Troubleshooting
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
73
To configure custom Prog 1/2 LEDs
You can customize the
Prog 1
and/or
Prog 2
LED for site-specific purposes by configuring the BACnet Analog
Output (BAO) microblock.
In the i-Vu® interface, select the TV-MPCXP1628-NR on the navigation tree, and on the
Properties
page >
I/O
Points
tab, under
Hardware Configuration
, set the following:
Status/Attribute
Microblock
type
Expander number :
Channel number
I/O type
Description
LED 1
BAO
0:61
Special
•
<=0 Normal
•
>15 On
The number of blinks equals the
Present Value.
The pulse pattern repeats after a
2-second delay
LED will blink the number of times
given in the BAO with ON pulse
0.5 seconds and OFF pulse 0.5
seconds.
LED 2
BAO
0:62
Special
•
<=0 Normal
•
>15 On
The number of blinks equals the
Present Value.
The pulse pattern repeats after a
2-second delay
LED will blink the number of times
given in the BAO with ON pulse
0.5 seconds and OFF pulse 0.5
seconds.
To get a Module Status report
A Module Status report provides information about the controller and verifies proper network communication with
the controller. You can get this report:
•
In the i-Vu® application
—
Right-click the controller on the navigation tree, then select
Module Status
.
•
On the controller setup
ModStat
tab
—
See
To set up the controller through the Service Port
(page 61).
See
Appendix - Module Status field descriptions
(page 81).
Summary of Contents for TruVu TV-MPCXP1628-NR
Page 2: ......
Page 4: ......
Page 93: ......
Page 94: ...CARRIER CORPORATION 2021 Catalog No 11 808 793 01 2 18 2021...