Addressing a network of controllers using the controller setup Local Network tab
TruVu™ UC561
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
13
Method 2: To address when you do not know the serial numbers
You will need physical access to each device so that you can press the DSC button on the bottom right of the TV-
UC561. This allows you to identify the device on the controller setup
Local Network
page.
1
Connect to the Service Port of one i-
Vu® XT or TruVu™ IP device on the network. Fo
r details, see
Addressing
the TV-UC561 through the Service port
(page 9).
2
Browse to the Service Port address (http://local.access or http://169.254.1.1).
3
On the
Ports
tab, set the device's
IP Address
,
Subnet Mask
, and
Default Gateway
.
NOTES
The other devices that you configure inherit this device's subnet mask and default gateway.
4
On the
Local Network
tab, click the
Clear
All
button to erase any pre-existing data in the
Local Devices
table.
5
On the controller you want to address, press the DSC button on the bottom right. When pressed, a row
appears in the
Local Devices
table on the
Local Network
tab. The row has a blue dot to indicate which
controller has just had the button pressed.
6
In the row for the identified controller, enter the
Address
and
Location
(optional).
7
Repeat steps 3 and 4 for each controller that you want to address.
8
For more details about discovering and configuring your devices, see
Local Network
tab
(page 45).
NOTE
To physically identify a device that is displayed on the
Local Devices
table, you can click the
Blink
button,
which causes that device's
Net
and
Sys
LEDs to flash light blue for 10 seconds.
The following are two possible methods you could use to identify and assign a network of controllers' addresses
after following steps 1 - 4 above.
•
Two technicians can work together if they are communicating throughout the process. The first technician
physically travels around the building to each controller, tells his co-worker exactly where he is, and then
presses the DSC button. The second technician, who is sitting at a computer connected to the controller,
watches for the blue dot to show up on the
Local Devices
table on the
Local Network
tab, where he can enter
the appropriate addressing and identifying information.
•
One technician alone can address the controllers on a mobile device showing the Local Network page by
plugging the Carrier wireless service adapter into a controller's Service Port. Then, with the computer, move to
each controller within 100 ft. of the adapter. Pressing the DSC button on the controller displays a blue dot in
the table where the addressing information can be entered.