background image

PHD4 Series K and WPH4 Series K: Installation Instruction

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

22

reversed  to  correct  rotation.  When  turning  backwards,  the  difference

between compressor suction and discharge pressures may be near zero. 

Checking and Adjusting Refrigerant Charge

The refrigerant system is fully charged with R-410A refrigerant and is

tested and factory sealed

.

NOTE: 

Adjustment of the refrigerant charge is not required unless the

unit is suspected of not having the proper R-410A charge. 

NOTE: 

Some  units  have  fixed  orifice  refrigerant  metering  devices.

There  is  a  different  charging  procedure  for  both  expansion  devices.

Refer to the correct procedure for your unit. 
The charging label and  the tables  shown  refer to system  temperatures

and  pressures  in  cooling  mode  only.  A  refrigerant  charging  label  is

attached  to  the  inside  of  the  compressor  access  panel.  (See 

Fig. 23

Subcool  chart  for  units  with TXV  and  superheat  chart  for  units  with

fixed orifice.) The chart includes the required liquid line temperature at

given discharge line pressures and outdoor ambient temperatures.
A superheat chart is attached to the inside of the compressor access panel

for the unit with fixed metering device. Refer to the charging procedure

on the label.
An accurate thermocouple- or thermistor-type thermometer, and a gauge

manifold are required when using the subcooling charging method for

evaluating  the  unit  charge.  Do  not  use  mercury  or  small  dial-type

thermometers  because  they  are  not  adequate  for  this  type  of

measurement.

NOTE: 

Allow system to operate for a minimum of 15 minutes before

checking or adjusting refrigerant charge.

IMPORTANT: 

When  evaluating  the  refrigerant  charge,  an  indicated

adjustment to the specified factory charge must always be very minimal.

If  a  substantial  adjustment  is  indicated,  an  abnormal  condition  exists

somewhere  in  the  cooling  system,  such  as  insufficient  airflow  across

either coil or both coils.
Proceed as follows:

1. Remove caps from low- and high-pressure service fittings.
2. Using  hoses  with  valve  core  depressors,  attach  low-  and

high-pressure  gauge  hoses  to  low-  and  high-pressure  service

fittings, respectively.

3. Start unit and let run until system pressures stabilize.
4. Measure and record the following:

a. Outdoor ambient-air temperature (°F [°C] db).

b. Liquid line temperature (°F [°C]) at TXV.

c. Discharge (high-side) pressure (psig). 

d. Suction (low-side) pressure (psig) (for reference only).

5. Using  Cooling  Charging  Charts  compare  outdoor-air  temperature

(°F  [°C] db)  with the  discharge line  pressure  (psig)  to  determine

desired system operating liquid line temperature (See 

Fig. 23

.)

6. Compare  actual  liquid  line  temperature  with  desired  liquid  line

temperature. Using a tolerance of ±2°F (±1.1°C), add refrigerant if

actual  temperature  is  more  than  2°F  (1.1°C)  higher  than  proper

liquid line temperature, or remove refrigerant if actual temperature

is  more  than  2°F  (1.1°C)  lower  than  required  liquid  line

temperature.

NOTE: 

If the problem causing the inaccurate readings is a refrigerant

leak, refer to Check for Refrigerant Leaks section.

Indoor Airflow and Airflow Adjustments

NOTE: 

Be sure that all supply-and return-air grilles are open, free from

obstructions, and adjusted properly. 

This unit is factory-set up for use with a  single cooling fan  speed.  In

addition, this unit has the field-selectable capability to run two different

cooling  fan  speeds: The  rated  cooling  fan  speed  (350~400  CFM/Ton)

and an enhanced dehumidification fan speed (As low as 320 CFM/Ton)

for  use  with  either  a  dehumidistat  or  a  thermostat  that  supports

dehumidification.
 The cooling speed is marked “LOW” on the interface fan board (IFB)

(See 

Fig. 21

). The factory-shipped settings are noted in 

Table 4

. There

are  4  additional  speed  tap  wires  available  for  use  in  either  electric

heating or cooling (For color coding on the indoor fan motor leads, see

Table 3

). The additional 4 speed tap wires are shipped loose with vinyl

caps  and  are  located  in  the  control  box,  near  the  interface  fan  board

(IFB) (See 

Fig. 21

).

Single Cooling Fan Speed Set-up (Dehumidification 

feature not used)

To change cooling speed:

1. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding). Add the wet coil pressure drop in 

Table 6

to the system static to determine the correct cooling airflow speed

in 

Table 4

 that will deliver the nominal cooling airflow as listed in

Table 1

 for each size.

2. Remove the current speed tap wire from the “LOW” terminal on the

interface fan board (IFB) (See 

Fig. 21

) and place vinyl cap over the

connector on the wire.

3. Connect the desired speed tap wire to the “LOW” terminal on the

interface fan board (IFB).

NOTE: 

If accessory electric heat is installed, and the electric heat fan

speed is chosen to be the same as the normal cooling fan speed, the dry

airflow  must  meet  or  exceed  the  minimum  airflow  speed  specified  in

Table 2

 for the specific size unit.

Two Cooling Fan Speeds Set-up (Dehumidification 

feature used)

IMPORTANT: 

Dehumidification control must open control circuit on

humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of either a 24

VAC dehumidistat or a thermostat which includes control of a 24 VAC

dehumidistat  connection.  In  either  case,  the  dehumidification  control

WARNING

!

EXPLOSION HAZARD

Failure to follow this warning could result in

death,  serious  personal  injury,  and/or

property damage.

Never use air or gases containing oxygen for

leak  testing  or  operating  refrigerant

compressors.  Pressurized  mixtures  of  air  or

gases  containing  oxygen  can  lead  to  an

explosion.

WARNING

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage.

For cooling operation, the recommended airflow is 350 to 450 cfm for

each 12,000 Btuh of rated cooling capacity. For heating operation, the

airflow  must  produce  a  temperature  rise  that  falls  within  the  range

stamped on the unit rating plate.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before

changing blower speed.

Summary of Contents for WPH4 Series

Page 1: ...and Defrost Mode 24 Maintenance 27 Indoor Blower and Motor 27 Refrigerant 30 Compressor Oil 30 Servicing Systems on Roofs with Synthetic Materials 31 Liquid Line Filter Drier 31 R 410A Refrigerant Cha...

Page 2: ...on on older G series roof curbs Two accessory kits are available to aid in installing a new G series unit on an old G roof curb 1 Accessory kit number CPADCURB001A00 small chassis and accessory kit nu...

Page 3: ...partial overhang such as a normal house overhang is 48 in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict out...

Page 4: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A221484 Fig 2 PHD4 24 30 Unit D...

Page 5: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 5 A221486 Fig 3 WPH4 24 30 Unit D...

Page 6: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 A221485 Fig 4 PHD4 36 60 Unit D...

Page 7: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 7 A221487 Fig 5 WPH4 36 60 Unit D...

Page 8: ...4 Attach ductwork to curb flanges of duct rest on curb 5 Insulated panels 1 in 25 mm thick fiberglass 1 lb density UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm Part Number CPRCURB011B00...

Page 9: ...al use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Particular attention should be...

Page 10: ...ing Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to...

Page 11: ...n accessory or is field supplied Make sure that the outlet of the trap is at least 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tu...

Page 12: ...24 volt splice box See Fig 12 for connection diagram Run the low voltage leads from the thermostat through the control wiring inlet hole grommet see Fig 2 Fig 5 and into the low voltage splice box Pr...

Page 13: ...r Dual Accuraters Orifice ID in mm N A 0 080 1 2 03 1 N A Orifice OD in mm 0 032 2 0 81 2 0 035 2 0 89 2 0 040 2 1 02 2 0 046 2 1 17 2 0 046 2 1 17 2 0 046 2 1 17 2 Outdoor Coil Rows Fins in face area...

Page 14: ...ries K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 14 A09098 Fig 13 Typical Insta...

Page 15: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 15 A221468 Fig 14 Connection Wiring Schem...

Page 16: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 16 A221469 Fig 15 Ladder Wiring Schemat...

Page 17: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 17 A221470 Fig 16 Connection Wiring Schem...

Page 18: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 18 A221471 Fig 17 Ladder Wiring Schemat...

Page 19: ...nd WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A221472 Fig 18 Connection Wiring Di...

Page 20: ...and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A221473 Fig 19 Ladder Wiring Diag...

Page 21: ...temperature NOTE Once the compressor has started and then has stopped it should not be started again until 5 minutes have elapsed The defrost board has a built in 5 minute delay between cycles The 5 m...

Page 22: ...r than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments NO...

Page 23: ...able range for the speed tap to be used for dehumidification cooling 7 Use any spare vinyl plugs to cap any unused speed tap wires Single Speed Cooling With Higher Electric Heat Speed This unit can al...

Page 24: ...tive defrost cycles the control will lengthen the defrost interval by 15 minutes up to a maximum of 120 minutes or 30 minutes greater than the original setpoint whichever comes first If the previous d...

Page 25: ...0 41 0 41 High Black CFM 1505 1464 1423 1380 1336 1292 1242 1199 1145 1096 BHP 0 38 0 39 0 40 0 42 0 43 0 43 0 44 0 45 0 46 0 47 42 Low Blue CFM 956 899 843 786 729 676 621 558 504 435 BHP 0 13 0 13 0...

Page 26: ...4x24x1 406x610x25 356x610x25 3 0 3 5 4 0 0 09 0 09 0 10 0 12 0 13 0 15 0 17 0 17 0 19 0 21 1500 2200CFM 16x24x1 18x24x1 406x610x25 457x610x25 5 0 0 15 0 17 0 18 0 20 0 21 0 22 0 23 0 23 Table 8 Electr...

Page 27: ...slide assembly out Be careful not to tear insulation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscr...

Page 28: ...wet bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check...

Page 29: ...pect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 25 to locate all the electrical controls and wiring Check a...

Page 30: ...e interchanged The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves...

Page 31: ...polyethylene plastic drip cloth or tarp Cover an approximate 10x10 ft 3x3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent ru...

Page 32: ...ng vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil see Fig 27 The thermostat closes at 32_F...

Page 33: ...nt line voltage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace...

Page 34: ...LECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOU...

Reviews: