To set up the controller through the Service port
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
49
Device tab
BACnet Object
Device Instance
Autogenerated
—
(Default) The Device Instance is automatically set to a number
using the IP Address, Subnet information, and the Carrier vendor ID 16.
Assigned
—
Lets you enter a specific number that is unique on the BACnet network.
Device Name
Autogenerated
—
(Default) The Device Name is automatically set as the word
the Device Instance. For example, device2423911.
Assigned
—
Lets you enter a specific name that is unique on the BACnet network.
Device Location
You can enter an intuitive location for the device in the i-Vu® interface.
Device Description
You can enter an intuitive description for the device in the i-Vu® interface.
Configuration
APDU Timeout
How many milliseconds the device will wait before resending a message if no
response is received.
APDU Segment Timeout
How many milliseconds the device will wait before resending a message segment
if no response is received.
APDU Retries
The number of times the device will resend a message.
Controller Information
Clear Counts/Logs
Clears Reset counters and the three message history fields from the Module
Status.
Data Backup and Restore
Backup
Displays time of the last backup. Click button to backup the controller's control
programs, properties, and schedules.
Restore
Displays time of the last restore. Click button to restore the most recent backup of
the controller's control programs, properties, and schedules.