DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
109
9M02-9249-A001-EN
Revision A
Name
Range
Default
Description
Closed Loop >
Gain
1 ~ 30
in 0.1 increments
19.0
The amount to increment or decrement
the RPM when the sensed value is
outside of the deadband. This number
does not represent an actual RPM. A
larger gain will generate a larger RPM
change than a smaller gain for the same
size error. This value must be tuned for
each installation.
Setpoints > Main-
In (Maintain In
Setpoint)
1 ~ 900
in 0.1 increments
300.0
The level set-point to attempt to maintain.
Only applies if the Control Type is set to
Maintain-In. This value takes on the units
of the Aux sensor set in the Closed Loop
> Sensor In menu.
Setpoints > Main-
Out (Maintain Out
Setpoint)
1 ~ 900
in 0.1 increments
500.0
The level set-point to attempt to maintain.
Only applies if the Control Type is set to
Maintain-Out. This value takes on the
units of the Aux sensor set in the Closed
Loop > Sensor In menu.
Setpoints >
D (High
Deadband)
1 ~ 30
in 0.1 increments
3.0
The high limit of the deadband.
Setpoints >
Deadband- (Low
Deadband)
1 ~ 30
in 0.1 increments
3.0
The low limit of the deadband.
Thresholds > High
Edge (High Limit)
1 ~ 900
in 0.1 increments
700.0
The high saturation. The maximum level
at which the RPM control is fixed. This
value takes on the units of the Aux sensor
set in the Closed Loop > Sensor In menu.
Thresholds > Low
Edge (Low Limit)
1 ~ 900
in 0.1 increments
100.0
The low saturation. The minimum level at
which the RPM control is fixed. This value
takes on the units of the Aux sensor set in
the Closed Loop > Sensor In menu.
Thresholds > Max
RPM (Max Limit
RPM)
500 ~ 4000 RPM
in 1 RPM increments
3200 RPM
The fixed RPM that should be used when
the level rises above the High Edge.
Thresholds > Min
RPM (Low Limit
RPM)
500 ~ 4000 RPM
in 1 RPM increments
1000 RPM
The fixed RPM that should be used when
the level falls below the Low Edge.
5.9.4 Pump System
This menu contains various settings related to pumping applications. It is used in conjunction with the Application
menu. The application menu is the end user-oriented menu which allows the end user to make changes.
In the front panel, the following settings are located under Other Config > Pump System.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...