Load Configuration to view the current list of logged parameters 12 For up to ten parameters to log Click to add a parameter to the list In a row in the list either Type a parameter s Modbus address in the...

Page 51: ...scribed the Configurator Software and how use it 10 6 1 Program Window Main Menu Access these menus File menu Exit close the program Setting menu Language open language Settings dialog box Serial Port open Serial Port dialog box Option open General Option dialog box Help menu Message Log open a serial communication message view About displays the About dialog with the program name and version and ...

Page 52: ...he standard default settings Open existing recipe open an existing recipe file Upload from unit create a new recipe with the value uploaded from a connected power controller Close close the current recipe Save save the recipe in a file Save as save a copy of the recipe in a file Download to unit send the current recipe parameters in the connected power controller Print print the recipe see sample ...

Page 53: ...xpand the options Status and Setup Indicators Digital input status light on when the input is a a closed circuit Enable indicator light on when the power controller is enabled Enable Disable button click on to enable the power controller if a digital input is not configured for this function ON indicator light on when there is demand for the output to be on SC indicator light on when there is a sh...

Page 54: ...w the set point signal from analog input 1 The value is a percent of full scale or can be set with the reference slider Soft Start Time show the time over which set point changes are ramped Output Scaling show the scaling applied to the set point signal before it is used by the control loop Voltage indicator show RMS load voltage Power indicator show RMS load power Current indicator show the RMS l...

Page 55: ...ent data Stop Play click toggle the live view or Hystorical view of graphic signal Scroll right click move the chart right to view older data The Actions to Clear to clear the data from the graph Save to save a JPEG image of the Load Analyzer window with the current trends Export to open a window that includes the trend graph and table with the currently displayed data that can be saved as a JPEG ...

Page 56: ...lerto the computer Delete File erases the selected file from the power controller Close closes the Data Log window and close the log mode on power controller 10 6 6 Data Log Configuration window Data log configuration window is used to view and set the parameter log table Close closes the window Load Configuration refresh and displays the list of parameters being logged Logged parameters list the ...

Page 57: ...hoose user settable options for the Configurator software Language Available Languages choose the language used in the program NOTE to be active the language change need close and open again the configuration software Serial Port Set the serial port parameter Test click to test for communication with a power controller via the selected port Port select the computer s COM port to use to communicate...

Page 58: ... the set point SP Analog In 1 2 this signal chooses which of the two analog inputs is used as the source of the set point when the remote set point is in effect When this signal is off analog input 1 is the source of the remote set point When the signal is on analog input 2 is the source of the remote set point Logging this signal turns data logging on or off When the signal is on data is logged W...

Page 59: ...8 4 Schematic 11 4 Alarms and Alarm Relay Output When an alarm occurs and while the condition persists the alarm relay is de energized The alarm relay is energized when power is supplied to the controller s electronics via the auxiliary power input and there are no alarms Choose which conditions determine the alarm relay output with the Alarm Function setting on Paragraph 9 4 4 Hardware menu NOTE ...

Page 60: ...ed by the HB Sense parameter Example Resistance 2200W 220V power voltage A 2200 220 10A nominal V 220 V nominal I 10A Nominal resistance R 22 Ohm HB sense parameter 20 threshold value 22 22 x 20 100 22 4 4 Ohm 26 4 Ohm 22 R V I HB sense 20 26 4 NO ALARM 30 25 20 15 10 5 0 Ohm ALARM No HB delay 22 R V I HB sense 20 26 4 30 25 20 15 10 5 0 Ohm HB delay es 2 5 sec NO ALARM 22 R V I HB sense 20 26 4 3...

Page 61: ...rm is activated when there is no data passage within the time established by the WD reset parameter 12 5 AUX Line Loss This alarm is activated when there is no auxiliary voltage 12 6 SD Error When the Logging option is present this alarm is activated when a writing error is found in the SD memory 12 7 SHRT This alarm is activated if the unit detects a short circuit in one of the power devices This...

Page 62: ...act abbreviated as SwS and the command from digital input is abbreviated as SwH 13 1 Using Digital Input only By setting the Digital Input as Enable it is possible to control the enable from Digital Input By closing the digital input via SwH contact the unit will be enabled and by opening the digital input the unit will be disabled The status can be read on bit 2 of parameter 14 on the serial port...

Page 63: ...strument Enable Software switch from communication 13 3 Using Digital Input Serial Port RS485 The static unit has the serial port as standard RS485 Modbus RTU always present The external contact SwH and the internal software contact SwS are connected in series therefore if you want to enable the static unit both contacts must be enabled Each variation of the SwH contact connected on the digital In...

Page 64: ...ld bus it is possible to change the status of the SwS contact with bit 2 of the Command table See the communication manual of the respective FieldBus NOTE The parameters written are command table reference rescaling if the FieldBus is active but disconnected these values will be forced to 0 SwS Switch software Sws DI Software switch from communication DI Function Configurated like Not Used or diff...

Page 65: ... possible to change the status of the SwS contact with bit 2 of the Command table See the communication manual of the respective FieldBus bearing in mind that the SwH contact must also be closed to enable it This configuration is useful for having an external contact for a safety or emergency alternative to the FieldBus NOTE The parameters written are command table reference rescaling if the Field...

Page 66: ...utput from temperature controllers and the Thyristor operates like a contactor The Cycle time is performed by temperature controller ZC minimizes interferences because the Thyristor unit switches ON OFF at zero voltage 14 2 Burst Firing The Burst Firing is similar to the Single Cycle but consecutive cycles ON are selectable between 2 and 255 with input signal equal at 50 When is specified 1 the fi...

Page 67: ...age demand This control mode compensates the voltage fluctuation of the incoming line supply I Current feed back The input signal is proportional to the current output This means that input signal becomes a current demand This control mode maintain the current also if the load impedance changes P VxI Power feed back The input signal is proportional to the power output This means that input signal ...

Page 68: ...the table below The range of the auxiliary voltage that can be set depends on the transformer mounted on the board see the ordering code on Digit 8 see table Order Code As ordered Change to Jumper JP1 JP2 are linked Link only Jumper JP3 Transformer range Line voltage Transformer range Line voltage RC2_ _ _ _1 90 135V 100 120V 180 265V 200 208 220 230 240V RC2_ _ _ _2 180 265V 200 208 220 230 240V ...

Page 69: ... 210A User s manual 69 Sequence for writing the Aux Voltage value Click on Actual Level and enter the password 1234 to access level 4 Click on the Fast Tune button Enter the voltage value in the AuxVoltage field press enter ...

Page 70: ...y Supply input in Terminal Block M4 optional terminals 1 and 2 can be used as an auxiliary power supply when the main network fails This auxiliary power supply keeps the communication circuits powered allowing data to be transferred to the supervision system 17 5 4 3 2 1 24VDC Input 5 Current 500mA option ...

Page 71: ...nication Manual for details 18 19 M4 Terminal Description 1 24V 2 GND 3 Not connected 4 RS485 A 5 RS485 B The serial communication port RS485 is available on the Command Terminals On this port may be done a network up to 127 REVO C Profibus Configuration Ethernet Configuration Second Serial 485 Configuration Connectors M4 Caution If Bus port is not connected or in error all writable parameters are...

Page 72: ...hort circuits The Fuses must have I2 T 20 less than thyristor s I2 T The warranty of thyristor is null if no proper fuses are used Type Fuse Code Spare Part Total Current ARMS Vac FUSE I2 T value Suggested A2s at500V FUSE I2 T value Suggested A2s at660V Quantity for each phase 060 FU2055920 160 160 660 10780 15400 1 090 FU2055920 160 160 660 10780 15400 1 120 FU2055920 180 180 660 14280 20400 1 15...

Page 73: ...ses Replacement Open the cover and remove the screws then replace it with the correct fuse use the screws with a proper suggested torque indicated below Type Screw Torque Lb in N m Screw Torque Lb in N m 60 120A M6 44 2 5 0 M5 31 3 5 150 210A M6 44 2 5 0 ...

Page 74: ...CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...