![Carrier WeatherMaker 48A020 Installation Instructions Manual Download Page 9](http://html.mh-extra.com/html/carrier/weathermaker-48a020/weathermaker-48a020_installation-instructions-manual_2560233009.webp)
9
Base Unit Dimensions — 48A2,A3,A6,A7040-050
Fig. 6 — Base Unit Dimensions — 48A2,A3,A6,A7040-050
A48-8689
A48-8689
NOTES:
1.
Weights include economizer.
2.
center of gravity.
3.
Unit clearances:
Top of units: no overhang
Condenser coil: 4’ - 0” [1219]
Economizer side: 6’ - 0” [1829]
Heat side: 4’ - 0” [1219]
Filter access side: 10’ - 0” [3048] (for
removal of evaporator coil)
4.
Bottom ducts are designed to be attached to
accessory roof curb. If unit is mounted on
dunnage, it is recommended that the ducts
be supported by cross braces as done on
accessory roof curb.
5.
Dimensions in [ ] are in millimeters. All other
dimensions are in inches.
*Operating weight includes largest indoor fan motor, micro-
channel heat exchanger, modulating power exhaust (vari-
able air volume units), and variable frequency drive
(variable air volume units).