Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
68
All rights reserved
Chilled Water Temperature Optimizer Reset
Navigation:
i-Vu®
Properties
>
Control Program
>
Chilled Water Temperature Optimizer Reset
Point Name/Description
Range
Optimizer Chilled Water Supply Reset Enable
— Displays status.
R:
Disabled/Enabled
Optimized Chilled Water Supply Setpoint AV
— Displays status.
Lock the CHWS temperature setpoint output __
D:
R:
Off
Off/On
To __ (Final setpoint, e.g., 44 degrees F)
CAUTION
Bypasses optimizer calculations.
D:
R:
44°F
40 to 50°F
16 CHWS STPT TEMP (REMOTE INPUT)
— Displays value.
Allows lockout if
Lock at value:
is checked. Allows communication if
Enabled?:
is
checked.
D:
D:
Unlocked (checked)
Enabled (checked)
16 CHWS TEMP (REMOTE INPUT)
— Displays value.
Allows lockout if
Lock at value:
is checked. Allows communication if
Enabled?:
is
checked.
D:
D:
Unlocked (checked)
Enabled (checked)
CHWR RETURN TEMP
— Displays value.
Total Chiller kW/ton
— Displays value.
Total Chilled Water Pump kW/ton
— Displays value.
Total Airside Fan kW/ton
— Displays value.
Total Chilled Water System kW/ton
— Displays value.
16 Optimized CHWS Reset Heartbeat ANO Minutes
— Displays value.
Allows lockout if
Lock at value:
is checked. Allows communication if
Enabled?:
is
checked.
D:
D:
Unlocked (unchecked)
Enabled (checked)
16 Optimized CHWS Setpoint ANO
— Displays value.
Allows lockout if
Lock at value:
is checked. Allows communication if
Enabled?:
is
checked.
D:
D:
Unlocked (unchecked)
Enabled (checked)