background image

CO2 Room Sensor with Temperature 

Installation and Operation

 

 
 

#NSA-HH/CO2-R2-CP-C, NSA-HH/CO2-R2O-CP-C, NSA-HH/CO2-R2SO-CP-C 

– 11/14/2019 

 

Specifications subject to change without notice. 

Catalog No. 11-808-794-01 

Page 

1

 of 

6

 

Overview 

 

The Carrier Carbon Dioxide Room Series Sensor with Temperature, Setpoint, and Override monitors the 
carbon dioxide (CO2) levels in commercial, school, and office-type environments. The concentration of 
CO2 is a strong indication of the overall indoor air quality. The NSA-HH/CO2-R2 Series is based on a 
single beam, non-dispersive infrared technology and is a cost-efficient solution for measuring carbon 
dioxide levels for building climate control. In addition, ABC software eliminates the need for manual 
calibration. Carbon Dioxide concentration is measured up to 2,000 ppm and is converted into 
proportional analog outputs. The factory default output is 4-20 mA, whereas 0-5 VDC and 0-10 VDC 
outputs are field selectable via integral dip switches. Thermistor temperature outputs, along with setpoint 
and override, are available as options for this configuration as well. The NSA-HH/CO2-R2 Series 
provides data which can be used in conjunction with a Building Automation System or Demand Control 
Ventilation to decrease energy consumption while creating a healthier indoor climate. 

Applications

: Schools, Office Buildings, Auditoriums, Gymnasiums, Shopping Malls, Theatres, Demand Control 

Ventilation & Economizers 

 

 

Part Numbers 

 

NSA-HH/CO2-R2-CP-C 

NSA-HH/CO2-R2O-CP-C 

NSA-HH/CO2-R2SO-CP-C 

 

 

Specifications 

 

Supply Voltage: 

24 VAC +/-20%, 50/60 Hz (half-wave rectifier) | 16.5-40 VDC Max. 

Power Consumption: 

3 VA for 24 VAC, 3W for 24 VDC (peak); <0.9W (average) 

Sensing Technology: 

Single beam infrared sensing technology (NDIR) 

Sensing Method: 

Diffusion 

Measurement Range Default: 

0 to 2,000 ppm 

Extended CO2 Ranges: 

Up to 10,000 ppm (factory set) 

Extended Range Accuracy: 

+/- 30 ppm and +/- 5% of reading 

CO2 Output Signal: 

Output 1

: 0-5 VDC or 0-10 VDC (Default) | 

Output 2

: 4-20 mA (500 Ohm Load maximum) 

Fail Safe: 

Polarity protected 

CO2 Accuracy

1

+/- 40 ppm +/- 3% of reading (@ 15-35°C; 20-70% RH and 101.3 kPa) 

Pressure Dependence: 

+ 1.6% reading per kPa (deviation from standard pressure 101.3 kPa) 

Response Time: 

≤ 2 minutes, diffusion 

Warm-Up Time: 

< 1 minute (@ full specs < 15 minutes) 

Temperature Accuracy: 

+/- 1°F (+/- 0.6ºC) 

Operating Temperature Range: 

32 to 122ºF (0 to 50ºC) 

Operating Humidity Range: 

0 to 95%, non-condensing 

Enclosure: 

ABS, Plastic, White, UL94-HB 

Sensor Coverage Area: 

7,500 sq. ft maximum 

Mounting Height: 

4-6 ft 

Sensor Life

2

> 15 years (typical) 

Calibration

3

 

ABC algorithm (Automatic Baseline Correction) 

Product Dimensions: 

(H) 4.50” (114.30 mm) x (W) 2.75” (69.85 mm) x (D) 1.12” (28.45 mm) 

Product Weight: 

0.230 lbs (0.104 kg) 

Agency Approvals: 

EMC Directive 2014/30/EC | RoHS Directive 2011/65/EU 

1

Accuracy is de-red after minimum three (3) ABC periods (1 period = 8 days) of continuous operations 

2

In normal indoor air quality (IAQ) applications | Corrosive environments are excluded 

3

Building CO2 levels must drop to 400 ppm same time during the week for ABC to work properly | If the building is occupied 24 hours / 

day, ABC must be turned off 

 

 

Summary of Contents for NSA-HH/CO2-R2-CP-C

Page 1: ...Numbers NSA HH CO2 R2 CP C NSA HH CO2 R2O CP C NSA HH CO2 R2SO CP C Specifications Supply Voltage 24 VAC 20 50 60 Hz half wave rectifier 16 5 40 VDC Max Power Consumption 3 VA for 24 VAC 3W for 24 VDC peak 0 9W average Sensing Technology Single beam infrared sensing technology NDIR Sensing Method Diffusion Measurement Range Default 0 to 2 000 ppm Extended CO2 Ranges Up to 10 000 ppm factory set Ex...

Page 2: ...ttom View Figure 1 Installation PRECAUTIONS Remove power before wiring Never connect or disconnect wiring with the power applied Do not allow live wires to touch the circuit board An isolation transformer is recommended when powering the device with 24vac Do not run the wiring in any conduit with line voltage Failure to wire devices with the correct polarity when using a shared transformer may res...

Page 3: ...er supply has to be connected to VIN and COM COM is considered as system ground 1 Mount the wall plate Run the wires from the back of the wall plate and through the square wire hole in the PCB Mount the wall plate to the wall being careful not to trap wires between the wall and the plate 2 Configure DIP switches The default setting is 0 10 VDC output switch 1 on and ABC on switch 2 on For 0 5 VDC ...

Page 4: ...int if these configurations are used Figure 4 Power Supply The power supply has to be connected to VIN and COM COM is considered as system ground The same ground reference has to be used for the NSA HH CO2 R2 unit and for the DDC signal receiver Connections of the main terminal of NSA HH CO2 R2 Shielded cable with 16 to 22AWG conductors is recommended The cover must be removed to wire the unit s t...

Page 5: ...ge reference VOUT 4 20mA Analogue output 1 Analogue output 2 0 5 VDC or 0 10 VDC 4 to 20mA 0 2000 ppm CO2 0 2000 ppm CO2 4 Attach and secure cover There are two tabs on the top of the cover that fit into slots on the top of the wall plate Begin with the cover above the wall plate with the bottom of the cover angled out from the wall plate Move the cover down to seat the tabs and then push the bott...

Page 6: ...ce Calibration The NSA HH CO2 R2 is basically maintenance free in normal environments thanks to the built in self correcting ABC algorithm The ABC logic may need to be turned off in some applications such as those with continuous occupancy Discuss your application with ACI in order to get advice for a proper calibration strategy NOTE The sensor accuracy is defined at continuous operation at least ...