REVO C/REVEX Service Panel Engineering Manual V1.0     Page 1 

 

 

 

 

 

 

Engineering manual 

 

 

 

REVO C / REVEX service terminal 

PLEASE  READ  THIS  MANUAL  BEFORE  ATTEMPTING  TO  CONNECT 
AND/OR  SWITCHING  POWER  ON  THE  MODULES.  THIS  DOCUMENT 
CONTAINS  VERY  IMPORTANT  INFORMATION  THAT  WILL  PREVENT 
WRONG CONNECTIONS THAT CAN CAUSE DAMAGE TO THE UNITS.

 

 

Summary of Contents for REVEX

Page 1: ...Engineering manual REVO C REVEX service terminal PLEASE READ THIS MANUAL BEFORE ATTEMPTING TO CONNECT AND OR SWITCHING POWER ON THE MODULES THIS DOCUMENT CONTAINS VERY IMPORTANT INFORMATION THAT WILL PREVENT WRONG CONNECTIONS THAT CAN CAUSE DAMAGE TO THE UNITS ...

Page 2: ...EVEX service terminal This manual should enable you to use your machine to full satisfaction Every effort has been made to provide you with maximum performance ergonomics and benefits from this premium quality product Version History 07 02 2020 Initial version V1 0 for software version V100 001 ...

Page 3: ...l thoroughly before starting up the system This can prevent damage and a dangerous situation for yourself and the end user of the equipment WARNING The configuration setup must be performed by technically educated personnel This can prevent damage and a dangerous situation for yourself and the end user of the equipment This system consists of 1x Pro face GP4116 touchpanel with COM1 3 wire RS 485 i...

Page 4: ... symbols 5 Touchscreen introduction 6 Touchscreen maintenance 6 Touchscreen cleaning 7 1 CONNECT REVO C REVEX MODULE AND GP 4116 screen 8 1 1 Connect communication cable between REVO C REVEX and GP4116 8 1 5 Connect power to GP 4116 11 2 CONFIGURING THE REVO C REVEX COMMUNICATION PORT SETTINGS 12 3 SETUP of GP4116 touchpanel 17 ...

Page 5: ...ur attention Hint Useful hints for ease of operation Printed in Blue Info Information you should know to fully understand your system and benefit from its properties Printed in green Warning Read these important messages before executing the desired operation Printed in red Warning Read these important messages before executing the desired operation Printed in red ...

Page 6: ...ctice this means that all objects are positioned and sized such that they can be touched easily with your finger without the need for a stylus or precise positioning A soft tipped stylus can be used if preferred but is normally not required for proper operation Touching objects on a touch screen can be compared with a mouse click on a computer screen Based on the shown graphical user interface and...

Page 7: ...ands Each valid command will invoke a short beep confirming the reception of the touch However whether or not the actual action is performed depends also on other conditions Avoid applying excessive force on the touch screen and never use sharp or hard objects e g nails tools kitchenware or a pencil to operate it In either case you might damage the screen and void your warranty Touchscreen cleanin...

Page 8: ...was supplied with the REVO C REVEX module 1 1 Connect communication cable between REVO C REVEX and GP4116 You can connect the RS485 modbus communication cable between the REVO C M5 port and the GP4116 COM1 connector REVO C M5 point 9 B and M1 point A white wire to GP4116 and M1 point B brown wire to GP4116 REVEX different connections depending on the size of the thyristor For 30 40A and 60 90A use...

Page 9: ...the REVEX communication port for higher currents than above For good EMC EMI immunity use a Lapp RS 485 modbus communication cable that is 120ohm impedance corrected Use Lapp Unitronic bus LD 2x2x0 22 article number 2170204 You can order per meter at Conrad electronic ...

Page 10: ...10 Please also note the red and blue wires that are bridging signals on the GP 4116 connector For completeness here an extra informative picture from the Pro face manual You see here a description of all signals that are present on the GP4116 COM1 connector ...

Page 11: ...hscreen Please regard the polarity of the 24VDC signals This is also marked on the touch screen The incorrect connection of the power supply can result in irrepairable damage that is outside the normal warranty The FG functional ground must also be connected to the central PE protective earth connection of the unit This can prevent damage to the touchscreen in case of an electrostatic discharge ...

Page 12: ...ice touchscreen you need to adjust the Modbus slave port on each REVO C REVEX to a Modbus address 1 2 3 or 4 and 19200bps N81 First connect the 24VDC power supply to the Revo C or REVEX unit see manual and make sure you have connection with it via a micro usb cable maybe your mobile phone has it First check in windows on which comport the interface to the Revo C REVEX has been mapped Keep on using...

Page 13: ...REVO C REVEX Service Panel Engineering Manual V1 0 Page 13 ...

Page 14: ...REVO C REVEX Service Panel Engineering Manual V1 0 Page 14 Select Revo C or REVEX and push upload from unit ...

Page 15: ...neering Manual V1 0 Page 15 Set address 1 and push read All parameters will now be read from the Revo C REVEX takes a short while just wait Push test click on the blue actual level 0 and login with 1111 when you want to make changes ...

Page 16: ...ring Manual V1 0 Page 16 Now move the window a bit to the left and push ONLINE to go online with the Revo C REVEX Push communications Set the COM1 comport speed to 19200bps and the desired Modbus address of the module either 1 2 3 or 4 ...

Page 17: ...les are configured properly we can start the GP4116 screen for the first time First we need to configure the touchpanel in the initial setup This will only be necessary when the screen starts for the first time After that the settings are stored and the screen will start automatically First select the language and push next ...

Page 18: ...the system There can be a mix of both the REVEX and REVO C modules of different sizes since the communication protocol of the REVEX and the REVO C is the same This is an overview what has been selected in the setup Push next and the settings will be stored in the screen and the system is ready for use ...