CANplus CP1000
Control Panel Operation Manual
*Patent Pending
30
9M02-1000-A401-EN Revision G
6.4.6 Configuring RPM and Time Profile Settings
Setting
Description
Idle RPM
Selects the RPM that the control system will request for idle speed. If the
engine or motor is started, it will always begin running at Idle speed.
Intermediate RPM
Selects the RPM that the control system will request for intermediate
speed. Intermediate speed is a specific speed point at which the engine or
motor will pause during the ramping up cycle. The intermediate speed can
be used to prime a pump or charge lines.
Run RPM
Selects the RPM that the control system will request for run speed. The
run speed is the normal operating speed. If the Maintain Transducer Level
“cruise control” is enabled, the control panel will dynamically throttle the
engine or motor to maintain the level using the Run RPM as the max.
Warm Up Time
The time (in seconds) the engine or motor will stay at the Idle RPM after
starting.
Ramp to Intermediate Time
The time (in seconds) the engine or motor will take to ramp from the Idle
RPM to the Intermediate RPM.
Intermediate Time
The time (in seconds) the engine or motor will stay at the Intermediate
RPM.
Ramp to Run Time
The time (in seconds) the engine or motor will take to ramp from the
Intermediate RPM to the Run RPM. If the Maintain Transducer Level is
enabled, the panel will not ramp to the Run RPM but will start throttling the
engine or motor to maintain the level.
Ramp to Cooldown Time
The time (in seconds) the engine or motor will take to ramp from the Run
RPM to the Cooldown RPM.
Cooldown Time
The time (in minutes) the engine or motor will stay at the Cooldown RPM
before shutting down engine or motor
Instead of a time-based system, the ramp profile can wait for an event to occur before Ramping to Run. These
events can be one of the following, for example:
•
Pump is primed
6.5
Transducers
The transducers can be configured for Autostart levels, scaled values, units of measure for setup and display,
calibration, warning, and fault levels.
6.5.1 Autostart Triggers
The low and high Autostart trigger levels can be set via the
Autostart
→
Transducer
→
Autostart Triggers
menu.
6.5.2 Setup
There are a few parameters that must be configured for proper operation of the transducer. These configurations
can be set via the
Autostart
→
Transducer
→
Setup
menu.