CANplus
TM
CP800
Control Panel Operation Manual
30
9M02-1000-A201-EN
Revision E
7.4.6 Configuring RPM and Time Profile Settings
Setting
Description
Idle RPM
Selects the RPM that the control system will request for idle speed. If the
engine is started, it will always begin running at Idle speed.
Intermediate RPM
Selects the RPM that the control system will request for intermediate
speed. Intermediate speed is a specific speed point at which the engine
will pause during the ramping up cycle. The intermediate speed can be
used to prime a pump or charge lines.
Run RPM
Selects the RPM that the control system will request for run speed. The
run speed is the normal operating speed. If the Maintain Transducer Level
“cruise control” is enabled, the control panel will ignore the Run RPM and
instead will dynamically throttle the engine to maintain the level.
Warm Up Time
The time (in seconds) the engine will stay at the Idle RPM after starting.
Ramp to Intermediate Time
The time (in seconds) the engine will take to ramp from the Idle RPM to
the Intermediate RPM.
Intermediate Time
The time (in seconds) the engine will stay at the Intermediate RPM.
Ramp to Run Time
The time (in seconds) the engine will take to ramp from the Intermediate
RPM to the Run RPM.
Ramp to Cooldown Time
The time (in seconds) the engine will take to ramp from the Run RPM to
the Cooldown RPM.
Cooldown Time
The time (in minutes) the engine will stay at the Cooldown RPM before
turning off the engine.
7.5 Transducer
The transducer can be configured for Autostart levels, scaled values, units of measure for setup and display,
calibration, warning and fault levels.
7.5.1 Autostart Triggers
The low and high Autostart trigger levels can be set via the
Autostart
→
Transducer
→
Autostart Triggers
menu.
7.5.2 Setup
There are a number of parameters that must be configured for proper operation of the transducer. These
configurations can be set via the
Autostart
→
Transducer
→
Setup
menu.
•
Type and Range
–
4 mA Scaled Value
*
Value in setup units represented by a 4 mA reading
–
20 mA Scaled Value
*
Value in setup units represented by a 20 mA reading
–
Setup Units
*
Units used to setup the 4 mA and 20 mA scaled values