Appendix D: BACnet points list
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
95
BACnet
Point Name
Point
Access
Units
Default Value BACnet Point Name
BACnet Object ID
Cool Min Damper Position
R
%
cl_min_dmp_pos
Cool Max Damper Position
R
%
cl_max_dmp_pos
Single Duct Reheat Damper Position R
%
re_ht_min_dmp_pos
Heat Min Damper Position
R
%
ht_min_dmp_pos
Heat Max Damper Position
R
%
ht_max_dmp_pos
Ventilation Position
R
%
vent_dmp_pos
Occupied Cooling Setpoint
R/W
°F
75
occ_cl_stpt
AV:3001
Occupied Heating Setpoint
R/W
°F
70
occ_ht_stpt
AV:3002
Unoccupied Cooling Setpoint
R/W
°F
90
unocc_cl_stpt
AV:3003
Unoccupied Heating Setpoint
R/W
°F
60
unocc_ht_stpt
AV:3004
Occupancy Contact State
R
0=Open
1=Closed
occ_switch
BI:1001
Air Source Outdoor Air Temp
R
°F
link_ahu_oat
AV:2609
Air Source Static Pressure
R
in H2O
link_ahu_static
AV:2610
Air Source Supply Air Temp
R
°F
link_sat
AV:2608
Baseboard Heating Capacity
R
%
bas_bd_ht_cap
AV:2031
Cooling Demand Level
R
cool_demand_level
AV:9006
Damper Position
R
%
dpr_pos
AV:1013
Effective Cool Setpoint
R
°F
eff_cl_stpt
AV:3005
Effective Heat Setpoint
R
°F
eff_ht_stpt
AV:3006
Fan Off Delay
R/W
sec
120
fan_delay_off
AV:9024
Filter Runtime
R
hr
filter_rntm
AV:2015
Filter Service Alarm Timer
R/W
hr
0
filter_service_hrs
AV:2019
Heating Capacity
R
%
htg_cap
AV:2030
Heating Demand Level
R
heat_demand_level
AV:9036
Heating Lockout Temperature
R/W
°F
70
oat_ht_lockout
AV:9003
Indoor Air Quality CO2 (ppm)
R
ppm
iaq
AV:1009
lux sensor BACnet accessible
R
lux_bn
Min Setpoint Separation
R/W
°^F
4
min_stpt_sep
Occ Override Delay
R/W
min
15
occ_ovr_delay
AV:9028
Occupied Alarm Hysteresis
R/W
°^F
5
occ_spt_alrm_hyst
Occupied RH Control Setpoint
R/W
%rh
65
occ_dehum_stpt
AV:3011
Outdoor Air Temperature
R
°F
oa_temp
AV:1003
Override Time Remaining
R
min
ovrde_time
AV:2016
Power Fail Restart Delay
R/W
sec
60
start_delay
AV:9007
Setpoint Adjustment
R
°F
stpt_adj
AV:1006
Setpoint Adjustment Range
R/W
°^F
2
stpt_adj_range
AV:9015
Space Relative Humidity
R
%rh
space_rh
AV:1011
Space Temperature - Prime Variable R
°F
space_temp
AV:2007
Standby Offset
R/W
°F
0
stdby_offset
AV:1017
Supply Air Temperature
R
°F
sa_temp
AV:1008
System Outdoor Air Temperature
R/W
°F
-999
system_oat
AV:1901
System Setpoint Adjustment
R/W
°F
-999
system_stpt_adj
AV:1913
System Space AQ
R/W
ppm
-999
system_iaq
AV:1903
System Space RH
R/W
%
-999
system_rh
AV:1904
Appendix D: BACnet points list