RRS-4 Technical Manual 7/20/2011
6.1.1 Unit Setup Test/No Test Position Configuration
Once selecting a breaker under unit setup (for example purposes GE 1200 has been
selected), the operator will be navigated to a screen displaying the chosen breaker and
the option to make modifications to the information specific to the Test or No Test
position.
To edit or enter data for the unit operating the breaker in the Test position, ensure
'Test' is highlighted then press "Configure". For example purposes, the Test position has
been selected.
1.
Test
– When pressed, the Test button highlights the Test Selection Indicator (as
shown in Figure 21 for example) allowing configurations in the Test position;
Some switchgear have a mandatory hard stop for test position; these breaker
styles require this mode of operation
2.
No Test
– When pressed, the No Test button highlights the No Test Selection
Indicator allowing configurations in the No Test position; this will allow the
breaker to rack Dis.-Connect in one operation
3.
Main Type 1
– Breaker name 1 from list of all breaker names
Figure 21: Unit Setup test options
1.
2.
6.
3.
5.
4.