background image

18

OPERATION

Occupancy  Determination  — 

 The Omnizone™

controller allows several methods of occupancy determination,

based upon the setting of the occupancy configuration. Local

occupancy is determined by either a local schedule (Local

Sched) contained in the controller, the use of the ROCC dis-

crete input point (Remote DI) or by setting the unit configura-

tion to always occupied (Always Occ).

When the Omnizone unit is connected to a network, occu-

pancy can be controlled the occupancy configuration. To oper-

ate to a BACnet schedule, set the configuration to "BACnet

Sched." To use a remote On/Off signal from a building automa-

tion system, set the configuration to "BAS On/Off."

Fan Control — 

All variable air volume (VAV) units have a

variable frequency drive (VFD) to provide variable fan motor

speed and thus variable airflow. Fan control turns the fan on

and off based on unit operating mode, and controls fan speed to

maintain a particular duct static pressure at a duct static pres-

sure (DSP) sensor. The objective is to maintain a reasonably

constant supply-air exit velocity at VAV system outlet grilles,

regardless of damper opening positions. The duct static pres-

sure sensor is field-installed about 2/3 of the way toward the

"far end" of the ductwork. A duct high static (DHS) limit

switch provides protection by shutting the fan down if the duct

static pressure exceeds a maximum setting.

For the 50XJ unit, a VFD interface display is mounted in

the front of the unit. A number of user-adjustable features can

be entered/changed using the keypad on the display. These fea-

tures are described in detail in the VFD Control and Display

section.

Sequence of Operation — 

The following control

sequence of operation for the 50XJ unit describes the various

sequences that occur depending upon the way an operation is

triggered and which software control points are involved.
SUPPLY FAN — The supply fan is enabled whenever the unit

enters occupied mode. The fan is also enabled in the unoccu-

pied mode with a cooling or heating demand. Fan operation

will be prevented if there is an active duct high static pressure

alarm, the optional phase rotation monitor indicates a problem,

the duct static pressure sensor has failed or has an alarm, or

there is a fire/smoke shutdown alarm.

When there are no alarms preventing fan operation and the

fan is enabled, the (remote terminal control) TRMCT should

turn on. Thirty seconds later the output to the VFD will in-

crease. The VFD output level is determined by a PID calcula-

tion, based on the duct static pressure (DSP) input and the sup-

ply static pressure set point. Once the supply fan is running and

the static pressure increases above the supply fan status set

point the supply fan status point (SFS) will indicate ON.

The space temperature sensor point indicates the current

value of the sensor used to determine cooling/heating demand.

The sensor selection is based on the sensors installed and the

configuration of these sensors in the custom configuration. The

following sensors, when valid, are used for the space tempera-

ture sensor with the highest precedence at the top of the list:
• Space temperature sensor (SPT)

• Return air temperature sensor (MA_RA) - only used if

the unit is NOT configured for reset by EWT.

• Entering water temperature (EWT) - only if the unit is

configured for reset by EWT.

• Default with no sensors is the occupied cooling set point

of 10 F (prevents unoccupied operation).
If the space has unoccupied demand, the supply fan is en-

abled.  If conditions allow, the fan will start as described above.

If the fan is running due to unoccupied heating or cooling de-

mand, the controlling temperature input must rise or drop to

within half way between the occupied and unoccupied set

points in order for the fan to turn back off. 

Once the unoccupied conditions are satisfied, there is a

fixed 5-minute delay for normal fan shutdown. During the  5-

minute delay, the cooling and heating routines become dis-

abled. This delay allows a compressor that may have just start-

ed to run for its 5-minute minimum on-time with the supply fan

on. For example, if the staging routine had just started com-

pressor no. 3 at the time the call was satisfied, the cooling rou-

tine would become disabled and compressor no. 1 and 2 would

shut off right away. Compressor no. 3 would continue to run

for its minimum on time of 5 minutes. The fan continues run-

ning until all compressors meet the minimum on time and run

with a load, preventing them from shutting down due to a

safety.
Supply Fan operation with Optional Bypass — If the option-

al VFD bypass is installed and the bypass switch has been

turned to bypass (line), and the VFD compartment access panel

is in place, the software point VFD Access Panel Secure has

been set to YES, there are no faults to prevent fan operation

and there is a call for fan operation, then the bypass start stop

point BPS_S will be engaged to start the fan. The terminal

open point TRMOP will go on with the TRMCT point 30 sec-

onds before the fan starts.
COMPRESSOR COOLING — If the fan is on and there is no

demand for heat, internal software point (COOLOK) will

switch to on. The unit MODE will not change to "Cooling" unit

there is an active call for compressor operation. 

If the unit is configured for variable flow the reverse/head

pressure control valve will open (otherwise it will already be

open), and if there is condenser water flow (or no flow switch

installed), then mechanical cooling will be enabled.

Units are equipped with 2, 3, or 4 compressors piped in sep-

arate refrigerant circuits, and staged on/off in a fixed sequential

manner (compressor no. 1 through compressor no. 4). The

compressor control routine uses a PID calculation to determine

the percentage of cooling required, from 1 to 100%. Demand

for the PID calculation is determined from the supply air tem-

perature and the supply air set point.

Compressor cooling will be disabled for any of the follow-

ing reasons:
• There is no water flow (CDWF is off, with switch

installed).

• Economizer freezestat (FREEZ) has been in alarm for

more than 15 minutes.

Fig. 10 — Condenser Air Vent

a50-7124tf

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: