To adjust the driver properties
VVT Bypass II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
33
Specific Events
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following
BACnet alarms:
Specific alarms:
•
Flow Control Alarm
•
Reheat Valve Alarm (future use)
NOTES
•
To set up alarm actions for controller generated alarms, see See
Alarms
in i-Vu® Help.
•
Reheat Valve Alarms are for future use.
Module Generated Alarm
Description
Short message shown on the i-Vu®
Alarms
page or in an alarm action when this
type of alarm is generated.
Events
Alarm Category and Alarm
Template
See
Alarms
in i-Vu® Help.
Enable
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from this controller.
Notification Class
Do not change this field.
Switches, Jumpers, Options
The
Switches, Jumpers, Options
page shows the current physical settings on the VVT Bypass II.
Flow Calibration Archive
The
Flow Calibration Archive
page shows measured flow and sensor readings that were entered in the i-Vu®
Test and Balance tool.