77
Table 23 —
VFD Unit Parameters - 50LC Size 26
MOTOR
OPTION VOLTAGE
MOTOR
P/N
VFD
CARRIER
P/N
VFD MFR
P/N
REGIONAL
SETTINGS
GRID
TYPE
MOTOR
POWER
MOTOR
VOLTAGE
MOTOR
FREQUENCY
(Hz)
MOTOR
CURRENT
(MUST-HOLD
AMPS)
MOTOR
NOMINAL
SPEED
(RPM)
0-03
0-06
1-20
1-22
1-29
1-24
1-25
STD
208/230V HD60FK657 HK30WA373
131L9798
[1]
[102]
[14]
230
60
21.2
1760
460V
HD60FK657 HK30WA380
131L9867
[122]
[14]
460
9.7
1760
575V
HD60FL576 HK30WA384
131N0229
[132]
[14]
575
7.2
1745
MID
208/230V HD62FK654 HK30WA374
131L9799
[102]
[15]
230
28.0
1760
460V
HD62FK654 HK30WA381
131L9868
[122]
[15]
460
13.7
1760
575V
HD62FL576 HK30WA384
131N0229
[132]
[15]
575
8.9
1750
HIGH
208/230V HD64FK654 HK30WA375
131L9800
[102]
[16]
230
37.3
1755
460V
HD64FK654 HK30WA386
131L9869
[122]
[16]
460
16.9
1755
575V
HD64FL576 HK30WA388
131N0233
[132]
[16]
575
12.6
1755
MOTOR
OPTION
VOLTAGE
START
DELAY
(sec)
FLYING
START
MIN SPEED
FOR
FUNCTION
(Hz)
MOTOR
THERMAL
PROTECTION
PRESET REFERENCE
1-71
1-73
1-82
1-90
3-10 [0]
3-10 [1]
3-10 [2]
3-10 [3]
3-10 [4]
3-10 [5]
3-10 [6]
3-10 [7]
STD
208/230V
2.0
[1]
1.0
[4]
0%
60.00%
72.00%
100%
100%
0%
0%
0%
460V
575V
MID
208/230V
460V
575V
HIGH
208/230V
460V
575V
MOTOR
OPTION
VOLTAGE
RAMP UP
TIME (sec)
RAMP DOWN
TIME (sec)
CURRENT
LIMIT
TERMINAL 18
DIGITAL
INPUT
TERMINAL 19
DIGITAL
INPUT
TERMINAL 27
DIGITAL
INPUT
TERMINAL 29
DIGITAL
INPUT
3-41
3-42
4-18
5-10
5-11
5-12
5-13
STD
208/230V
10.00
10.00
100%
[8}
[16]
[17]
[18]
460V
575V
MID
208/230V
460V
575V
HIGH
208/230V
460V
575V
MOTOR
OPTION
VOLTAGE
TERMINAL 53
LOW
VOLTAGE
TERMINAL 53
HIGH
VOLTAGE
TERMINAL 53
LOW
REFERENCE
TERMINAL 53
HIGH
REFERENCE
RESET
MODE
AUTO.
RESTART
TIME (s)
RFI FILTER
6-10
6-11
6-14
6-15
14-20
14-21
14-50
STD
208/230V
2
[10]
0
[60]
[3]
600
[0]
460V
575V
MID
208/230V
460V
575V
HIGH
208/230V
460V
575V
Summary of Contents for WeatherExpert 50LC14
Page 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Page 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Page 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Page 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Page 8: ...8 Fig 6 50LC Bottom View Size 14...
Page 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Page 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Page 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Page 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Page 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Page 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Page 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Page 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Page 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Page 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Page 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Page 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Page 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Page 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Page 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Page 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Page 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Page 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Page 80: ......
Page 81: ......