background image

Air Conditioners and

Heat Pumps Using

R-22 Refrigerant

Application Guide

and Service Manual

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .....................................................2

INTRODUCTION ..........................................................................2

INSTALLATION GUIDELINE ....................................................2

Residential New Construction ..................................................2
Add-On Replacement (Retrofit) ...............................................2
Seacoast (For Air Conditioners Only) .....................................2

ACCESSORY DESCRIPTIONS ...................................................2

Compressor Crankcase Heater..................................................2
Evaporator Freeze Thermostat..................................................2
Winter Start Control .................................................................2
Compressor Start Assist—PTC ................................................2
Compressor Start Assist—Capacitor/Relay..............................2
Low-Ambient Controller ..........................................................2
MotorMaster™ Control ............................................................2
Low-Ambient Pressure Switch.................................................2
Wind Baffle...............................................................................3
Coastal Filter.............................................................................3
Support Feet ..............................................................................3
Liquid-Line Solenoid Valve .....................................................3
Thermostatic-Expansion Valve.................................................3
Isolation Relay ..........................................................................3

LOW-AMBIENT GUIDELINE.....................................................3

LONG-LINE GUIDELINE............................................................3

Approved Systems ....................................................................3
Interconnecting Tubing Sizing .................................................3
Metering Device Sizing ............................................................5
Liquid-Line Solenoid And Tubing Configuration ...................5
Charging Information................................................................6
2–Speed Applications ...............................................................7

UNIT IDENTIFICATION .............................................................9

Product Number Stamped on Unit-Rating Plate......................9
Serial Number Identification ..................................................10

CABINET.....................................................................................10

Remove Top Cover-WeatherMaker™ ...................................10
Remove Fan-Motor Assembly-WeatherMaker™ ..................10
Information Plate—WeatherMaker™.....................................11
Control-Box Cover—Cube Products......................................11
Remove Top Cover—Cube Products.....................................11
Remove Fan-Motor Assembly—Cube Products....................11

ELECTRICAL..............................................................................12

Aluminum Wire ......................................................................12
Contactors................................................................................13
Capacitors................................................................................14
Cycle Protector........................................................................16
Crankcase Heater ....................................................................16
Time-Delay Relay...................................................................17
Pressure Switches....................................................................18

Defrost Thermostats................................................................18
Defrost-Control Board ............................................................18
Fan Motors ..............................................................................22
Service Alarm Control Board.................................................23
Outdoor Thermostat(s)............................................................24
Compressor Plug.....................................................................24
Low-Voltage Terminals ..........................................................24

RECIPROCATING COMPRESSOR ..........................................25

Mechanical Failures ................................................................25
Electrical Failures ...................................................................26
System Cleanup After Burnout ..............................................27
Compressor Removal And Replacement ...............................28

COPELAND SCROLL COMPRESSOR ....................................28

Features ...................................................................................28
Troubleshooting ......................................................................28
Discharge Thermostat .............................................................28
Discharge Solenoid Valve ......................................................29

MILLENNIUM SCROLL COMPRESSOR ................................29

Features ...................................................................................29
Compressor Protection............................................................29
Troubleshooting ......................................................................29
Scroll-Compressor, 3–Phase Monitor.....................................29

OLYMPIA SERIES HORIZONTAL UNITS .............................29

General ....................................................................................29
Remove Fan Motor.................................................................31
Cleaning Coil ..........................................................................31

TWO-SPEED SYSTEM ..............................................................31

Cautions and Warnings...........................................................31
System Functions ....................................................................31
Factory Defaults......................................................................34
Major Components..................................................................34
LED Function/Malfunction Lights .........................................36
Troubleshooting ......................................................................36

REFRIGERATION SYSTEM .....................................................38

Refrigeration Cycle.................................................................38
Leak Detection ........................................................................38
Brazing ....................................................................................39
Service Valves ........................................................................39
AccuRater™ (Bypass-Type) Heat Pumps Only ....................40
Reversing Valve......................................................................41
Thermostatic-Expansion Valves (TXV) .................................42
Thermostatic-Expansion Valve (Bi-Flow TXV)....................43
Coil Removal ..........................................................................43
Liquid-Line Strainer (Heat Pumps Only) ..............................43
Accumulator ............................................................................43
Contaminant Removal ............................................................45
System Charging.....................................................................45
Checking Charge.....................................................................45

CARE AND MAINTENANCE...................................................46

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

1

4

4

Tab

3a 5a 2a 5a

PC 101

Catalog No. 563-732

Printed in U.S.A.

Form 38-10SM

Pg 1

11-00

Replaces: 38-1SM, 38-16XA

Summary of Contents for R-22

Page 1: ...ctors 13 Capacitors 14 Cycle Protector 16 Crankcase Heater 16 Time Delay Relay 17 Pressure Switches 18 Defrost Thermostats 18 Defrost Control Board 18 Fan Motors 22 Service Alarm Control Board 23 Outdoor Thermostat s 24 Compressor Plug 24 Low Voltage Terminals 24 RECIPROCATING COMPRESSOR 25 Mechanical Failures 25 Electrical Failures 26 System Cleanup After Burnout 27 Compressor Removal And Replace...

Page 2: ...system clean up operate system for 10 hr Monitor pressure drop across drier If pressure drop exceeds 3 psig replace suction line and liquid line filter driers Be sure to purge system with dry nitrogen and evacuate when replacing filter driers Continue to monitor pressure drop across suction line filter drier After 10 hr of run time remove suction line filter drier and replace liquid line filter dr...

Page 3: ...speed products For applications involving 2 speed prod ucts refer to Step 6 first NOTE The presale literature for outdoor unit must be referred to in conjunction with this guideline Step 1 Approved Systems Any residential indoor outdoor unit combination listed in the outdoor unit presale literature is an approved system EXCEPT the following Indoor coils with capillary metering devices All equipmen...

Page 4: ...close cell insulation material specified for accessory tubing kits is a compound of vinyl neoprene or nitrile blends of these polymers Performance requirements include thermal range of 0 F to 200 F 17 8 C to 93 C and a maximum thermal conductivity of 0 28 NOTE Special consideration must be given to isolating intercon necting tubing from building structure Isolate tubing so that vibration or noise ...

Page 5: ... no change is required When sizing an accessory TXV for long line applications TXV should be the same nominal tonnage as outdoor unit Refer to presale literature for kit part numbers Step 4 Liquid Line Solenoid And Tubing Configuration There are 2 types of liquid line solenoids 1 for single flow applications and the other for bi flow applications The purpose of having 2 solenoids is to minimize th...

Page 6: ...tem charge is increased for long line applications it may be necessary to calculate the additional refrigerant charge Since long line applications only involve 3 8 in liquid lines the additional refrigerant charge required is 0 6 oz of Refrigerant 22 R 22 per ft of 3 8 in liquid line over 15 ft EXAMPLE To calculate additional charge required for a 25 ft line set 25 ft 15 ft 10 ft X 0 6 oz ft 6 oz ...

Page 7: ...16 24 3 4 16 3 16 8 1 4 29 13 16 27 13 16 33 15 16 31 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 31 13 16 29 13 16 35 15 16 33 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 33 13 16 31 13 16 37 15 16 35 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 35 13 16 33 13 16 Large 30 25 15 16 23 7 8 25 3 4 40 1 8 10 11 16 32 1 4 23 11 16 15 13 16 23 13 16 21 13 16 27 15 16 25 7 8 25 3 4 40 1 8 ...

Page 8: ...26 50 4 Table 8 Calculation of Outdoor Piston No OUTDOOR UNIT ABOVE INDOOR FT PISTON CHANGE 0 50 0 51 75 4 76 100 6 101 125 8 126 150 10 OUTDOOR UNIT BELOW INDOOR FT PISTON CHANGE 0 50 0 Table 9 Common Piston Sizes ACCURATER CHATLEFF ACCURATER CHATLEFF 32 65 65 33 67 67 35 35 68 36 70 70 37 71 38 38 73 73 39 74 40 40 76 76 41 78 78 42 42 80 80 43 81 45 82 82 46 84 84 47 86 86 49 49 88 88 51 51 89 ...

Page 9: ... Model Letters Identifies a specific product model Positions 6 7 and 8 Nominal Cooling Capacity in thousands Btuh Example 036 36 000 Btuh or 3 ton capacity Position 9 Not Used Ths position will contain a dash Position 10 Description C Canada L Limited Edition Position 11 Not Used Ths position will contain a dash Position 12 Electrical Characteristics Fig 4 Application with Air Conditioner Installe...

Page 10: ... 5 Manufacturing Site Example A Indianapolis E Collierville Positions 6 through 10 Serial Number CABINET Certain maintenance routines and repairs require removal of cabinet panels There are 4 basic cabinet designs for air condition ers and heat pumps See Fig 8 The horizontal discharge unit will be discussed in a separate section of this manual Step 1 Remove Top Cover WeatherMaker 1 Turn off all po...

Page 11: ...x Cover Cube Products This panel contains much of the same information as the informa tion plate mentioned previously but is designed only to cover the control box Step 5 Remove Top Cover Cube Products 1 Turn off all power to outdoor and indoor units 2 Remove 5 screws holding top cover to coil grille and coil tube sheet 3 Remove 2 screws holding control box cover 4 Remove 2 screws holding informat...

Page 12: ...re is used in the branch circuit wiring with this unit adhere to the following recommendations Connections must be made in accordance with the National Electrical Code NEC using connectors approved for aluminum wire The connectors must be UL approved marked Al Cu with the UL symbol for the application and wire size The wire size selected must have a current capacity not less than that of the coppe...

Page 13: ...r off use ohmmeter to check for continuity of coil Disconnect leads before checking A low resistance reading is normal Do not look for a specific value as different part numbers have different resistance values 3 Reconnect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to heat or cool Check voltage at co...

Page 14: ...it may explode START CAPACITORS AND PTC DEVICES Sometimes under adverse conditions a standard run capacitor in a system is inadequate to start compressor In these instances a start assist device is used to provide an extra starting boost to compressor motor The first device is called a positive temperature coefficient PTC or thermistor See Fig 13 It is a resistor wired in parallel with the run cap...

Page 15: ...orting a 15 000 ohm 2 watt resistor across terminals NOTE Some start capacitors already have a bleed resistor attached If so it will discharge itself over a short period of time 6 Run compressor 10 minutes Stop and allow unit to sit idle for 5 minutes 7 Check system pressure equalization 8 Attempt to restart without capacitance boost If PTC thermistor device is inadequate as start device a start c...

Page 16: ...erant does not migrate to and condense in compressor shell when the compressor is off This prevents flooded starts which can damage compressor Crankcase heaters come in 2 basic types wraparound bellyband type that is wrapped externally around compressor shell and insertion type that is inserted into compressor oil well in shell of compressor Both types are used in outdoor units On units that have ...

Page 17: ...compression shutdown thereby improving the efficiency of the system The sequence of operation is that on closure of the wall thermostat and at the end of a fixed on delay of 1 sec the fan relay is energized When the thermostat is satisfied an off delay is initiated When the fixed delay of 90 20 sec is completed the fan relay is de energized and fan motor stops If the wall thermostat closes during ...

Page 18: ... closed at 30 3 F and open at 80 5 F NOTE The defrost thermostat must be located on the liquid side of the outdoor coil on the bottom circuit and as close to the coil as possible Step 9 Defrost Control Board Solid state defrost boards used on heat pumps replace electrome chanical timer and defrost relay found on older defrost systems The defrost control board can be field set to check need for def...

Page 19: ...timing cycle setting Liquid line temperature rises to range where defrost thermostat contacts open Temperature range is from 75 F to 85 F Resistance goes from zero to when contacts open 8 If either opening or closing temperature does not fall within above ranges or thermostat sticks in 1 position replace thermostat to ensure proper defrost operation CES0110063 DEFROST CONTROL Some heat pumps built...

Page 20: ... is now operating in defrost mode Check between C and W2 using voltmeter as shown in Fig 21 Reading on voltmeter should indicate 24v This step ensures defrost relay contacts have closed energizing supplemental heat W2 and reversing valve solenoid O 11 Unit should remain in defrost no longer than 10 minutes Actual time in defrost depends on how quickly speed up jumper is removed If it takes 2 sec t...

Page 21: ...ee Fig 22 To upgrade to the new control you must have replacement defrost thermostat and harness kit See your replacement component representative for kit part number Defrost Settings The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on board see Table 12 between defrost cycles of 30 60 90 and 120 minutes factory set at 90 minutes To...

Page 22: ...ill enter a 1 1 2 in to 2 in long 3 8 OD stub prior to entering the coil There is only one stub tube per coil All other feeder tubes enter the coil directly The defrost thermostat attaches to this stub tube See Fig 23 Step 10 Fan Motors Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Motors are totally enclosed to increase reliability Th...

Page 23: ... Units with RLA of less than 14 amps will require 2 passes through the metallic loop Refer to Fig 25 or 26 for wiring connections for service alarm or service alarm with solid state cycle protector accessories when used NOTE The wire from the X terminal on the service alarm to L on the outdoor terminal board indoor terminal board and thermostat subbase is field supplied and wired when using defros...

Page 24: ... resultant pitted or discolored terminals are reduced The plug is oriented to the relief slot in the terminal box so the cover cannot be secured if wires are not positioned in slot assuring correct electrical connection at the compressor The plug can be removed by simultaneously pulling while rocking the plug However these plugs are specialized and vary in terminal orientation in the plug Therefor...

Page 25: ...il and so forth which could be contributing to the failure RUNS DOES NOT PUMP In this type of failure compressor motor runs and turns compres sor but compressor does not pump the refrigerant A clamp on ammeter on common leg of a single phase compressor or any 1 lead of a 3 phase compressor shows a very low current draw much lower than RLA rated load amps value stamped on compressor nameplate Becau...

Page 26: ... identification SINGLE PHASE MOTORS To identify terminals C S and R 1 Turn off all unit power 2 Short the run and start capacitors to prevent shock 3 Remove all wires from motor terminals 4 Read resistance between all pairs of terminals using an ohmmeter on 0 10 ohm scale 5 Determine 2 terminals that provide greatest resistance reading Through elimination remaining terminal must be common C Greate...

Page 27: ...all or part of the winding s be sure the following conditions are met 1 Correct motor winding resistances must be known before testing either from previous readings or from manufacturer s specifications 2 Temperature of windings must be as specified usually about 70 F 3 Resistance measuring instrument must have an accuracy within 5 10 percent This requires an accurate ohmmeter such as a Wheatstone...

Page 28: ... by debris liquid slugging and flooded starts Due to the design of the scroll compressor the internal compression components unload equalize pressure on shutdown The white oil Sontex 200LT used in the scroll is compatible with 3GS oil which can be used if additional oil is required See Table 14 for oil recharge requirements Step 2 Troubleshooting Troubleshooting mechanical or electrical problems i...

Page 29: ...d on the motor windings Internal protectors respond to overcurrent and high temperature These protectors are automatic reset devices containing a snap action bi metal switch Step 3 Troubleshooting Troubleshooting mechanical and electrical problems in a scroll compressor is similar to a reciprocating compressor except that a scroll compressor should never be allowed to pump into a vacuum The scroll...

Page 30: ... 32 CESO130075 3 Phase Monitor Wiring Diagram A00011 EQUIP GND CONT L1 COMP 11 21 T1 T2 T3 CH L2 L3 13 23 OFM CAP CONT L1 L3 L2 C Y CONT LOGIC CESO130075 CONT T2 T3 T1 LPS HPS LLS CTD IFR R C Y G R INDOOR THERMOSTAT EXTERNAL POWER SUPPLY 24 V LOGIC 30 ...

Page 31: ...terconnecting tubing lengths greater than 100 ft Do not decrease or increase interconnect ing tubing diameters To avoid electrical shock bleed resistor must be connected across run capacitor Replace if missing or damaged Contactor is mechanically interlocked Do not disable me chanical interlock Compressor damage may occur Contactor control voltage is 240vac Do not attempt to operate this equipment...

Page 32: ...wire between terminals 15 and 16 Heat Pumps After the termination of a defrost cycle the outdoor fan delays come on for 20 sec This allows the refrigeration system to recover the outdoor coil heat and minimize the steam cloud effect SECOND STAGE LATCHING When low speed cooling operation no longer satisfies the first stage of the indoor thermostat the indoor temperature will increase by 2 until sec...

Page 33: ...fies the thermostat To utilize this function the economic and or thermal balance point must be determined See the appropriate heat pump balance point work sheet available from your distributor or branch BALANCE POINT This feature can be used in 2 different options furnace interface or electric heat staging Refer to the Furnace Interface section for its application If the heat pump is installed wit...

Page 34: ...cu rate readings If a PTC trip occurs 3 times the control will lock out the outdoor unit operation and provide malfunction signals at both the control and indoor thermostat PRESSURE SWITCH PROTECTION The outdoor unit is equipped with high and low pressure switches wired in series If a pressure switch opens the control provides a 5 minute time delay in outdoor unit operation with the outdoor fan ru...

Page 35: ...rol The control defrosts every 90 minutes of heating operation and terminates in 5 minutes See Table 15 ICM OUTDOOR FAN MOTOR The outdoor integral control motor ICM is a variable speed motor which operates from 400 to 900 rpm The motor is a DC permanent magnet type motor with the electronic controls inte grated into its rear cover The control package includes a small diode bridge capacitors and po...

Page 36: ...e all capacitors 3 Remove wires from T1 T2 T3 T7 and T8 4 Allow crankcase heater to remain on for several hrs before checking motor to ensure that windings are not saturated with refrigerant 5 Using an ohmmeter on R X 10 000 ohm scale place 1 meter probe on ground motor or compressor frame Make a good metal to metal contact Place other probe on terminals T1 T2 T3 T7 and T8 in sequence Note meter s...

Page 37: ...R 25 15 C2 26 16 C2 22 12 C1 23 13 C1 C F C2 14 24 C2 L2 LS SR 2 5 1 SCHEMATIC DIAGRAM LADDER FORM Fig 43 High Speed Windings A91445 EQUIP GND SC 17 27 EXT MAIN 11 21 C1 L1 BR CAP H LOW START MAIN T2 T7 COMP T1 HIGH START T3 T8 2 5 1 HS SR 25 15 C2 26 16 C2 22 12 C1 23 13 C1 C F C2 14 24 C2 L2 LS SR 2 5 1 SCHEMATIC DIAGRAM LADDER FORM 37 ...

Page 38: ...ing unit through liquid line and enters metering device at indoor coil As it passes through metering device it becomes a gas liquid mixture As it passes through indoor coil it absorbs heat and refrigerant and is again compressed to a hot gas The cycle then repeats In a heat pump the basic cycle is the same See Fig 44 Reversing valve in system decides which coil indoor or outdoor becomes evaporator...

Page 39: ...er solder is used on copper to brass copper to steel or copper to copper Flux is required when using silver solder 4 Fluxes should be used carefully Avoid excessive application and do not allow fluxes to enter into the system 5 Proper brazing temperature of copper is when it is heated to a dull red color This section of brazing is not intended to teach a technician how to braze There are books and...

Page 40: ...s to 9 2 ft lb torque The seating surface of the valve stem has a knife set edge against which the caps are tightened to attain a metal to metal seal If accessory pressure switches are used the service valve must be cracked Then the knife set stem cap becomes the primary seal The service valve cannot be field repaired therefore only a complete valve or valve stem and service port caps are availabl...

Page 41: ...ng device check inlet and outlet line temperatures DO NOT touch lines If reversing valve is operating normally inlet and outlet temperatures on appropriate lines should be close Any difference would be due to heat loss or gain across valve body Temperatures are best checked with a remote reading electronic type thermometer with multiple probes Route thermo couple leads to inside of coil area throu...

Page 42: ...1 to 2 minutes Hard Shutoff HSO Has no bleed port and allows no bleed through after system shutdown No pressure equalization occurs Because of unequalized system pressures a start capacitor and relay must be installed on single phase reciprocating compressors to start the compressor See Table 21 for TXV superheat settings These settings are factory set and are not field adjustable Table 21 setting...

Page 43: ...efrigerant from system through service valves 3 Remove top cover See Remove Top Cover section 4 Remove screws in base pan to coil grille 5 Remove coil grille from unit 6 Remove screws on corner post WeatherMaker service valve panel Cube unit holding coil tube sheet Cut tubes to reduce the possibility of fire and personal injury 7 Use midget tubing cutter to cut liquid and vapor lines at both sides...

Page 44: ...K VALVE CLOSED BYPASS TUBE DISTRIBUTOR FEEDER TUBES CAPILLARY TUBE COIL BULB EXTERNAL EQUALIZER TUBE Fig 52 TXV in Heating Mode A88405 OUTLET INLET PUSHRODS BYPASS TXV DIAPHRAGM NEEDLE VALVE SPRING CHECK VALVE OPEN BYPASS TUBE DISTRIBUTOR FEEDER TUBES CAPILLARY TUBE COIL BULB EXTERNAL EQUALIZER TUBE 44 ...

Page 45: ...ng refrig erants If system has lost all charge weigh in charge using dial a charge or digital scale System charge should be fine tuned by using the superheat or subcooling method whichever is appropriate These methods are covered in the Checking Charge section below NOTE Heat pump check charts are for checking charge and performance and for adding a small amount of charge During heating mode corre...

Page 46: ...jury or death The minimum maintenance that should be performed on this equipment is as follows 1 Check outdoor coil for cleanliness each month during the heating heat pump only or cooling season and clean as necessary but clean at least once each heating heat pump only and cooling season 2 Check fan motor and blade for cleanliness each heating and cooling season and clean as necessary 3 Check elec...

Page 47: ...4 Subcooling at Liquid Service Valve for Units Produced Through December 1992 WEATHERMAKER AIR CONDITIONERS MODEL 38TG 38TH 38TK 38TKB 38TMA 38TM 38TR 38TD High Low SERIES 0 1 2 0 1 2 3 0 1 2 3 0 1 0 0 0 0 0 014 14 14 14 14 14 6 6 018 17 17 14 14 14 7 7 11 8 024 13 13 17 17 17 8 8 13 15 12 11 030 15 15 9 10 10 6 6 10 13 11 16 9 10 036 13 12 16 16 16 12 12 5 9 15 13 12 12 9 038 16 042 13 13 14 16 1...

Page 48: ...unit for leaks using an electronic leak detector 2 If any leaks are found recover or isolate charge pumpdown if applicable and make necessary repairs 3 Evacuate recharge and operate unit through entire cycle FINAL CHECKOUT After the unit has been operating the following items should be checked 1 Check that unit operational noise is not excessive due to vibration of components tubing panels etc If ...

Page 49: ...cating the unit on side of structure opposite the prevailing winds 2 Elevating the unit to height where drifting sand cannot pile up against coil Four in high mounting feet or an 18 in high mounting rack are available as accessories and can be used to elevate the unit 3 Addition of coastal filter see pre sale literature for accessory listing Special maintenance requirements are as follows 1 Freque...

Page 50: ...IR RESTRICTED OR RECIRCULATING RESTRICTED DISCHARGE TUBE OVERCHARGE OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE LOW SUCTION PRESSURE DIRTY AIR FILTERS DUCT RESTRICTED DAMPERS PARTLY CLOSED COMPRESSOR RUNS BUT CYCLES ON INTERNAL OVERLOAD COMPRESSOR RUNS BUT INSUFF...

Page 51: ...E RESTRICTED DISCHARGE TUBE OVERCHARGE OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR DEFROST RELAY N C CONTACTS OPEN MOTOR DEFECTIVE LOW SUCTION PRESSURE DIRTY AIR FILTERS DUCT RESTRICTED DAMPERS PARTLY CLOSED COMPRESSOR RUNS BUT CYCLES ON INTERNAL OVERLOAD COMPRESSOR RUNS BUT INS...

Page 52: ...OR KLIXON OPEN FAN MOTOR BURNED OUT DEFROST RELAY N C CONTACTS OPEN ON CIRCUIT BOARD REVERSING VALVE DID NOT SHIFT UNIT NOT PROPERLY CHARGED OUTDOOR FAN RUNNING REVERSING VALVE STUCK RESTRICTED LIQUID LINE PISTON RESTRICTED OR IS CLOGGED UNDER CHARGED OUTDOOR COIL DIRTY STRAINER RESTRICTED OUTDOOR COIL HEAVILY FROSTED DEFECTIVE DEFROST THERMOSTAT DEFROST THERMOSTAT IN POOR PHYSICAL CONTACT WITH TU...

Reviews: