Table 7 — W7220 Menu Structure* 

 MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

NOTES

STATUS

ECONO AVAIL

NO

YES/NO

FIRST STAGE COOLING DEMAND (Y1–IN)

YES = economizing available; the system can use outside air for 

free cooling when required

ECONOMIZING

NO

YES/NO

FIRST STAGE COOLING RELAY OUTPUT

YES = outside air being used for 1 stage cooling

OCCUPIED

NO

YES/NO

OCCUPIED

YES = OCC signal received from space thermostat or unitary 

controller

YES = 24 Vac on terminal OCC

NO = 0 Vac on terminal OCC

HEAT PUMP

N/A**

COOL

HEAT

HEAT PUMP MODE

Displays COOL or HEAT when system is set to heat pump

(Non-conventional)

COOL Y1—IN

OFF

ON/OFF

FIRST STAGE COOLING DEMAND (Y1-IN)

Y1–I signal from space thermostat or unitary controller for cooling 

stage 1.

ON = 24 Vac on terminal Y1–I

OFF = 0 Vac on terminal Y1–I

COOL Y1—OUT

OFF

ON/OFF

FIRST STAGE COOLING RELAY OUTPUT

Cool stage 1 Relay Output to stage 1 mechanical cooling 

(Y1–OUT terminal)

COOL Y2—IN

OFF

ON/OFF

SECOND STAGE COOLING DEMAND (Y2–IN)

Y2–I signal from space thermostat our unitary controller for second 

stage cooling.

ON = 24 Vac on terminal Y2–I

OFF = 0 Vac on terminal Y2–I

COOL Y2—OUT

OFF

ON/OFF

SECOND STAGE COOLING RELAY OUTPUT

Cool Stage 2 Relay Output to mechanical cooling 

(Y2–OUT terminal)

MA TEMP

_ _ . _ F

0°F to 140°F

(–17°C to 60°C)

SUPPLY AIR TEMPERATURE, Cooling Mode

Displays value of measured mixed air from MAT sensor.

Displays _ _ . _ F if not connected, short or out-of-range.

DA TEMP

_ _ . _ F

0°F to 140°F

(–17°C to 60°C)

DISCHARGE AIR TEMPERATURE, after Heating section

Displays when Discharge Air sensor is connected and displays 

measured discharge temperature.

Displays _ _ . _F if sensor sends invalid value, if not connected, 

short or out-of-range.

OA TEMP

_ _ . _ F

–40°F to 140°F

(–40°C to 60°C)

OUTSIDE AIR TEMP

Displays measured value of outdoor air temperature.

Displays _ _ . _F if sensor sends invalid value, short or out-of-

range.

OA HUM

_ _ %

0 to 100%

OUTSIDE AIR RELATIVE HUMIDITY

Displays measured value of outdoor humidity from OA sensor.

Displays _ _% if not connected short, or out-of-range.

RA TEMP

_ _ . _ F

0°F to 140°F

(–17°C to 60°C)

RETURN AIR TEMPERATURE

Displays measured value of return air temperature from 

RAT sensor.

Displays _ _ . _ F if sensor sends invalid value, if not connected, 

short or out-of-range

RA HUM

_ _ %

0 to 100%

RETURN AIR RELATIVE HUMIDITY

Displays measured value of return air humidity from RA sensor.

Displays _ _% if sensor sends invalid value, if not connected, short 

or out-of-range

IN CO2

_ _ _ ppm

0 to 2000 ppm

SPACE/RETURN AIR CO

2

Displays value of measured CO

2

 from CO

2

 sensor. Invalid if not 

connected, short or out-of-range

DCV STATUS

N/A

ON/OFF

DEMAND CONTROLLED VENTILATION STATUS

Displays ON if above setpoint and OFF if below setpoint, and 

ONLY if a CO

2

 sensor is connected.

DAMPER OUT

2.0v

2.0 to 10.0v

Displays voltage output to the damper actuator.

ACT POS

N/A

0 to 100%

Displays actual position of outdoor air damper actuator

ACT COUNT

N/A

1 to 65535

Displays number of times actuator has cycled.

1 cycles equals 180 deg. of actuator movement in any direction.

ACTUATOR

N/A

OK/Alarm (on 

Alarm menu)

Displays ERROR if voltage or torque is below actuator range.

EXH1 OUT

OFF

ON/OFF

EXHAUST STAGE 1 RELAY OUTPUT

Output of EXH1 terminal:

ON = relay closed

OFF = relay open

EXH2 OUT

OFF

ON/OFF

EXHAUST STAGE 2 RELAY OUTPUT

Output of AUX terminal; displays only if AUX = EXH2

ERV

OFF

ON/OFF

ENERGY RECOVERY VENTILATOR

Output of AUX terminal; displays only if AUX = ERV

Summary of Contents for WeatherMaster 50GC 04-06 Series

Page 1: ...FAN OPERATION 2SP H C AND 3 SPEED FAN OPERATION CHECKOUT TROUBLESHOOTING RTU Open Controller Factory Option 35 SystemVu Controller Factory Option 35 Controller Options 35 LOW AMBIENT Smoke Detectors 3...

Page 2: ...uld cause personal injury death and or equipment damage R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on R 410A refr...

Page 3: ...installed W7212 EconoMi er IV Non Fault Detection and Diagnostic 2 RTU Open Multi Protocol Controller 3 SystemVu Controller 6 Electro mechanical can be used with W7220 EconoMi er X with Fault Detecti...

Page 4: ...4 Fig 2 50GC 04 06 Unit Dimensional Drawing...

Page 5: ...5 Fig 2 50GC 04 06 Unit Dimensional Drawing cont...

Page 6: ...6 Fig 2 50GC 04 06 Unit Dimensional Drawing cont...

Page 7: ...ions 9 Install other accessories PAD MOUNTED INSTALLATION 1 Prepare pad and unit supports 2 Check and tighten the bottom condensate drain connection plug 3 Rig and place unit 4 Convert unit to side du...

Page 8: ...ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRAFTER CHECKER D 48TC400427 B WEIGHT MMC 06 17 11 SHEET 5 OF 5 SURFACE FINISH MFG PURCH MODEL INTERNAL USE ONLY...

Page 9: ...using unit frame as a refer ence See Table 2 on page 7 and Fig 5 for additional information Lifting holes are provided in base rails as shown in Fig 5 Refer to rigging instructions on unit Rigging mat...

Page 10: ...weatherproof all external ductwork joints and roof or build ing openings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibility to the unit s informati...

Page 11: ...Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be used as the top of the hood Remove the screws along the sides and bottom of the indoor coil a...

Page 12: ...owered convenience outlet the power source leads to the convenience outlet s transformer primary are not factory connected Installer must connect these leads accord ing to required operation of the co...

Page 13: ...ndle Fig 18 Power Wiring Connections Field Install the NFD Shaft and Handle 1 Remove the Control Box access panel The NFD enclosure is located below the Control Box see Fig 19 2 Remove 3 cap head scre...

Page 14: ...sition See Fig 22 6 Tighten the locking screw to secure the shaft to the HACR 7 Turn the handle to the OFF position with red arrow pointing at OFF 8 Install the handle on to the painted cover horizont...

Page 15: ...over Aweatherproof while in use cover for the factory installed conve nience outlets is now required by UL standards This cover cannot be factory mounted due its depth it must be installed at unit ins...

Page 16: ...zation is con firmed Observe National Electrical CodeArticle 210 Branch Cir cuits for use of convenience outlets Fuse On Power Type The factory fuse is a Bussman1 Fusetron T 15 non renewable screw in...

Page 17: ...rminals during operation must be within voltage range indicated on unit nameplate On 3 phase units volt ages between phases must be balanced within 2 and the current within 10 Use the formula shown in...

Page 18: ...terminal strip on the upper left corner of the Unit Control Board See Fig 32 NOTE If thru the bottom connections accessory is used refer to the accessory installation instructions for information on r...

Page 19: ...e heater module VIO and BRN two of each if a two circuit heater module is installed identify for circuit 1 to the 4 pole terminal board TB4 located on the heater bulkhead to the left of the Heater mod...

Page 20: ...ee Fig 40 Fig 40 Humidistat Connections to UCB Connecting the Thermidistat device 33CS2PPRH 01 1 Route the Thermidistat multi conductor thermostat cable field supplied through the hole provided in the...

Page 21: ...it with Humidi MiZer Adaptive Dehumidification System and Edge Pro Thermidistat Device Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg C HUM G W2 W1 Y2 Y1 R PROGRAMMABLE THERMOSTAT UNIT CONTROL...

Page 22: ...22 Fig 42 Typical 50GC 04 06 Control Wiring Diagram 208 230V W7220 Control Unit Shown...

Page 23: ...23 Fig 43 Typical 50GC 04 06 Power Wiring Diagram 208 230V Unit Shown...

Page 24: ...ce Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keypad Electrical Rated Voltage 20 to 30 V...

Page 25: ...Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output C...

Page 26: ...t a menu s item and return to the list of menus Fig 48 W7220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Ad vanced Settings Checkout tests and Alarms 1 Navig...

Page 27: ...the and arrow buttons to move forward and back ward through the menus and press the button to select and confirm setup item changes TIME OUT AND SCREENSAVER When no buttons have been pressed for 10 m...

Page 28: ...re Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature D...

Page 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Page 30: ...If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode See Menu Note 4 In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump...

Page 31: ...o adjust for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay f...

Page 32: ...A OUTSIDE AIR TEMPERATURE SENSOR ERROR Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A ACTUATOR ERROR Actuator has f...

Page 33: ...dary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high lim it boundary for differential enthalpy The high limit boundary...

Page 34: ...delay time specified N A Not applicable Table 9 Fan Speed STATE FAN SPEED OCC Low Y1 Low Y2 High W High Table 10 Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV O...

Page 35: ...Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired...

Page 36: ...e sure that the elbow fitting is pointing down See Fig 51 Step 2 3 Screw the sensor and detector plate into its operating position using screws from Step 1 See Fig 51 Step 3 4 Connect the flexible tub...

Page 37: ...oc cupied sequence at terminals marked OCCUPANCY Detach the jumper covering the Occupancy terminals on the UCB and then attach the required connections Step 13 Install Accessories Available accessorie...

Page 38: ...for the base unit Then add Vdc for any accessories installed per the Field Accessories section of the label NOTE The fan speed set up labels are located on the High Volt age cover in the Control Box...

Page 39: ...he following determin ing the values per the RPM Calculator label see Fig 55 Use the UP and DOWN arrow keys and the BACK key to set the values Press ENTER after setting each value to continue to the n...

Page 40: ...75 66 80 107 0 4 1477 1544 1615 1688 1764 1842 1921 2003 2068 66 0 6 1639 1699 1763 1828 1897 1967 2040 2115 2191 0 8 1788 1843 1902 1962 2025 2090 2157 2227 2298 66 1 0 1925 1976 2031 2087 2146 2208...

Page 41: ......

Page 42: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500269 01 Printed in U S A Form 50GC 4 6 03SI Pg 42 12 19A 12 19 Replaces 50...

Page 43: ...ns Y N _____ Verify that all electrical connections and terminals are tight Y N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y...

Page 44: ...______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N _____ F Check for correct ramp up of outdoor fan motor as condenser...

Reviews: