background image

19

• MODE changes to heat.

• OK-FAN turns off during normal shut down.

During normal compressor operation the minimum on time

is 5 minutes and the minimum off time is 5 minutes.
ECONOMIZER COOLING  — The  unit  diverts  condenser

inlet water flow through an optional economizer coil to precool

evaporator entering airflow. This occurs when there is demand

for the cooling, and the temperature at an entering water tem-

perature (EWT) thermistor is colder than the economizer start

set point. Water flow is controlled via two electronic water

flow valves. This option also incorporates an economizer

freeze sensor or switch (economizer temperature/freeze stat),

located at the inlet of the economizer coil.

Economizer water flow is in series with the condensers

allowing compressor operation while the economizer is

operating.

The equipment mode will change to "Free Cooling" if there

is no call for compressor operation, the fan is on, and there is

no demand for heat. If the unit is configured for variable flow

the reverse head pressure control valve will open (otherwise it

will already be open), and if there is condenser water flow, then

economizer cooling is enabled.

If the entering-water temperature is below the economizer

set point then the Mod. Econ Enabled point (ECONOK) will

change to enable and the economizer valve will modulate open

to lower the economizer control temperature to the supply air

set point temperature. The economizer modulation is con-

trolled by a PID loop and the reverse/head pressure control

valve will modulate in reverse of the economizer valve using

the formula MVLV = 100 - ECONO.
COOLING RESET — The controller can reset the supply air

set point using these two methods:
• An external 0 to 10 volt input reset

• The value of the space control point

The external 0 to 10 volt input reset is configured to produce

a 0 to 20 degree supply air reset over the 2 to 10 volt range. If

more than 1.8 volts is sensed on the input, this method of reset

takes priority over other methods.
NOTE: The reset from all methods may be limited from 0 to

20 F by the Maximum Reset set point.

The return-air sensor, space temperature sensor, or entering

water temperature input will be used as the space control point.

If this control input goes below the Occupied Cooling set point,

then for each degree that the point is below the set point value

the supply air set point will be reset by the value configured in

the reset ratio set point.
HEATING — The controller is configured to control either a

hot water/steam valve or electric heat through a modulating

0 to 10 vdc output.  A field-supplied and installed step sequenc-

er can convert the modulating signal into two, four, or more

discrete stages of control for non-SCR electric heat control.

For either method of heat to function, a space control point

must be configured in the custom configuration. This control

point comes from a return-air sensor or space sensor, or the en-

tering water temperature sensor.

 Whenever the space control point is below the occupied or

unoccupied heat set point the mode will change to heat and if

unoccupied the fan will be started. The heat control routine

uses a PID to control the heating output to maintain the supply

air set point.

When unoccupied heat is enabled the fan will be stopped

and the heat turned off when the space control temperature is

more than halfway above the difference between the occupied

heat set point and the unoccupied heat set point. For example,

if the occupied heat set point is 70 and the unoccupied heat set

point is 60 the unit will come on for unoccupied heating below

60 F and turn off again above 65 F.

HEAD PRESSURE CONTROL (HPC) — In  installations

where entering water temperature can fall below 55 F, where a

water economizer (described above) is not installed, the HPC

provides an electronic water flow control valves to vary flow to

the condensers. Controlling the water flow maintains

compressor discharge pressure above a minimum value, ensur-

ing sufficient refrigerant flow out of the condenser and

throughout the refrigerant circuit. Refrigerant pressure is mea-

sured at compressor circuit no. 1 by a discharge pressure sensor

(PRES).

The 50XJ units not equipped with a water economizer can

be ordered with the reverse/head pressure control valve factory

installed and a pressure transducer located in the discharge line

of compressor no. 1.

When the unit is operating, cooling is enabled, a compressor

is engaged, and the entering water temperature falls below

60 F, head pressure control will be enabled. The head pressure

control valve will modulate to keep the head pressure at the Re-

frigerant Head Pressure set point. The default set point is

225 psig and may be set from 200 to 300 psig. The minimum

output value for the head pressure control algorithm is 40% in

order to maintain a minimum flow through the condensers. The

valve will modulate between 40 and 100%.
VENTILATION REQUEST — The  ventilation  request  out-

put will close a set of relay contacts to activate a ventilation

damper whenever the supply fan and supply fan status are both

true and the unit status is occupied or override.
VAV TERMINAL OPERATION OUTPUT — The  VAV

terminal control output (TRMCT) closes a set of relay contacts

to indicate to non-Carrier air terminals that the fan is on and op-

eration has been verified. This signals the terminals to open and

start controlling to the desired cfm and temperature set points.
VAV TERMINAL OPEN OUTPUT — The  VAV  terminal

open output (TRMOP) closes a set of relay contacts to com-

mand the air terminals to open to maximum cfm at times when

the fan is operating on the VFD bypass.  This contact will close

30 seconds before the supply starts in bypass mode.
PUMP OUTPUT — The pump output closes a set of relay

contacts to indicate that the 50XJ unit is in operation and may

require condenser water flow through the unit.  This contact is

closed when the unit is not in heating mode and the supply fan

is operating.  This contact is also close if the economizer freeze

controls (described above) detects unacceptable conditions

with the unit configured without an air economizer or head

pressure control.
TOWER OUTPUT — The tower output closes a set of relay

contacts to start/stop tower controls. This contact closes when

the unit is not in heating mode and the supply fan is operating.
BUILDING PRESSURE CONTROL — The  building  pres-

sure control output provides an analog 0 to 10 vdc signal to

control return fan or exhaust fan speed. Fan speed is modulated

to maintain the building static pressure set point.

The control parameters for the building pressure set point

and building pressure are read and controlled in voltage but are

converted to inches of water for ease of setting and display. The

range and low start values of the sensor selected should be con-

figured in the setpoint screen, after the use of space static pres-

sure sensor has been enabled on the configuration screen.

Diagnostic Features — 

The controller and BACview

display provide a number of features to help protect the unit

and allow problem diagnosis.
CRITICAL FAULT — The controller provides an output (for

field connection) to signal an external building systems moni-

tor or control that the unit has a critical alarm that may be im-

pacting unit operation. The alarm lamp on the BACview dis-

play provides visual indication of this condition.

The BACview display allows the user to monitor alarms

and determine sensor input values.

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: