To use values from individual sensors in your control program
ZS Sensor
CARRIER CORPORATION ©2020
Applications Guide
All rights reserved
29
When using multiple ZS Sensors on a single Rnet, an ASVI microblock outputs the average, minimum, or
maximum value of the sensors. However, if you need to use the value of just one of the sensors, you can use an
Analog Network Input (ANI) microblock that addresses a specific ZS Sensor.
1
In the Snap application, select the Sensor Binder microblock and note the
Index
number for the sensor
whose value you want to use.
2
Verify that the sensor in enabled in the ASVI microblock.