CAS Systems TT-WIS Installation & Operation Instructions Download Page 1

TT-WIS

Web Interface Server 

Installation/Operation Instructions 

General Information 

Please read these instructions and keep them in a safe place. These 
instructions must be followed carefully to ensure proper operation. 

Web Interface Server (TT-WIS) module provides a convenient way 
for people to know the real-time status of the site through internet 
(TCP/IP). It has been designed for use with TraceTek TTSIM-2 / 
TTSIM-1A 

/ TTSIM-1 

by using RS485 MODBUS communication.

All connected TTSIM-2 / TTSIM-1A

 / TTSIM-1

 data will be accessed

via  web  browser.

 

In  all  cases,  each  WIS  offers  the  following  list  of 

features and specification. 

90 mm 

(3.54”) 

57 mm 
(2.24”) 

35 mm 
(1.38”) 

Using two wires for RS485 MODBUS communication

 

TT

-

WIS

Product Information 

General Features 

Number of TTSIM

 Units

 Supported 

Weight 
Network Communication 
Visual Indicator 
Ethernet 
Ethernet Connector 
Built-in Clock 
Built-in Web Server 
Power Requirement 
Power Consumption 
Power Connection 
Mounting Method 

Reset to Factory Default 
Locate Point of Leakage 
Browser Support 

Language Support 

DHCP Support 
Static IP Address 
Real-time Status 
Email Alert 
Number of Email Contact 
History Log 
Max. History Log Record 
History Log Export 
History Log Export Format 
Login Protection 

At Least 

200 g 
Serial RS485, TCP/IP 
LED (Power, Serial RS485, Ethernet) 
10 Mbps 
RJ-45 
Yes 
Yes 
12Vdc ± 3V 
Max. 3W 
Wire Terminal 
Case Mount (TTSIM-BBC),  
DIN-Rail Mount, Wall Mount 
Support 
Support 
Internet Explorer 8, Firefox 4, 
Safari 5, Chrome 5 or above 
English, Simplified Chinese, 
Traditional Chinese 
Yes 
Yes 
Yes 
Yes (via External SMTP Server) 

Yes (with Time Stamp) 
64 
Yes 
XML, HTML 
Password Required 

Web Server 

Figure 1. Schematic Diagram of the TT-WIS

Reviews: