Wiring inputs and outputs

 

 

 

 
 

TruVu™ UCXP683T

-V 

 

CARRIER CORPORATION ©2021   

Installation and Start-up Guide 

 

All rights reserved 

 

21 

 

  

 

Inputs 

The TV-UCXP683T-V has inputs that accept the following signal types. 
  

Signal Type  

Description 

Thermistor 

1

 

Precon Type 2 (10kOhm at 77 °F) 

Input voltages should be from 0.2 Vdc to 4.0 Vdc for thermistors 

Dry contact 

The maximum current when the contact is closed is 0.5 mA. The input voltage should be 4.1 

V when the contact is open. Maximum closed contact resistance is 1kOhms. 

0

5 Vdc 

0

10 Vdc 

The input impedance of the TV-UCXP683T-V is approximately 120 kOhm when configured as 

a voltage input. 

Pulse counter 

2

 

Pulse counting up to 10 pulses per second.  

Minimum pulse width (on or off time) required for each pulse is 50 msec. 

1   

To use a thermistor not listed above, you can set up a custom translation table for your sensor in the controller's 

driver. 

2

  The TV-UCXP683T-V can perform pulse counting for dry contact or voltage inputs if you assign the input to a 

Pulse to Analog Input microblock. See 

To adjust input and output properties

 (page 28)

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring inputs and outputs 

Summary of Contents for TruVu UCXP683T-V

Page 1: ...T Tr ru uV Vu u U UC CX XP P6 68 83 3T T V V I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e Carrier 2021 Catalog No 11 808 850 01 12 3 2021...

Page 2: ...version of this document from www hvacpartners com the Carrier Partner Community website or your local Carrier office Important changes are listed in Document revision history at the end of this docu...

Page 3: ...ice 17 Wiring devices to the TV UCXP683T V s Rnet port 18 Wiring devices to the TV UCXP683T V s Act Net port 19 Wiring inputs and outputs 21 Inputs 21 Outputs 22 Wiring specifications 23 To wire input...

Page 4: ...Access connection in the i Vu interface 57 Troubleshooting 58 LEDs 58 To configure custom Prog LED 61 To get a Module Status report 61 Troubleshooting inputs and outputs 62 To get a Device Log 63 To...

Page 5: ...twork statistics that can be viewed numerically or as trend graphs Has built in airflow sensors Supports BACnet MS TP Supports Rnet devices Supports Act Net devices Works with the i Vu v7 0 or later s...

Page 6: ...lowing ports Rnet port for connecting ZS sensors an Equipment Touch an TruVu ET Display and Wireless Adapter for wireless sensors Service USB port for connecting locally to controller setup pages the...

Page 7: ...ations exceeding the listed operating ranges may reduce the power supplied by the Rnet port NOTE If the total power required by the sensors on the Rnet exceeds the power supplied by the Rnet port use...

Page 8: ...ccurate to 3 of sensor reading at 2 in H2O Controller microprocessor 32 bit ARM Cortex A8 600MHz processor with multi level cache memory Memory 4 GBs eMMC Flash memory and 256 MB DDR3 DRAM 2 MB availa...

Page 9: ...7 78 in 19 77 cm 5 88 in 14 94 cm 2 00 in 5 09 cm Screw mounting dimensions C D 5 3 in 13 45 cm 4 50 in 11 43 cm Air flow sensors E F G 49 in 1 26 cm 1 96 in 4 98 cm 41 in 1 05 cm Weight 1 2 lbs 0 54...

Page 10: ...quipment Touch or TruVu ET Display to the TV UCXP683T V s Rnet port to view or change the controller s property values schedule equipment view trends and alarms and more without having to access the s...

Page 11: ...il until you hear it click and the spring loaded latch secures the controller to the DIN rail Screw Mount Leave about 2 in 5 cm on each side of the controller for wiring Pull the mounting tabs until t...

Page 12: ...screw terminal connector from the controller s power terminals labeled 24V 3 Connect the power supply s wires to the red screw terminal connector 4 Connect an 18 AWG or larger wire from the power supp...

Page 13: ...TV UCXP683T V to a computer using the Carrier wireless service adapter 1 Insert the Carrier wireless service adapter part USB W into the controller s USB Service Port to communicate with a Wi Fi comp...

Page 14: ...hown below 2 A new Ethernet connection will appear on your computer 3 If your computer uses a static IP address use the following settings for the new connection Address 169 254 1 x where x is 2 to 7...

Page 15: ...ce located on the other side of an IP router Be connected to any third party IP devices NOTE Carefully plan your addressing scheme to avoid duplicating addresses If third party devices are integrated...

Page 16: ...ays intact during power cycles MS TP For MS TP on Port S1 set up autobaud or the baud rate On the controller setup pages BACnet tab Port S1 In the i Vu interface on the navigation tree right click you...

Page 17: ...the Clear All button to erase the Local Devices table if there is information in it 6 Click Discover The table finds and lists the first 256 unconfigured devices on the same subnet The table is sorted...

Page 18: ...r the identified controller enter the Address and Location optional 7 Repeat steps 3 and 4 for each controller that you want to address 8 For more details about discovering and configuring your device...

Page 19: ...r 100 Mbps Port S1 1 BACnet MSTP Modbus Serial RS485 9 6 to 115 2 kbps I O Bus To attach expanders in the future Service Port 2 USB 2 0 USB Comm Port future use USB 2 0 USB Rnet Port See Wiring device...

Page 20: ...sy chain configuration Cat5e or higher Ethernet cable 164 feet 50 meters MS TP 22 AWG low capacitance twisted stranded shielded copper wire 2000 feet 610 meters See the MS TP Networking and Wiring Tec...

Page 21: ...dcast Management Devices BBMDs in SiteBuilder or i Vu Help To wire to a BACnet MS TP network An MS TP network can be wired to Port S1 1 Turn off the TV UCXP683T V s power 2 Check the communications wi...

Page 22: ...Rnet port in a daisy chain configuration ZS sensors Wireless Adapter that communicates with wireless sensors Equipment Touch TruVu ET Display See the device s Installation and Start up Guide for comp...

Page 23: ...available for Act Net devices AC supply 25 VA 1 A DC supply 15W 0 625A Use an external transformer if your devices exceed the maximum power CAUTIONS If the power source for the Act Net devices require...

Page 24: ...wire the Act Net port terminals on the controller to the matching terminal on the supported device They may not be in the same order See example below The TV UCXP683T V supports Act Net communication...

Page 25: ...act is open Maximum closed contact resistance is 1kOhms 0 5 Vdc 0 10 Vdc The input impedance of the TV UCXP683T V is approximately 120 kOhm when configured as a voltage input Pulse counter 2 Pulse cou...

Page 26: ...y can switch up to 3 75 A 30 Vac Vdc The total power and current that can be switched by a bank of 3 relays cannot exceed the Class 2 limits of 100 VA or 4 2 A Universal output The TV UCXP683T V s uni...

Page 27: ...305 meters 26 AWG Shielded Pulse counter TLO 1000 feet 305 meters 22 AWG Shielded Output wiring To size output wiring consider the following Total loop distance from the controller to the controlled d...

Page 28: ...tart up Guide All rights reserved 24 To wire inputs and outputs WARNING Do not apply line voltage mains voltage to the controller s ports and terminals The Gnd terminal is shared by the inputs outputs...

Page 29: ...TV UCXP683T V s power and communications connections work properly 2 Turn off the TV UCXP683T V s power 3 Connect the input wiring to the screw terminals on the TV UCXP683T V NOTE Connect the shield w...

Page 30: ...S The universal output is set to Binary in the factory To avoid damage to the controller use a voltmeter to verify there is no voltage on the UO 01 and Common terminals before setting the DIP switch t...

Page 31: ...and Start up Guide All rights reserved 27 7 Turn on the TV UCXP683T V s power See Troubleshooting inputs and outputs page 62 NOTE You can install connector covers sold separately part PLM KIT by snapp...

Page 32: ...S type 1 in the Num field for Pump S S NOTES Exp expander number is 00 for the inputs and outputs located on the TV UCXP683T V Do not assign the same output number to more than one point 4 Enter the a...

Page 33: ...Vdc 0 10 Volt Linear w Offset 2 10 Volts Engineering values associated with 2 Vdc Min and 10 Vdc Max 1 Thermistor Thermistor Select your Thermistor type or set up and select a Non Linear Custom Table...

Page 34: ...ax No Translation N A The Analog Output microblock will output the same value that comes in to the microblock 2 10 Vdc Electrical 0 10 Volt Linear w Offset 2 10 Volts Engineering values associated wit...

Page 35: ...puts differently To set these values appropriately you should understand how the driver uses them Offset Polarity Notes Analog Input BAI Offset value positive or negative adds a fine adjustment to a s...

Page 36: ...w sensors NOTE Tubing should be at least 2 ft 61 meters long for stable airflow measurement The combined high and low tubing length should not exceed 16 4 ft 5 meters in order to ensure accurate measu...

Page 37: ...rd In a dual duct system 1 In the Snap application set the Airflow Microblock Properties Editor Hardware Configuration Primary Use to Cooling 2 Save your control program 3 In the i Vu interface on the...

Page 38: ...routers are found select one or more routers in the list on the Manage tab and click Upload All Content to upload to the i Vu application Use Ctrl click Shift click or both to select multiple items 4...

Page 39: ...id Time Synch Sensitivity seconds When the controller receives a time sync request if the difference between the controller s time and the time sync s time is greater than this field s value the contr...

Page 40: ...Also if the object s value updates excessively for 30 seconds an alarm is sent to the i Vu application listing all objects that are updating excessively A Return to normal alarm is sent only after al...

Page 41: ...ler clock s time and date Configuration BACnet System Status The current state of the controller Operational Download in Progress Download Required Backup in Progress Non Operational The following fie...

Page 42: ...the i Vu interface on the Alarm Enable Disable tab change the acknowledgment settings for an alarm source or an alarm category Recipient List Recipients The first row in this list is from the i Vu app...

Page 43: ...ked I O Program Stopped Excessive COV All Programs Stopped Controller Generated Alarm Description Short message shown on the i Vu Alarms page or in an alarm action when this type of alarm is generated...

Page 44: ...See Alarms in i Vu Help Enable Clear these checkboxes to disable Alarm or Return to normal messages of this type from this controller Notification Class Do not change this field Custom Translation Ta...

Page 45: ...displays the state of the End of Net termination switch for Port S1 IP Configuration Allow setup of IP addressing through an external tool When this field is enabled you can set up IP addressing throu...

Page 46: ...the Network Activity tab Eth0 Eth1 Port Statistics BACnet IP Statistics BACnet IP Rx Unicast Packets BACnet IP packets received from a single BACnet device BACnet IP Tx Unicast Packets BACnet IP pack...

Page 47: ...pture file The capture will automatically resume Click on the Start Stop option to end the Continuous capture If the port is set up for MS TP select an option in the Capture section To download the ca...

Page 48: ...Act Net device This number is printed on a label on the device Device Status Displays the current status of the device Possible statuses Description Normal Operation Successful communication No Commu...

Page 49: ...e table click Accept after every change Unknown Error Firmware or bus error Auto addressed device When a device that does not have an address is found on the bus an unused address in automatically ass...

Page 50: ...Special Modbus Serial Modbus TCP IP and Modbus Error Definitions pages If the controller will be used with Modbus devices see the Modbus Integration Guide for information on using these pages Flow Ca...

Page 51: ...d of time you define in the time and date fields Enable Trend Historian Archives trend data to the system database Store Trends Now Writes all trend data in the controller to the system database witho...

Page 52: ...communicate through a BACnet Service port network page 48 To access the controller setup pages and use the Local Network tab you must first connect to and manually address one TV UCXP683T V For instr...

Page 53: ...ion for the device in the i Vu interface Device Description You can enter an intuitive description for the device in the i Vu interface Configuration APDU Timeout How many milliseconds the device will...

Page 54: ...S1 Configuration BACnet tab NOTE The TV UCXP683T V can be configured for only one BACnet communication type On the BACnet tab you can choose to run BACnet Over IP or BACnet Over Ethernet on the Eth0 a...

Page 55: ...V controller or by using the i Vu application In the i Vu navigation tree right click the TV UCXP683T V select Driver Properties and go to Driver Settings tab Local Network Configuration Check Allow...

Page 56: ...de To change the Mode 1 Select the devices you want to change 2 Select one of the following IP addressing modes Default IP Devices with rotary switches that are used when autogenerating the address if...

Page 57: ...ssing the DSC button immediately adds it to the table and displays a blue dot TIP You can build a table of devices in the order that you ve pressed the DSC buttons Clear the table and then press each...

Page 58: ...available you will have to assign a network number and enter it 5 Click Apply 6 On the right of the page in the Networks using selected connection table click the checkbox next to the network you want...

Page 59: ...elected connection table click the checkbox next to the network you want to connect to 15 Click Apply 16 Select the BACnet IP Service Port Connection and click Start The status changes to Connected 17...

Page 60: ...rence between the controller s ground and the computer s AC power ground could damage the USB Link and the controller If you are not sure of the wiring polarity use a USB isolator between the computer...

Page 61: ...tart Control Panel System Device Manager Ports Com LPT The COM port number is beside Silicon Labs CP210x USB to UART Bridge 6 Set the Baud rate to 115200 7 Click Apply 8 On the right of the page in th...

Page 62: ...UCXP683T V CARRIER CORPORATION 2021 Installation and Start up Guide All rights reserved 58 If you have problems mounting wiring or addressing the TV UCXP683T V contact Carrier Control Systems Support...

Page 63: ...MSTP Change MAC address to unique address using USB Service Port Blue 2 blink Controller has same MAC address as another connected device Duplicate address on MSTP Change MAC address to a unique value...

Page 64: ...uired Green 2 blink Download of driver is in progress Download in progress No action required Green 3 blink BACnet Device ID is not set Download required Download the controller Green Fast blink Insta...

Page 65: ...the Present Value The pulse pattern repeats after a 2 second delay LED will blink the number of times given in the BAO with ON pulse 0 5 seconds and OFF pulse 0 5 seconds To get a Module Status report...

Page 66: ...nfigured microblock A misconfiguration on the expander A missing or disconnected expander To check for errors 1 In the i Vu navigation tree select the equipment controlled by the 2 On the Properties p...

Page 67: ...in Max limits No Output Output s Hand Auto Off switch is in Hand or Off position The expander s Hand Auto Off switch is in the Auto position No Sensor No device is attached to the output The device is...

Page 68: ...ide circuit board See To get a Module Status report page 61 To replace the TV UCXP683T V s fuse The TV UCXP683T V has one fuse If the TV UCXP683T V s power LED is not lit this could be due to a blown...

Page 69: ...place the power connector 8 Verify the LEDs on the TV UCXP683T V are lit To revert to default settings WARNING This erases all archived information and user configuration settings When recovery is com...

Page 70: ...leshooting or start up you can prevent the i Vu application from communicating with the TV UCXP683T V by shutting down communication from the TV UCXP683T V to the i Vu application When Out of Service...

Page 71: ...radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception whic...

Page 72: ...and versions Reset Counters The number of times each of the following events have occurred since the last time the controller was commanded to clear the reset counters See NOTE below this table Power...

Page 73: ...ion 6 MB maximum contains data that does not need to be preserved through a power cycle such as status values that are calculated during runtime IP Networks BBMDs Shows the following information for e...

Page 74: ...m bend radius X TS BB O BM Wiring devices to the TV UCXP683T V Rnet Port Changed Rnet rate of communication from 115 kbps to 115 2 kbps X TS BB O Specifications Specified N O binary outputs 9 28 21 Ad...

Page 75: ......

Page 76: ...Carrier 2021 Catalog No 11 808 850 01 12 3 2021...

Reviews: