![Carrier Weathermaster 48P2030-100 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 42](http://html.mh-extra.com/html/carrier/weathermaster-48p2030-100/weathermaster-48p2030-100_controls-start-up-operation-service-and-troubleshooting_2560338042.webp)
42
SYSTEM MODES (
OPERATING MODES
SYS.M
)
System Mode Off
When the system mode is OFF, all outputs are to be shut down
and no machine control is possible. The following list displays
the text assigned to the System Mode when in the OFF mode
and the conditions that may cause this mode are checked in the
following hierarchal order:
1. Wake up timer on a power reset.
(“Initializing System ...”)
2. System in the process of shutting down compressors and
waiting for timeguards to expire.
3. (“Shutting Down ...”)
4. Factory shut down (internal factory control level —
SHUTDOWN).
(“Factory Shut Down”)
5. Unit Stop (software application level variable that acts as a
hard shut down —
Service Test
STOP
).
(“Local Machine Stop”)
6. Fire Shut Down (fire shutdown condition based on the Fire
Shutdown Input (
Inputs
FIRE
FSD
).
(“Fire-Shutdown Mode”)
7. Emergency Stop, which is forced over the CCN through
the Emergency Stop Variable (EMSTOP).
(“CCN Emergency Stop”)
8. Start-up Delay.
(“Startup Delay = 0-900 secs”)
9. Service test ending transition timer.
(“Service Test Ending”)
10. Unexplained internal software failure.
(“Internal Failure”)
System Mode Test
When the system mode is Test, the control is limited to the Test
mode and is controllable via the local displays (scrolling mar-
quee and Navigator™ display). The System Test modes are Fac-
tory Test Enabled and Service Test Enabled. See the Service Test
section on page 36 for details on test control in this mode.
1. Factory Test mode (“Factory test enabled”)
2. Service Test mode (“Service test enabled”)
System Mode Run
When the system mode is Run, the software application in the
control is free to run the HVAC control routines by which cool-
ing, heating, IAQ, etc., is possible. There are two possible text
displays for this mode: one is normal run mode and the other
occurs if one of the following fire-smoke modes is present:
smoke purge, pressurization or evacuation.
1. Normal run time state (“Unit Operation Enabled”)
2. Fire-Smoke control mode (“Fire-Smoke Control”)
HVAC MODES
(
OPERATING MODE
HVAC
)
The HVAC mode is dependent on the system mode to allow it
to further determine the operational state of the rooftop unit.
The actual determination of an HVAC mode is based on a hier-
archal decision making process whereby certain overrides may
interfere with normal temperature/humidity control. The deci-
sion making process that determines the HVAC mode is shown
in Fig. 4 and Appendix E.
Each HVAC mode is described below. The HVAC mode num-
ber is shown in the parentheses after the mode.
HVAC Mode — STARTING UP (0)
The unit is transitioning from the OFF mode to a different mode.
HVAC Mode — DISABLED (1)
The unit is shut down due to a software disable command
through the scrolling marquee, a CCN emergency stop com-
mand, a service test end, or a control-type change delay.
HVAC Mode — SHUTTING DOWN (2)
The unit is transitioning from a mode to the OFF mode.
HVAC Mode — SOFTSTOP REQUEST (3)
The unit is off due to a soft stop request from the control.
HVAC Mode — REM SW.DISABLE (4)
The unit is off due to the remote switch.
HVAC Mode — FAN STATUS FAIL (5)
The unit is off due to a supply fan status failure.
HVAC Mode — STATIC PRESSURE FAIL (6)
The unit is off due to failure of the static pressure sensor.
HVAC Mode — COMP.STUCK ON (7)
The unit is shut down because there is an indication that a com-
pressor is running even though it has been commanded off.
HVAC Mode — OFF (8)
The unit is off and no operating modes are active.
HVAC Mode — TEST (9)
The unit is in the self test mode which is entered through the
Service Test menu.
HVAC Mode — TEMPERING VENT (10)
The economizer is at minimum vent position but the supply-air
temperature has dropped below the tempering vent set point.
Staged gas heat, modulating gas heat, SCR electric heat, or hy-
dronic heat is used to temper the ventilation air.
HVAC Mode — TEMPERING LOCOOL (11)
The economizer is at minimum vent position but the combina-
tion of the outside-air temperature and the economizer position
has dropped the supply-air temperature below the tempering
cool set point. Staged gas heat, modulating gas heat, SCR elec-
tric heat, or hydronic heat is used to temper the ventilation air.
HVAC Mode — TEMPERING HICOOL (12)
The economizer is at minimum vent position but the combina-
tion of the outside-air temperature and the economizer position
has dropped the supply-air temperature below the tempering
cool set point. Staged gas heat, modulating gas heat, SCR elec-
tric heat, or hydronic heat is used to temper the ventilation air.
HVAC Mode — VENT (13)
This is a normal operation mode where no heating or cooling is
required and outside air is being delivered to the space to con-
trol IAQ levels.
HVAC Mode — LOW COOL (14)
This is a normal cooling mode where a low cooling demand is
present.
HVAC Mode — HIGH COOL (15)
This is a normal cooling mode where a high cooling demand is
present.
HVAC Mode — LOW HEAT (16)
The unit will be in low heating demand mode using gas, elec-
tric, or hydronic heat.
HVAC Mode — HIGH HEAT (17)
The unit will be in high heating demand mode using gas, elec-
tric, or hydronic heat.
HVAC Mode — UNOCC. FREE COOL (18)
In this mode the unit will operate in cooling but will be using the
economizer for free cooling. Entering this mode will depend on
the status of the outside air. The unit can be configured for outside
air dry bulb changeover, differential dry bulb changeover, outside
air enthalpy changeover, differential enthalpy changeover, or a
custom arrangement of enthalpy/dew point and dry bulb. See the
Economizer section on page 72 for further details.
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...