62-61753-21
7-95
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
249 MICROPROCESSOR ERROR
TRIGGER-ON: Microprocessor Input Conversion Error.
UNIT CONTROL: Shutdown and alarm.
RESET CONDITION: Auto Reset when input conversions are valid, or Alarm may be manually
reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any
active alarm occurs. Continue with the steps below as necessary.
1
Check Microprocessor
a. Check Temperature Sensor Data
Must be valid reading for RAT, SAT, AAT, etc.
b. Check for any Active Sensor
Alarms
Must all be cleared.
2
Check Microprocessor & Unit Wiring
a. Check Wiring to Micro and at input
devices to the micro.
Must not be miss wired to allow 12 VDC on any of the
sensor input circuits.
3
Reset Microprocessor
a. Turn START/RUN-OFF switch off
for 30 seconds, then turn back on.
Microprocessor powers up OK
b. Alarm 249 remains active.
Replace microprocessor. Refer to Section 5.4
Summary of Contents for NDK33BN0KB
Page 2: ......
Page 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Page 4: ......
Page 14: ......
Page 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Page 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Page 30: ...62 61753 21 2 6...
Page 48: ......
Page 212: ......
Page 226: ......
Page 248: ......
Page 252: ......
Page 262: ......
Page 270: ......