6–15
T-366
External Checks:
Check for leaks with the following recommended checks. Re-pressurize the container to 2 inches water gauge and
look for leaks at the following areas using soapy water (mixture of dish detergent and water) looking for bubbles.
• Inspect evaporator unit access panels. Check gasket is properly in place. Tighten access panel bolts to 60
inch-lbs. and caulk if necessary.
• Inspect at condensate drain outlet line. If leaking, complete other checks and re-inspect internally.
• Inspect unit/container box joints. Caulk if necessary.
• Inspect the through-wire bulkhead connections. Secure and caulk if required.
• Inspect the container floor drains under container (if accessible). If leaking, complete external checks and
reinspect internally.
• Inspect the rear door seals. Ensure curtain is properly installed (curtain should be visible throughout the
perimeter of the doors). Remove an install new curtain. De-pressurize the container prior to opening the con-
tainer.
• Ensure manual fresh air panel is equipped with collars (Part # 79-04064-00).
Figure 6.22 Fresh Air Panel Collars
Internal Checks:
Remove pressure within the container and perform inspections at the following locations.
• Inspect curtain for any rips. Replace curtain
• Inspect the container floor drains. Ensure they are properly sealed. Standard drains can not be used.
• Inspect condensate drain outlet line. Confirm drain line is filled with water.
• Inspect for any internal wall damage. Repair and caulk as required
• Inspect floor to side wall joint, floor to front bulkhead joint for any damage. Repair and caulk as required
On completion of the checks and any associated repairs it is recommended that the unit be tested again to verify it
that it now meets the required level.
6.12 CONTAINER CURTAIN
WARNING
!
Potential hazardous atmosphere and low oxygen levels inside the container, ventilate before
entering. Stay away from doors while venting. Refer to
.
Collars
Fresh Air Panel
Summary of Contents for XtendFRESH
Page 2: ......
Page 4: ......
Page 8: ...T 366 iv LIST OF TABLES TABLE NUMBER Page Table 6 1 Maintenance Schedule 6 1...
Page 12: ......
Page 42: ...T 366 7 2 Figure 7 1 PIDs NT2570 and NT2617 Schematic and Diagram...
Page 43: ...7 3 T 366 Figure 7 2 PIDs NT2570 and NT2617 Schematic and Diagram Page 2...
Page 44: ...T 366 7 4 Figure 7 3 PIDs NT2570 and NT2617 Diagram and Legend...
Page 45: ...7 5 T 366 Figure 7 4 PIDs NT2619 and NT2704 Schematic and Wiring Diagram...
Page 46: ...T 366 7 6 Figure 7 5 PIDs NT2619 and NT2704 Schematic and Wiring Diagram Page 2...
Page 47: ...7 7 T 366 Figure 7 6 PIDs NT2619 and NT2704 Diagram and Legend...
Page 48: ...Figure 7 7 PIDs NT2709 and NT2774 Schematic and Wiring Diagram...
Page 49: ...7 9 T 366 Figure 7 8 PIDs NT2709 and NT2774 Schematic and Wiring Diagram Page 2...
Page 50: ...T 366 7 10 Figure 7 9 PIDs NT2709 and NT2774 Diagram and Legend...
Page 52: ...T 366 9 1 9 Parts List for XtendFRESH Sheet 1 of 2 6 7 9 12 2 8 10 15 3 5 1 10 11 4 5 14...
Page 68: ......
Page 71: ......