cashco 6A00 Installation, Operation And Maintenance Manual Download Page 1

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

IOM-6A00 IIA1/IIA

03-16

SECTION I

I. DESCRIPTION AND APPLICATION

As autonomous safety systems for intended use in hazardous areas, the listed types comply with the
requirements of the European Regulations 94/9/EC (ATEX95) and the harmonized standard for flame
arrestors EN ISO 16852.
This document applies to the following Types according to the Charts 1-3. The limit values of the maximum
operating pressure P

0

,

 the maximum operating temperature T

0

 and the maximum distance to the ignition

source L

U

 must be kept!

Model 6A00

Inline Deflagration Flame Arrestor

Ex- Gr.

Pipe size

Type

P

0

[kPa(abs.)]

T

0

[

o

C]

L

U

[m]

EC-type

examination

certi

fi

 cate

IIA1

DN20    (3/4”)

6A0B1

110

60

1.00

IBExU13ATEX2122 X

DN25      (1”)

6A0C1

110

60

1.25

DN32  (1-1/4”)

6A0K1

110

60

1.60

DN40  (1-1/2”)

6A0U1

110

60

2.00

DN50       (2”)

6A0V1

110

60

2.50

DN65  (2-1/2”)

6A131

110

60

3.25

DN80       (3”)

6A1B1

110

60

4.00

DN100     (4”)

6A1K1

110

60

5.00

DN125     (5”)

6A1T1

110

60

6.25

DN150     (6”)

6A1U1

110

60

7.50

Ex- Gr.

Pipe size

Type

P

0

[kPa(abs.)]

T

0

[

o

C]

L

U

[m]

EC-type

examination

certi

fi

 cate

IIA1

DN20    (3/4”)

6A0B6

160

60

1.00

IBExU13ATEX2148 X

DN25       (1”)

6A0C6

160

60

1.25

DN32  (1-1/4”)

6A0K6

160

60

1.60

DN40  (1-1/2”)

6A0U6

160

60

2.00

DN50        (2”)

6A0V6

160

60

2.50

DN65  (2-1/2”)

6A136

160

60

3.25

DN80        (3”)

6A1B6

160

60

4.00

DN100      (4”)

6A1K6

160

60

5.00

DN125      (5”)

6A1T6

160

60

6.25

DN150      (6”)

6A1U6

160

60

7.50

DN200      (8”)

6A226

160

60

10.0

DN250     (10”)

6A2A6

160

60

12.5

DN300     (12”) 

6A2H6

160

60

15.0

Chart 1: Types of explosion group IIA1 (MESG > 1.14 mm) protect against deflagration and endurance burning.

Chart 2: Types of explosion group IIA1 (MESG >1.14 mm) protect against deflagration and short time burning,
 

maximum time of stablized burning = 1minute.

ISO Registered Company

Summary of Contents for 6A00

Page 1: ...110 60 1 25 DN32 1 1 4 6A0K1 110 60 1 60 DN40 1 1 2 6A0U1 110 60 2 00 DN50 2 6A0V1 110 60 2 50 DN65 2 1 2 6A131 110 60 3 25 DN80 3 6A1B1 110 60 4 00 DN100 4 6A1K1 110 60 5 00 DN125 5 6A1T1 110 60 6 25...

Page 2: ...ected against endurance burning Attention The protection against endurance burning refers exclusively to the existence of pure hydrocarbons Any application extended to other chemicals requires additio...

Page 3: ...ufacturer 2 Type designation 3 Number of the EC type examination certificate 4 Serial number year of manufacture 5 Pipe size 6 Marking hazardous area G for gas and vapor 7 Explosion group 8 Standard f...

Page 4: ...the flame arrestor The distance LU between the potential ignition source and the deflagration inline flame arrestor shall not exceed the data given in the Charts 1 3 If the flame arrestor is marked a...

Page 5: ...65 DN80 2 1 2 3 DN100 4 DN125 DN150 5 6 DN200 8 DN250 10 DN300 12 6 7 CS 27 54 93 230 465 800 SST 25 45 80 185 400 680 8 SST 12 12 25 45 185 400 680 CS Carbon Steel SST Stainless Steel WARNING SYSTEM...

Page 6: ...the sales representative can quote a price for each of the required parts Item No Description Maintenance Kit A 1 Housing 1 2 Housing 2 3 Crimped Metal Ribbon X 4 Star 5 Round Ring X 6 Bolts 8 Center...

Page 7: ...7 IOM 6A00 Figure 5 2 Standard Flanged Connections Figure 6 Standard Flanged Connections with Cage...

Page 8: ...re not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability We reserve the right to modify or improve the de...